background image

Installation

Page 4

WARNING

DO NOT INSTALL WITHIN 3 FEET OF A HEAT PUMP OR
AN OUTDOOR CONDENSING UNIT.  STRONG AIR INTAKE
FROM THIS TYPE OF EQUIPMENT CAN DISTURB THE
COMBUSTION PROCESS AND CAUSE DAMAGE OR PER-
SONAL INJURY.

H

EATER WITH

O

UTDOOR

S

TACKLESS

T

OP

Heaters must not be installed under an overhang of less

than 3 ft from the top of the heater.  Three sides must be
open in the area under the overhang.  Roof water drainage
must be diverted away from heaters installed under over-
hangs with the use of gutters.

For U.S. installations, the point from where the flue prod-
ucts exit the heater must be a minimum of 4 ft below, 4 ft
horizontally from, or 1 ft above any door, window or gravi-
ty inlet into any building.  The top surface of the heater
shall be at least 3 ft above any forced air inlet, or intake
ducts located within 10 ft horizontally.  See Figure 6.

For installations in Canada, pool heaters shall not be
installed with the top of the vent assembly within 10 ft
below, or to either side, of any opening into the building.
Refer to the latest revisions of CAN/CGA-B149.1 and
B149.2

O

UTDOOR

H

IGH

-W

IND

T

OP

NOTE: The outdoor high-wind top is optional equip-
ment and does not come standard with the heater.
Use the following part numbers.

P/N 004301 (Green)

P/N 011558 (Gray)

H

IGH

W

IND

C

ONDITIONS

(O

UTDOOR

U

NITS

O

NLY

)

In areas where high winds are frequent, it may be neces-

sary to locate the heater a minimum of 3' from high vertical
walls, or install a wind-break so the heater is not in direct
wind current.

In areas of daily high winds, it may be necessary to

replace the outdoor stackless top with a stack adapter in
combination with a wind-resistant/weather-proof outdoor
stack.  See Figure 4.

The outdoor stack serves the same function as the low-

profile stackless top and should be installed in accordance
with the same clearance requirements.  Follow the installation
instructions provided with the High Wind Kit for installation.

Figure 4.  Outdoor High-Wind Top.

I

NDOOR

I

NSTALLATION

The heater is design-certified for indoor installation when

equipped with the approved drafthood.

NOTE:  For Canada, indoor installation is restricted
to an enclosure that is not occupied and does not
directly communicate with an occupied area. Refer
to the latest edition of CAN/CGA-B149.1 and B149.2
for specific requirements.

Locate heater as close as is practical to a chimney or gas

vent. Heater must always be vented to the outside. See Vent
Piping section for details. Minimum allowable space is shown
on the nameplate.  Follow the installation instructions provid-
ed with the Indoor Drafthood Kit for installation.

Figure 5.  Indoor Drafthood.

I

NDOOR

D

RAFTHOOD

NOTE: The indoor drafthood is optional equipment
and does not come standard with the heater.  Use
the following part number.

P/N 003723

Indoor
Drafthood

HIGH-WIND
TOP

Summary of Contents for 130A

Page 1: ...IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas s...

Page 2: ...ined from your pool or spa builder accredited pool shop or chemical supplier for the correct levels for your water AUTOMATIC CHLORINATORS CHEMICAL FEEDERS All chemicals must be introduced and complete...

Page 3: ...a fire or explosion causing property damage bodily injury or death Should you have any problems understand ing the warnings and instructions in this manual STOP and get help from a qualified installer...

Page 4: ...rd for Gas Fired Pool Heaters The heater can be used either indoors or outdoors If necessary the top of the heater can be changed after installation to accommodate indoors or out doors WARNING USE OF...

Page 5: ...a level base such as cementable slab cement blocks or another non combustible surface An alternate method for providing a base for com bustible floors is illustrated Heaters may not be installed on c...

Page 6: ...UNITS ONLY In areas where high winds are frequent it may be neces sary to locate the heater a minimum of 3 from high vertical walls or install a wind break so the heater is not in direct wind current...

Page 7: ...B149 2 As much as possible avoid long horizontal runs of vent pipe and too many elbows If installation requires hori zontal runs the vent pipe must have a minimum of 1 4 in per ft rise and should be...

Page 8: ...plied field supplied Vent Pipe Drafthood Heater 5 MIN 2 MIN 2 MIN Vent Cap 10 or Less CAUTION THE HEATER AND ITS MANUAL SHUT OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TEST...

Page 9: ...d 3 The outlet of the heater is plumbed to the return line to the pool or spa The pump filter and heater are thus plumbed in series Plumbing from the heater back to the pool or spa must not have any v...

Page 10: ...e valve as an auxiliary bypass valve AUXILIARY BYPASS VALVE ADJUSTMENT To set bypass With clean filter adjustment is made by feeling the inlet and outlet pipes at the heater Outlet pipes should be sli...

Page 11: ...ransformer for 120 VAC input power hookup Heater must be electrically grounded and bonded in accordance with local codes or in the absence of local codes with the latest edition of the National Electr...

Page 12: ...mit HI Limit In Out In Out Thermostat Manual Switch Switch Switch AGS Water Press Gas Valve Roll Out Valve Pilot Generator To Firemans Switch field installed Optional BK BK R Y BK TH PP W R PP TH V BK...

Page 13: ...y gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the appliance 4 This appliance is equipp...

Page 14: ...to Off unless knob is pushed in slightly Do not force 6 Wait 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to the next st...

Page 15: ...FOR FREEZE PROTECTION WHEN HEATER IS USED DURING FREEZ ING WEATHER CARE MUST BE TAKEN TO AVOID FREEZE UPS CONTINUOUS PUMP OPERATION IS A MUST ADDITIONAL PROTECTION MAY BE REQUIRED THE HEATER IS NOT WA...

Page 16: ...RATE MEETS THE REQUIREMENTS LISTED IN TABLE 6 WATER PRESSURE SWITCH ADJUSTMENT Figure 24 Water Pressure Switch Adjustment 1 With pump and heater on turn adjustment knob clock wise until a click is hea...

Page 17: ...am of heater 3 Remove front door 4 Disconnect gas line from gas valve 5 Remove 2 screws that mount burner tray to unit and 2 screws that secure gas valve to jacket 6 Disconnect wires that terminate at...

Page 18: ...move 2 screws that mount the igniter to the burner tray 3 Remove igniter from burner tray 4 Reverse above procedure to reinstall Figure 29 Direct Spark Igniter Spark Gap 0 15 0 18 PILOT REMOVAL AND CL...

Page 19: ...from the heater and wash with a garden hose making sure soot is removed from spaces between fins 5 Reverse above procedure to reinstall NOTE In extreme cases it may be necessary to do high pressure cl...

Page 20: ...gure 14 Air starvation Refer to installation instructions Improper venting Follow recommended installation instructions Insects or debris clogging burner intake ports Clean burners Pilot outage Low ga...

Page 21: ...across each high limit and remove jumper Replace thermostat Replace high limit that prevented from firing Jump across both TH wires on gas valves Check gas supply gas line size gas pressure Also chec...

Page 22: ...White Negative Red Positive 2 Pilot Load 500mV 100 Pilot generator connected to valve Power applied to pilot solenoid TP Thermopile Robertshaw PP Power Pile Honeywell TH TP Common Invensys TH PP Comm...

Page 23: ...o run at its normal flow rate Turn knob to a desired temperature zone Yes Yes Yes No No No Turn switch ON After 6 seconds does the igniter spark Does the burner tray light Does the burner tray stay li...

Page 24: ......

Reviews: