OUTDOOR INSTALLATIONS
Raypak Hi Delta Heaters are design certified
for outdoor installation. Heaters must not be installed under an overhang that
is less than three (3) feet from the top of the heater. Three (3) sides must be open in the area under the overhang. Roof water
drainage must be diverted away from heaters installed under overhangs.
TABLE 2
OUTDOOR INSTALLATION MINIMUM CLEARANCES
Heater Model
Heater Side
120-322
Rear
12"
Right
36”
Left
36"
Top
Unobstructed
Vent
N/A
These clearances required where the outdoor vent cap is used. If installing the heater outdoors with a vent stack, the
indoor clearances may be used.
10
FRONT VIEW
SIDE VIEW
Fig # 9400
Summary of Contents for 122-322
Page 6: ...HI DELTA COMPONENT LOCATION 6 BACK LEFT SIDE FRONT See detail page 7 See detail page 7 ...
Page 7: ...7 General Information GasValve Detail Air Shutter Adjustment ...
Page 17: ...17 SINGLE HEATER DOMESTIC HOTWATER WITH ONE STORAGE TANK ...
Page 35: ...DIRECT VENT Vertical Venting Category I VERTICALVENTINGTABLE 35 SECTION J 4 ...
Page 41: ...41 WIRE DIAGRAM MODELS 122 322 Reference Drawing Number M152564C ...
Page 50: ...Fig 241093 50 ...
Page 51: ...51 HEATEXCHANGERDETAIL ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 54: ......