Table R: Temperature Control Default Setpoints—H7 & WH7 Models
Item
Modes
Default Setting
Range
Boil Target
1, 2
160°F
OFF, 70 to 220°F
3
160°F
OFF, 70 to 190°F
4, 5, 6, 7
180°F
OFF, 70 to 220°F
Boil Max
1, 2, 4, 5, 6, 7, 8
200°F
OFF, 120 to 225°F
3
180°F
OFF, 120 to 190°F
Boil Min
1, 2, 3, 4, 5, 6, 7
150°F
OFF, 80 to 180°F
‘Burner’ Delay
All
0:00 min
0:00 to 3:00 min
Boil Mass
All
1 (Low)
1 (Low), 2 (Med), 3 (High)
Diff
1, 2, 3, 4, 5, 6, 7
Auto
Auto, 2 to 42°F
DHW Target
3
120°F
OFF, 70 to 190°F
DHW Diff
3
5°F
2 to 10°F
‘Pump’ Dly
All
3:00 min
OFF, 0:20 to 9:55 min, ON
Outdr Start
4, 5
70°F
35 to 85°F
Outdr Design
4, 5
-10°F
-60 to 32°F
Boil Start
4, 5
135°F
35 to 150°F
Boil Dsgn
4, 5
180°F
120 to 220°F
WWSD
4, 5
70°F
35 to 100°F
Units
All
°F
°F or °C
Mode
N/A
2
1, 2, 3, 4, 5, 6, 7, 8
External Input Signal
6, 7
2 to 10 VDC
2 to 10 VDC or 0 to 10 VDC
Offset
6, 7
0°F
-10°F to 10°F
Pool Heater (WHP)
Item
Modes
Default Setting
Range
Boil Target
2
78°F
OFF, 45 to 106°F
Boil Max
2
86°F
OFF, 70 to 106°F
Boil Min
2
70°F
OFF, 45 to 106°F
‘Burner’ Delay
All
0:00 min
0:00 to 3:00 min
Boil Mass
All
1 (Low)
1 (Low), 2 (Med), 3 (High)
Diff
2
1°F
1 to 3°F
‘Pump’ Dly
All
3:00 min
OFF, 0:20 to 9:55 min, ON
Units
All
°F
°F or °C
Mode
N/A
2
2
Table S: Temperature Control Default Setpoints—WHP Models
California Hot Water Supply, Inc.
(800) 249-7244
33