Heating Cable Repair
16 | nVent.com
nVent.com | 17
Figure 12: Check insulation resistance
Verify continuity of conductors using a multimeter or
ohmmeter.
Using a vernier caliper (or micrometer), measure
the outside diameter of the heated section and/or
cold lead section (not including polymer jacket) and
select the 1/2 in (13 mm) or 3/4 in (19 mm) joint
from Table 5 or Table 6.
Figure 13: Check cable diameter
Note: If replacing the hot-cold joint, the
diameters of both the heated section and cold lead
section must be considered when choosing the
correct size joint from Table 5 or Table 6.