FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
NOTE: Shut off valves and unions should be installed
at the inlet and outlet connections of the boiler/hot
water heater to provide for isolation of the unit should
servicing be necessary.
Freeze Protection
This boiler/water heater is CSA designed certifi ed for out-
door installation. Outdoor installations in areas where the
danger of freezing exists are not recommended unless
proper freeze protection is provided. The following
precautions MUST be observed:
1. A continuous fl ow of water through the unit MUST be
maintained! The pump responsible for fl ow through the
boiler/water heater must run continuously!
2. An ethylene glycol/water mixture suitable for the
minimum temperature that the unit will be exposed to
must be used. The pump must be capable of producing
a minimum of 15% more fl ow and overcoming a 20%
increase in head loss. Domestic water systems must be
isolated from the water heater by the use of a heat
exchanger or other approved method.
3. If the unit must be shut off for any reason the electric,
gas and water supplies MUST be shut off and the unit
and its pump completely drained.
Figure 12 – Futera II Piping
CAUTION: Improper outdoor installation of this unit
can cause boiler failure voiding the manufacturer’s
warranty!
Relief Valve
Pipe the discharge of the pressure relief valve as shown
in Figure 12.
WARNING: Never install any type of valve between
the boiler/water heater and the relief valve or an
explosion causing extensive property damage,
severe personal injury or death may occur!
Flow Switch
The fl ow switch supplied with the boiler/water heater must
be wired to the terminal strip in the control panel to prevent
the boiler from fi ring unless there’s adequate water fl ow
through the unit. The fl ow switch must be installed in the
supply piping adjacent to the boiler outlet connection.
CAUTION: Failure to properly install the fl ow switch
may result in damage to the boiler/water heater heat
exchanger voiding the warranty!