3. After selecting two areas the screen goes to statistics
13- Temperatures
14- Burner – fuel consumption
15- amount of burned Kg or Kg/h
16- first range of statistics
17- second range of statistics
min – minimum temperature
avg – average temperature
max – maximum temperature
The history of the installation operation is updated every 1 minute. The maximum history memory capacity is 10
days. By using the menu visible on the right-hand side of the screen, it is possible to hide unnecessary charts.
This increases legibility of information on the screen. After selecting the data range, the controller calculates the
average value for the data. It is possible to compare two different time periods (e.g. boiler room operation on a
Monday and on a Tuesday) to analyze the influence of control settings on fuel consumption. The controller
shows total fuel consumption in a given period and average burning per hour. Moreover, data (work history)
can be saved to an SD card and analyzed on a PC.
SUMMER/WINTER modes
Select the operating mode. This option chooses the operating mode though it is possible to choose the AUTO
mode (more on SUMMER/WINTER/AUTO).
Manual mode
The manual control mode is used to check devices and sensors connected to the regulator.
Manual control
This allows forcing operation of particular devices. The knob is used to select a device. The operation state of a
device is made by pressing the knob. The knob can be also used to set fan power.
The v31.09 software version (and higher) include information about the number of revolutions per minute if the
Hall generator is working and connected. This information is shown on the rpm symbol. Sample screens:
If the Hall generator is not connected or it is damaged, the rpm symbol is replaced with red lines.