3
Heating Cable Repair
40 | nVent.com
nVent.com | 41
Slide the end cap as far forward as possible (the
flare on the cable sheath will stop it), then move it
back 3/16 in (5 mm) to ensure proper placement of
the heating cable in the end cap (see cross section).
End cap
3/16 in
(5 mm)
Figure 56: Placement of cable in end cap
You are now ready to braze the end cap to the cable
sheath.
Using a large sizzling flame (see Appendix E), heat
out the moisture from the cable beginning 12 in (30
cm) back from the end cap (begin 4 in (10 cm) back
for polymer jacketed cable), stopping 1/2 in (13 mm)
from the end cap. Immediately proceed to next step.
Note: Details on heating out (drying out) the
cable may be found in Appendix D.
Figure 57: Heat out cable
12 in.
Polymer
jacket
4 in.
1/2 in.
Sizzling flame