Installation

Page 5

C

OMBUSTION AND

V

ENTILATION

A

IR

(I

NDOOR

U

NITS

O

NLY

)

The heater must have both combustion and ventilation air.

Minimum requirements for net free air supply openings are
one opening that is 12 inches from the ceiling for ventilation,
and one opening that is 12 inches from the floor for combus-
tion air as outlined in the latest edition of the National Fuel
Gas Code, ANSI Z223.1(Canada-CAN/CGA-B149.1 and
B149.2)  and any local codes that may have jurisdiction.

A

LL

A

IR

F

ROM

I

NSIDE

T

HE

B

UILDING

Each opening shall have a minimum net free area of 130

sq. in.

A

LL

A

IR

F

ROM

O

UTDOORS

When air is supplied directly from outside of  building,

each opening shall have a minimum net free area of 33 sq.
in.

CAUTION

COMBUSTION AIR MUST NOT BE CONTAMINATED BY
CORROSIVE CHEMICAL FUMES WHICH CAN DAMAGE
THE HEATER AND VOID THE WARRANTY.  DO NOT
STORE CHLORINE, BROMINE, BAQUASIL OR ACID IN
THE SAME ROOM AS THE HEATER.

V

ENT

P

IPING

Vent piping the same size as the drafthood outlet is rec-

ommended, however, when the total vent height is at least 10
ft (drafthood relief opening to vent terminal), the vent pipe
size may be reduced as specified in the National Fuel Gas
Code, ANSI Z223.1 (Canada - CAN/CGA-B149.1 and
B149.2). As much as possible, avoid long horizontal runs of

vent pipe and too many elbows.  If installation requires hori-
zontal runs, the vent pipe must have a minimum of 1/4 in. per
ft rise and should be supported at not more than five foot
intervals.  Plumbers tape, criss-crossed, will serve to space
both horizontal and vertical piping.  Gas vents supported only
by the flashing and extending above the roof more than five
feet should be securely guyed or braced to withstand snow
and wind loads.  We recommend use of insulated vent pipe
spacers through the roof and walls.

For protection against rain or blockage by snow, the vent

pipe must terminate with a vent cap which complies with local
codes or, in the absence of such codes, the latest edition of
the National Fuel Gas Code, ANSI Z223.1 (Canada -
CAN/CGA-B149.1 and B149.2).

The discharge opening must be a minimum of 2 ft verti-

cally from the roof surface and at least 2 ft higher than any
part of the building within 10 ft.  Vent stack shall be at least 5
ft in vertical height above the drafthood outlet. The vent cap
location shall have a minimum clearance of 4 ft horizontally
from, and in no case below, unless a 4 ft horizontal distance
is maintained, from electric meters, gas meters, regulators
and relief equipment.

4

ft

Minimum

4

ft

Minimum

1

ft

Minimum

4

ft

Minimum

3

ft

Minimum

10

ft

Minimum

Forced Air Inlet

Figure 6.  Outdoor Installation Clearances.

Summary of Contents for 130A

Page 1: ...IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas s...

Page 2: ...ined from your pool or spa builder accredited pool shop or chemical supplier for the correct levels for your water AUTOMATIC CHLORINATORS CHEMICAL FEEDERS All chemicals must be introduced and complete...

Page 3: ...a fire or explosion causing property damage bodily injury or death Should you have any problems understand ing the warnings and instructions in this manual STOP and get help from a qualified installer...

Page 4: ...rd for Gas Fired Pool Heaters The heater can be used either indoors or outdoors If necessary the top of the heater can be changed after installation to accommodate indoors or out doors WARNING USE OF...

Page 5: ...a level base such as cementable slab cement blocks or another non combustible surface An alternate method for providing a base for com bustible floors is illustrated Heaters may not be installed on c...

Page 6: ...UNITS ONLY In areas where high winds are frequent it may be neces sary to locate the heater a minimum of 3 from high vertical walls or install a wind break so the heater is not in direct wind current...

Page 7: ...B149 2 As much as possible avoid long horizontal runs of vent pipe and too many elbows If installation requires hori zontal runs the vent pipe must have a minimum of 1 4 in per ft rise and should be...

Page 8: ...plied field supplied Vent Pipe Drafthood Heater 5 MIN 2 MIN 2 MIN Vent Cap 10 or Less CAUTION THE HEATER AND ITS MANUAL SHUT OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TEST...

Page 9: ...d 3 The outlet of the heater is plumbed to the return line to the pool or spa The pump filter and heater are thus plumbed in series Plumbing from the heater back to the pool or spa must not have any v...

Page 10: ...e valve as an auxiliary bypass valve AUXILIARY BYPASS VALVE ADJUSTMENT To set bypass With clean filter adjustment is made by feeling the inlet and outlet pipes at the heater Outlet pipes should be sli...

Page 11: ...ransformer for 120 VAC input power hookup Heater must be electrically grounded and bonded in accordance with local codes or in the absence of local codes with the latest edition of the National Electr...

Page 12: ...mit HI Limit In Out In Out Thermostat Manual Switch Switch Switch AGS Water Press Gas Valve Roll Out Valve Pilot Generator To Firemans Switch field installed Optional BK BK R Y BK TH PP W R PP TH V BK...

Page 13: ...y gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the appliance 4 This appliance is equipp...

Page 14: ...to Off unless knob is pushed in slightly Do not force 6 Wait 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to the next st...

Page 15: ...FOR FREEZE PROTECTION WHEN HEATER IS USED DURING FREEZ ING WEATHER CARE MUST BE TAKEN TO AVOID FREEZE UPS CONTINUOUS PUMP OPERATION IS A MUST ADDITIONAL PROTECTION MAY BE REQUIRED THE HEATER IS NOT WA...

Page 16: ...RATE MEETS THE REQUIREMENTS LISTED IN TABLE 6 WATER PRESSURE SWITCH ADJUSTMENT Figure 24 Water Pressure Switch Adjustment 1 With pump and heater on turn adjustment knob clock wise until a click is hea...

Page 17: ...am of heater 3 Remove front door 4 Disconnect gas line from gas valve 5 Remove 2 screws that mount burner tray to unit and 2 screws that secure gas valve to jacket 6 Disconnect wires that terminate at...

Page 18: ...move 2 screws that mount the igniter to the burner tray 3 Remove igniter from burner tray 4 Reverse above procedure to reinstall Figure 29 Direct Spark Igniter Spark Gap 0 15 0 18 PILOT REMOVAL AND CL...

Page 19: ...from the heater and wash with a garden hose making sure soot is removed from spaces between fins 5 Reverse above procedure to reinstall NOTE In extreme cases it may be necessary to do high pressure cl...

Page 20: ...gure 14 Air starvation Refer to installation instructions Improper venting Follow recommended installation instructions Insects or debris clogging burner intake ports Clean burners Pilot outage Low ga...

Page 21: ...across each high limit and remove jumper Replace thermostat Replace high limit that prevented from firing Jump across both TH wires on gas valves Check gas supply gas line size gas pressure Also chec...

Page 22: ...White Negative Red Positive 2 Pilot Load 500mV 100 Pilot generator connected to valve Power applied to pilot solenoid TP Thermopile Robertshaw PP Power Pile Honeywell TH TP Common Invensys TH PP Comm...

Page 23: ...o run at its normal flow rate Turn knob to a desired temperature zone Yes Yes Yes No No No Turn switch ON After 6 seconds does the igniter spark Does the burner tray light Does the burner tray stay li...

Page 24: ......

Reviews: