18
Raypak, Inc.
outdoor cutoff teMperature
Adjustable Off, 20
º
F - 100
º
F, On
Default: 65ºF
Button: MENU/Set Point/Outdoor Cutoff
in Set Point
Button: MENU/Set Point/Offset/Outdoor Cutoff
in Reset
• If the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear after
the temperature Set Point has been selected.
• When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the
TempTracker mod+ will control and modulate Boilers to hold the calculated temperature.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
• When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the TempTracker mod+ will disable the system.
The Message Display Line will display
Outdoor Cutoff.
• The Outdoor Cutoff can be set from 20°F to 100°F. In addition, the Setting can be set to ON or OFF. In the ON position, the
System Relay will run regardless of the Outdoor temperature (OD) and the burner stages will be active to hold the calculated water
temperature. (Note: The lowest water temperature the TempTracker mod+ will circulate is 70°F. If the Outdoor Cutoff is turned
ON and the Season is set to Winter, the TempTracker mod+ will circulate at least 70°F water even in the hottest of weather.) In the
OFF position, the system pump will always be off and all burner stages will be off for heating.
offset
Adjustable 50
º
F - (-50
º
F)
Default: 0
º
F
Button: MENU/Set Point/Offset
in Reset only
• The Offset setting lets you adjust the starting points of the Reset Ratio curves. This means
that, regardless of the Outdoor temperature (OD), or the Reset Ratio that has been selected,
when the Offset setting is changed, that change is directly added to or subtracted from the
calculated temperature. For example, if the Set Point temperature was 130°F and the Offset
was changed from 0° to 10° (an increase of 10°), then the Set Point temperature would
increase to 140°F
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
• The Offset setting does not change the ratio selection. For instance, with 1.00 (OD):1.00 (SYS) Reset Ratio, the System water
temperature (SYS) will always increase one degree for each degree change in the Outdoor temperature (OD). What the Offset does
is add or subtract a constant temperature value. (See Understanding Operation Concept on page 5)
• If required:
Adjust the Water Offset in mild weather
. If the ambient building temperatures are too warm in the mild weather,
decrease the Water Offset. If the ambient building temperatures are too cold in the mild weather, increase the Water Offset. The
rule of thumb for baseboard radiation is to change the Offset 4°F for every 1°F you wish to change the building temperatures. In
radiant heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building temperature.
MInIMuM Water teMp
Adjustable 70
º
F - 180
º
F
Default: 120
º
F
Button: MENU/Set Point/Offset/Outdoor Cutoff/Minimum Water Temp
in Reset only
• The Minimum Water Temperature must be set to the boiler manufacturer’s specification.
The TempTracker mod+ will calculate the Set Point based on the Outdoor temperature
(OD), the Reset Ratio, and the Offset value. The TempTracker mod+ will control all boilers
modulation to hold either the Set Point temperature, or the Minimum Water Temperature,
whichever is higher.
• The Minimum Water Temperature must be at least 20°F lower than the Maximum
Temperature (See next setting).
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
MaxIMuM Water teMp
Adjustable 90
º
F - 240
º
F
Default: 240
º
F
Button: MENU/Set Point/Offset/..../Maximum Water Temperature
in Reset only
• This is the highest temperature heating water the TempTracker mod+ will circulate through
the heating system. It is available in Reset mode only.
• When using a radiation system, it should be set according to the tubing or floor
manufacturer’s specification.
• The Maximum Temperature must be at least 20°F higher than the Minimum Temperature.
----------- SETTINGS ------------
Season
Winter
Set Point
140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
140
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
65
F
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
140
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
220
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled