Protections
The control has the ability to connect an safety edge. This can be an opto sensor, 1K2 air pressure
contact or an 8K2 contact. It can be connected to X12. Parameter 0.3 can be chosen whether it is
automatically detected or the connected security can be fixed. If no security is detected with
startup error message 2.0 appears on the display. If there is chosen to close hold to run in normal
operation there will appear once an error message 2.0. If automatic closing is selected, this will be
repeated continuously.
Parameter 0.3 can be used to set the function of the safety edge in normal operation. At factory
defaults, the door stops and then opens completely. Option 2 can be chosen to stop if the safety
edge is activated and then a needs a new command to move the door further.
Applies only when an OSE light list/curtain is connected.
Parameter 0.4 can be used to set the function of the safety edge and/or photocell protection when
closing with fire alarm or smoke detection, or if it is chosen to close at low battery voltage
(parameter 3.7 set to 2). If the voltage is below the voltage set to parameter 3.8. At factory setting
(option 1), the safety edge is disabled. With option 2, 4 and 6, the door or roller shutter stops with
closing and waits a set time (parameter 0.5) and then closes further. With option 3, 5 or 7 the roller
shutter (if the mains supply is still present), waits for the time set to parameter 0.5 and then closes
again. If the mains supply is not present, the door/shutter stops and continue to close after the set
time ( parameter 0.5). For option 2, 3, 6, and 7, safety edge is turned on, and Option 4, 5, 6, and 7
enables the Photocell protection.
Parameter 3.6 can be chosen to disable the safety edge and/or photocell if it is not present or
interrupted when the fire alarm, smoke detection or low voltage becomes active.
With parameter 3.5, you can limit the number of stops by the safety edge or photocell. If this is
chosen, parameter 3.9 sets that the safety edge or photocell can be ignored if the maximum number
of attempts is reached (i.e. to close without an safety edge or photocell) or that the door or shutter
is sent up 2 seconds and then stops or stops immediately.
The photocell only works with normal operation if automatically Closing is selected. The door or
roller shutter will stop if it is activated and then open fully .
10.6
Impulse function
An impulse input is available on the controller. If in hold to run, the impulse must be held in that .
When it is released, the motor stops. If it is pressed again, the other direction is active.
If automatically-Opening is selected, the door will ( according to factory settings) run until the
limit switch open is reached and can then be sent back down by the impulse input. By converting
parameter 2.2 to setting 2, the door can also be stopped during open running by activating the
impulse input again. At the next activation of the impulse input, the door is in hold to run as long
as the impulse input remains active.