System Registers
Input Registers
Tag
Address
Type
Function
Code to
Read
Function
Code to
Write
Size Notes
Packed Status
31000
Unsigned
Integer
4
N/A
1
0- OK
1- Alarm 1
2- Alarm2
3- Alarm3
4- Fault
5- Warmup
6- Inhibited
7- Zero Calibration
8- Calibration Span
9- Calibration Purge
10- Calibration Mode
11- Diagnostics Mode
12- Value Error (Calibration needed or
Channel State Over range)
13- Sensor Error
(Channel State Corrupted,
Channel State Over range,
Channel State Mismatch,
Channel State No Sensor,
Channel State Sensor Error,
Channel State Comm Error,
Channel state Scaling Error)
Analog Output
31001
Unsigned
Integer
4
N/A
1
12-bit value;
800 = 4mA;
4000 = 20mA
Sensor Life
31009
Integer
4
N/A
1
16-bit signed integer 1 to 100
1 indicates Calibration Required
Temperature
31011
32-Bit
Floating
Point
4
N/A
2
16-bit integer 1 to 4095
scaled for - 55°C to +125°C
4-20mA(mA)
31210
32-Bit
Floating
Point
4
N/A
2
32-bit floating point
Bridge Supply(V) 31220
32-Bit
Floating
Point
4
N/A
2
32-bit floating point
Bridge Out(V)
31224
32-Bit
Floating
Point
4
N/A
2
32-bit floating point
Version
32002
Unsigned
Integer
4
N/A
1
Factory use only
Summary of Contents for 10-0517
Page 4: ...UM 1096 Revision A III Drawings 44...
Page 10: ...UM 1096 Revision A 5 Figure 2 Remote Sensor Enclosure Mounting Dimensions...
Page 26: ......
Page 49: ...UM 1096 Revision A 44 Appendix 9 Drawings Drawings Figure 13 Mounting Dimensions...
Page 50: ...UM 1096 Revision A 45 Figure 14 10 0517 CPU Board Figure 15 10 0533 I O Board...
Page 51: ...UM 1096 Revision A 46 Figure 16 10 0532 Modbus Relay Board...