9
Raypak Advanced Design Boilers are design certified by AGA/CGA
for outdoor installation. Roof water drainage must be
diverted away from boilers installed under overhangs.
TABLE 2
OUTDOOR INSTALLATION MINIMUM CLEARANCES
Boiler Size
Boiler Side
751, 1001, 1501
Rear
6"
Right
36” (Water side)
Left
36"
Top
0"
Vent
1"
WARNING:
Combustion air inlet (blower air inlet) should have 6" minimum clearance from any obstruction, i.e. walls or
other appliances.