25
MODE 3
(With Default Settings Shown)
ADJUST MENU
(Page 2 of 2)
Item Field
Range
Description
Setting
Au, 0:30 to
9:55 min
STAGE DELAY
Select the minimum time delay between
stages.
Note:
This setting is only available when
STAGE MODE is set to PId.
2 to 42°F
(1 to 23°C)
STAGE DIFFERENTIAL
Select the interstage temperature differential
between stages for proportional staging.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 8:00 min
INTERSTAGE ON DELAY
Select the amount of time that must pass
once a stage has been turned on in order
to allow the next stage to turn on.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 4:00 min
INTERSTAGE OFF DELAY
Select the amount of time that must pass
once a stage has been turned off in order
to allow the next stage to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM ON TIME
Select the minimum amount of time that the
stage contact must remain on before it is
allowed to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM OFF TIME
Select the minimum amount of time that the
stage contact must remain off before it is
allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the system pump purge time after
shutting off the burner.
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Table K: Adjust Menu, Mode 3 (page 2 of 2)