50
Item
Application
Range
Description
Default
TARGET
H MODE 1, 2, 3
RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
SETP
MODE
H MODE 1, 2, 3
1,2,3
Piping and application configuration
1
SETPOINT
H MODE 1, 2, 3
50°F to 200°F (10°C to 93°C)
Heater target temperature while a heat demand is present for setpoint
operation
180°F (82°C)
OUT START
H MODE 1, 2, 3
35°F to 85°F (2°C to 29°C)
Outdoor starting temperature - outdoor reset
70°F (21°C)
OUT DESIGN
H MODE 1, 2, 3
-60°F to 45°F (-51°C to 7°C)
Outdoor design temperature - outdoor reset
10°F (-12°C)
Boil START
H MODE 1, 2, 3
35°F to 150°F (2°C to 66°C)
Starting heater target temp when the outdoor temperature is at outdoor
start outdoor reset
70°F (21°C)
Boil DESIGN
H MODE 1, 2, 3
70°F to 200°F (21°C to 93°C)
Design heater target temperature when the outdoor temperature is at
outdoor design outdoor reset
180°F (82°C)
TARGET MAX
H MODE 1, 2, 3
100°F (38°C) to PIM value*
Maximum target system temperature
200°F (93°C)
TARGET MIN
H MODE 1, 2, 3
OFF, 50°F to 190°F (10°C to
88°C)
Minimum target system temperature
50°F (10°C)
TARGET DIFF
H MODE 1, 2, 3
2°F to 42°F (1°C to 23.3°C)
Differential for target system temperature
10°F (5.6°C)
IND SENSOR
H MODE 1, 2, 3
OFF <> ON
Selects whether a DHW sensor is used for indirect DHW tank
OFF
IND SETP
H MODE 2, 3
OFF, 50°F (10°C) to 180°F
(82°C)
Target Indirect DHW Temperature, requires IND SENSOR = ON
140°F (60°C)
DHW DIFF
H MODE 2, 3
2°F to 10°F (1°C to 5.6°C)
Target indirect DHW tank temp, requires IND SENSOR = ON
6°F (3.4°C)
GLYCOL
IDLE only
0% - 50%
Glycol concentration
50%
Delta T Offset
H MODE 1,2,3
2°F to 15°F (1°C to 8.5°C)
DT Offset (Flow Warning threshold)
10°F
Isol Valve ON/OFF
IDLE only
0:CLOSE, 1:OPEN
Manual Open / Close of ISOL Valve
1, OPEN
VENT MATERIAL
IDLE only
PVC, CPVC, PPS, SS
Defines VENT Piping material. To update value unit must be in IDLE
status. (Tap 6 times on setting label to enable SET button)
PVC
VENT DIFF
IDLE only
1°F to 20°F (1°C to 11.2°C)
Substractive differential of VENT Temperature. This value sets the
threshold for VENT protection to be active
10°F (5.6°C)
VENT RATE
IDLE only
MIN Firing Rate to 80%
Forced firing rate when VENT protection is present
50%
# ISOL Valves
Open
Cascade Only
1, 2, 3, 4
Number of ISOL Valves open in a cascade configuration
1
Cascade Type
Cascade Only
SEQ, PAR
Cascade operation type
SEQ
Cascade MIN Flow
Offset
Cascade Only
-25 to 15 GPM
Overrides MIN flow condition for next unit in cascade to allow next unit to
be called to fire sooner or later.
0
Flow Override
IDLE only
0,MIN % to 80%
Overrides MIN Flow condition for ignition sequence, setting expires in
24hrs.
0
IND SUPPLY
H MODE 2, 3
OFF, 50°F (10°C) to PIM
value*
Target heater temperature for the DHW heat exchanger during indirect
DHW operation, requires IND SENSOR = OFF
180°F (82°C)
DHW PRIORITY
H MODE 2
OFF <> ON
Selects whether or not Indirect DHW priority is active during indirect DHW
operation
OFF
PRI OVR
H MODE 2, 3
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority override time
1:00hr
SYS PURGE
All
OFF, 0:20min to 20:00min
Sets the length of the system pump post purge
20 seconds
MIX TYPE
H MIX
H (VALVE, PUMP, PLNT)
WH (1 <> 2)
Selects the type of control depending on pipe configuration for CWP
H VALVE
MIX TARGET
H MIX
50°F to 140°F (10°C to 60°C)
Inlet Target Temperature
120°F (49°C)
MIX LOCK
H MIX
OFF <> ON
The equipment will trigger a warning when “MIX Target” is not reached
within 7 minutes. MIX LOCK = ON; Alarm and lockout, MIX LOCK = OFF;
Alarm only
OFF
MIX TRIM
H MIX
-5 to 5
This adjustment is for various types and sizes of units as well as various
actuator motor speeds and types supplied by Raypak
0
MIX SPEED
H MIX
SLOW <> MED <> FAST
This setting defines speed of response
MED
MIX INV
H MIX
OFF <> ON
Relates to the use of spring return actuators with a proportional valve
OFF
WWSD
H MODE 1, 2, 3
40°F to 100°F (4°C to 38°C)
The system warm weather shutdown temperature outdoor reset, requires
TARGET = RSET
70°F (21°C)
UNITS
All
deg F <> deg C
Show units using icons in display
deg F
MODBUS
All
OFF <> MNTR <>TEMP <>
RATE
ModBus Operating Mode: Off, Monitor, Temp Control, Rate Control
MNTR
ADDRESS
All
1 to 247
ModBus slave address
1
DATA TYPE
All
RTU <> ASCI
Modbus data type
RTU
BAUD RATE
All
2400 <> 9600 <> 19K2
<>57K6 <> 115K
19K2
PARITY
All
NONE <> EVEN <> ODD
EVEN
* Maximum operator dial setting.
Table W.
Setup/Adjust Menus