IMPOSTAZIONE DEI PARAMETRI ALLARME
IMPOSTAZIONE DEI PARAMETRI SIFONE
SETTING THE ALARM PARAMETERS
SETTING THE SIPHON PARAMETERS
stal
mntc
stal
mntc
Modify
- Modifica
Description
Descrizione
Min
Max
Def.
tmc0
Set maximum condensation temperature
(° C)
tmc0
Imposta Temperatura massima di
condensazione (° C)
45.0
65.0
55.0
dh20
Set H2O High Temperature Alarm Delay
(seconds)
dh20
I mposta R itardo Allar me Alta
Temperatura H2O (secondi)
0
900
120
dgas
Set Temperature Delay Mancanca Gas (° C)
dgas
Imposta Delta temperatura Mancanca
Gas (° C)
0.0
15.0
5.0
dven
Set Fan Alarm Activation delay (seconds)
dven
Imposta Ritardo Attivazione Allarme
Ventilatori (secondi)
0
900
120
hH20
High Temperature Alarm Set
hH20
Set Allarme Alta Temperatura (° C)
0.0
35.0
27.0
siph
antc
sif0
antc
Modify
- Modifica
Description
Descrizione
Min
Max
Def.
enct
Set type of Siphon Check
Off / Modu / stop
enct
Imposta tipo di Controllo Sifone
Off / Modu / stop
OFF
MODU
STOP
MODU
tmrc
Set the interval for checking the drain
procedure (minutes)
tmrc
Imposta l’intervallo di controllo della
procedura di scarico (minuti)
0
120
40
stun
Set the duration of the siphon discharge
procedure (minutes)
stun
Imposta la durata del ciclo della
procedura di scarico sifone (minuti)
0
300
25
uctr
Set the fan rpm control threshold (rpm)
uctr
Imposta la soglia di controllo giri del
ventilatore (rpm)
0
999
300
bps1
Proportional Term (PID) for fan speed
control
bps1
Azione Proporzionale (PID) per il
controllo velocità del ventilatore
0
9999
100
tis1
Integrative Term (PID) for fan speed
control
tis1
Azione Integrativa (PID) per il controllo
velocità del ventilatore
0
999
300
mspe
Minimum fan speed limit during the
procedure (%)
mspe
Limite minimo della velocità del
ventilatore durante la procedura (%)
0
100
22