background image

HEATSEEKER

®

GAS FIREBOX

INSTALLATION & OPERATING MANUAL

The Heatseeker Gas Firebox is approved to be installed into a masonary

fireplace and as a zero clearance firebox and is designed to operate on

Natural Gas and Propane (LPG) gases ONLY. Approval Number 6094.

Installed primarily as a decorative appliance. Not certified as a Space Heater.

VERSION 13

Summary of Contents for HEATSEEKER 700

Page 1: ...Firebox is approved to be installed into a masonary fireplace and as a zero clearance firebox and is designed to operate on Natural Gas and Propane LPG gases ONLY Approval Number 6094 Installed primar...

Page 2: ...N OPERATION CARE MUST BE TAKEN TO ENSURE THAT ANY RETURN AIR REGISTER OR EXHAUST SYSTEM DOES NOT ADVERSLEY AFFECT THE OPERATION OF THE APPLIANCE OR DRAUGHT OF CHIMNEY OR FLUE INSTALLATION NOTICE The i...

Page 3: ...16 Zero Clearance Model Components 17 Zero Clearance Model Assembly 18 Zero Clearance Model Installation Procedure 19 Lighting instructions 20 Commissioning 21 Optional Power Flue 22 Introduction 22 I...

Page 4: ...ODEL NATURAL GAS LPG UNIT Inj Size MJ Hr P T P Inj Size MJ Hr P T P 540 2 x 2 2 37 0 8 kPa 2 x 1 1 31 2 6 kPa 750 2 x 2 5 39 0 63 kPa 2 x 1 2 36 2 55 kPa 600 700 850 1000 4 DATA PLATE Affixed to burne...

Page 5: ...ng installed should be installed using a gather single skin flue and AGA approved gas cowl If the flue is to be exposed or enclosed with any combustible material the appropriate approved twin skin flu...

Page 6: ...6 E J H H FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 600 Heatseeker 600 Trim A B C D E F 790 800 740 670 100 75 A B C D E F G H 670 740 370 610 605 130 330 365 I J K L 380 150 65 60...

Page 7: ...E H J FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 700 Heatseeker 700 Trim A B C D E F 890 800 840 670 100 75 A B C D E F G H 665 830 370 710 605 130 330 365 I J K L 380 150 65 60 7...

Page 8: ...E H J FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 850 Heatseeker 850 Trim A B C D E F 1040 800 990 670 100 75 A B C D E F G H 665 980 370 860 605 130 330 365 I J K L 380 150 65 60 8...

Page 9: ...J H E B A FRONT 3 SIDED FRONT 4 SIDED D C F DIMENSIONS Heatseeker 1000 Heatseeker 1000 Trim A B C D E F 1190 800 1140 670 100 75 A B C D E F G H 665 1130 370 1005 605 130 330 365 I J K L 380 150 65 60...

Page 10: ...J FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 600 ZC Heatseeker 600 ZC Trim A B C D E F 790 800 740 670 100 75 A B C D E F G H 665 730 415 675 235 650 I J K L 380 150 65 60 10...

Page 11: ...J FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 700 ZC Heatseeker 700 ZC Trim A B C D E F 890 800 840 670 100 75 A B C D E F G H 665 830 415 775 235 650 I J K L 380 150 65 60 11...

Page 12: ...J FRONT 3 SIDED FRONT 4 SIDED E B A D C F DIMENSIONS Heatseeker 850 ZC Heatseeker 850 ZC Trim A B C D E F 1040 800 990 670 100 75 A B C D E F G H 665 985 415 930 235 650 I J K L 380 150 65 60 12...

Page 13: ...J E B A FRONT 3 SIDED FRONT 4 SIDED D C F DIMENSIONS Heatseeker 1000 ZC Heatseeker 1000 ZC Trim A B C D E F 1190 800 1140 670 100 75 A B C D E F G H 665 1130 415 1075 235 650 I J K L 380 150 65 60 13...

Page 14: ...1 Remove box containing logset and unpack Place the large log at the rear of the burner just in front of the 2 square tabs on the log support panel Figure 2 Place the 14 large coals and 8 small coals...

Page 15: ...ll the metal angle at the rear of the fireplace and place one row of pebbles behind the burner rail Figure 6 Place pebbles between the first row and the angled tray Figure 7 Place remaining pebbles up...

Page 16: ...e frame is suitable for fire weight HEATSEEKER ZERO CLEARANCE MODEL MODEL A B C D 600 750 750 450 2100 700 750 850 450 2100 850 750 1000 450 2100 1000 750 1150 450 2100 Frameout Dimensions in mm IMPOR...

Page 17: ...to suit the Heatseeker model you are fitting This should be fitted to the firebox as shown on page 10 Components No Description Qty 1 Panel Base 1 2 Panel Side LH 1 3 Panel Side RH 1 4 Panel Rear 1 5...

Page 18: ...n base panel and secure 3 Secure gather Item 6 to main fire box 2 Secure side strips Item 7 and top strip Item 8 to main fire box ITEM 1 ITEM 7 ITEM 8 ITEM 7 ITEM 6 4 Secure LH and RH side panels Item...

Page 19: ...mm minimum above roof line Min total flue run 3 6m Plaster to unit with trim removed Install trim Assemble unit as per page 18 Test the unit for safe operation and show customer correct operating proc...

Page 20: ...and turn the gas control knob anticlockwise to the pilot position 2 Keep knob depressed and turn the knob anticlockwise toward the until you hear a click If the pilot lights continue to depress knob f...

Page 21: ...re they continue to function satisfactorily as multiple flues can work against one another If spillage is detected during this procedure it could indicate a faulty flue or lack of ventilation If the p...

Page 22: ...flue motor this access MUST be at least 400mm x 400mm There MUST be a minimum clearance of 250mm between the top of the motor and any fixed object i e ceiling or stud work This is so the top of the f...

Page 23: ...tilation 500mm ELECTRICAL SHOULD THE SUPPLY FLEX AT THE BACK OF THE FIREBOX BE DAMAGED A SPECIALLY PREPARED FLEX IS REQUIRED FOR REPLACEMENT CONTACT THE MANUFACTURER THE ON OFF WALL SWITCH MUST NEVER...

Page 24: ...equivalent to the inner flue spigot diameter of the firebox the top of the muffler has a 150mm spigot which the motor fits to or the 150 200 twin skin flue if required The flow arrow on the muffler is...

Page 25: ...e 250mm Minimum height 150mm 200mm twin skin flue optional for additional height OPTIONAL POWER FLUE continued Ensure there is adequate ventilation within this cavity to prevent motor over heating Mot...

Page 26: ...400mm Access Panel D A C B 90mm x 38mm ON EDGE IMPORTANT Install unit and fluing before plasterboard MODEL A B C D 600 750 750 450 1800 700 750 850 450 1900 850 750 1000 450 2100 For Heatseeker 600 7...

Page 27: ...200mm twin skin flue if required 150mm x 200mm flue extension 300mm min 900mm Min Distance Domestic 220mm Industrial 320mm 200mm 500mm 25mm Termination Top Termination Flue Access Panel OPTIONAL POWER...

Page 28: ...skin flue if required 150mm x 200mm flue extension 900mm 200mm External Motor 340mm 25mm clearance Miniumum 1290mm External Motor 28 OPTIONAL POWER FLUE continued Fan Box Dimensions A B C D E F G H 30...

Page 29: ...solenoid valve 2 Dungs DGAI 73 Module 5 1 3 3 Electronic Ignition Sparker 4 Electronic Flame Sensor 5 Ecofit 2GTA35 Motor Complete with sail switch 6 900mm Real Flame Power Flue Muffler LED Indicator...

Page 30: ...ront of burner B The power polarity is reversed Check polarity B Sparker is to far from metal C Pressure switch Power Flue is not operating correctly Adjust sparker so it cross lights to metal Remove...

Page 31: ...red LED light that indicates the possible cause of a problem the LED light will flash in different sequences for different problems the most common are Long Flash Short Flash 1 0 Normal Running State...

Page 32: ...lator SC 75 03N S I T ODS Pilot Assembly Natural Gas 03P S I T ODS Pilot Assembly Propane Gas 04 1 2 Male to 1 2 Copper Union 05 1 2 to 3 8 Hex Nipple 06 5 16 90O Union Elbow 07 1 4 Nut and Olive 08 I...

Page 33: ...A trafficable roof designed for personal or public use the end of the flue shall be at least 2 meters above the roof level This dimension is to be increased where necessary so that the minimum distanc...

Page 34: ...1 Install Heatseeker with trim in place 2 Install marble over trim up to the fire opening Use liquid nails to fix to wall Marble should look like the diagram below once it has been installed and befo...

Page 35: ...0 235 Adelaide Federation 1460 1300 1170 950 950 235 Windsor Universal 1810 1665 1180 1090 860 280 100 80 Bouvier Universal 1810 1665 1180 1090 860 280 100 80 Kensington Universal 1810 1665 1180 1090...

Page 36: ...ELECTRICAL DIAGRAM Earth Green Lo Off Hi 3 pin plug Active Brown Common Blue Low Red High White Common Black Motor Switch 2 Pole 3 Position Lo Off Hi 36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Page 40: ...Showroom 654 Pacific Highway Chatswood NSW 2067 Ph 02 8905 0189 Fax 02 8905 0192 E mail info realflame com au Miranda NSW Showroom 36 Kareena Rd Miranda NSW 2228 Ph 02 8513 6202 Fax 02 9520 1974 E ma...

Reviews: