4.1 DALI Wiring Instructions

Cross section in mm

2

Maximum cable length L in m

25°C

50°C

75°C

0.14

31

28

26

0.50

112

102

93

0.75

168

153

140

1.00

224

204

187

1.50

300

300

281

2.00

300

300

300

2.50

300

300

300

5. Troubleshooting

1.  Ensure the two LED boards are correctly wired to terminal block. Red to Red : Black to 

Black – paired cables

2.  Ensure Mains input is correctly connected. 

3.  Ensure Mains Input is turned on at the source.

4.  If LED panel fails to light is it possible to identify if problem is with LED panel or power 

supply by swapping LED cables to opposite power supply to help identify problem.

Max number of fittings allowed per MCB 

MCB Type

Rating

SPZ/SPX-HP10K

(120W Version)

SPZ/SPX-HP15K

(180W Version)

SPZ/SPX-HP20K

(240W Version)

SPZ/SPX-HP25K

(300W Version)

B

10A

4

3

2

1

B

16A

10

6

4

3

B

20A

12

7

5

4

B

25A

15

10

7

6

C

10A

8

5

4

3

C

16A

16

8

6

5

C

20A

20

10

8

6

C

25A

26

16

13

9