PROGRAM NUMBER OF LINEAR SEGMENTS
This programming step loads in the number of linear segments desired for
multisegment linearization. If single slope scaling is desired, program
“1”
for
this step. If two segments are desired, program
“2”
, etc. You must have one more
scaling point known than the number of segments selected
(ie. 1 segment = 2
points, 2 segments = 3 points, etc)
. This step may also be used to deactivate
previously programmed segments where lower segments would override higher
segments.
(ex. changing “SEGt” from 5 to 3 causes slopes 4 & 5 to be replaced
by an extension of slope 3).
“SEGt” < > “1 - 9”
If
“1”
was selected, the indicator will return to
“Pro 0”
since scaling for the
first slope was already completed. Otherwise, a choice of either returning to
“Pro
0”
or commencing with the multislope-linearization scaling is offered.
“SCALE” < > “yES”
“NO”
If
“yes”
was selected, the display value for the third point is entered.
Otherwise, the indicator returns to
“Pro 0”
.
KEY-IN DISPLAY VALUE FOR SCALING POINT #3
“dSP 3”< >“-99999” to “99999”
KEY-IN INPUT VALUE FOR SCALING POINT #3
“INP 3”< >“0.000 to 5.000 AMPS AC”
The sequence of entering display and signal values continues with
“dSP 4”,
“INP 4”, “dSP 5”
, etc. until the number programmed for
“SEGt”
is reached. It is
recommended that the scaling be checked by exiting the programming mode and
applying signal values and verifying for correct display values.
Note: As the “UP” or “DOWN” button is continually held in, the display will
progressively increment faster until the fourth most significant digit is
changing at a rate of one number per second.
-9-