Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
32
0.4
Choice of safety edge
input
(X12)
and/or
photocell
input
(X10)
in
case
of fire
.1 Disable safety edge and photo cell
.2 Turn off photo cell.
Enable safety edge. Stop if safety edge is
activated and after set time (parameter 0.5)
continues to close.
.3 Turn off photo cell. Enable safety edge If
power supply is still present, open completely,
and if power supply is not present reclose after
set time (parameter 0.5).
.4 Disable safety edge. Enable photocell.
Stop when Photocell is activated and continue
closing after set time (parameter 0.5).
.5 Disable safety edge. Enable photocell If
power supply is still present, open completely,
and if power supply is not present stop and
reclose after set time (parameter 0.5).
.6 activate safety edge and photo cell.
Stop when Photo Cell is activated and continue
closing after set time (parameter 0.5).
.7 Enable safety edge and photocell If power
supply is still present, open completely, and if
power supply is not present reclose after set
time (parameter 0.5).
0.5
Reclose time in case of
fire after activation
safety edge and/or photo
cell
2 t/m 60 seconds
3
sec.
0.6
Action when reaching
pre end position
closed
.1 Stop if safety edge is activated
.2 Disable/ignore safety edge
0.7
Return time safety edge
closing direction
.0
±
50ms
.1
±
120ms
.2
±
220ms
.3
±
480ms
0.9
Type limit switch
.0 Automatically
.1 DES GFA
.2 DES Kostal
.3 NES
* Check the door if it does not exceed the maximum permissible compressive force in case of a
entrapment! If the remote control does not have sight on the door then set to parameter. 3. If the
entrapment protection is activated/defective, the door will no longer close with the remote control.