INSTALLATION INSTRUCTION & OPERATION MANUAL     

PowerPlus RDIDC-100-3R-1U-X

INSTALLATION INSTRUCTION & OPERATION MANUAL

PowerPlus RDIDC-100-3R-1U-X 

PowerPlus RDIDC-100-3R-1U-1 

PowerPlus RDIDC-100-3R-1U-2 

Summary of Contents for PowerPlus RDIDC-100-3R-1U Series

Page 1: ...raycap com INSTALLATION INSTRUCTION OPERATION MANUAL PowerPlus RDIDC 100 3R 1U X INSTALLATION INSTRUCTION OPERATION MANUAL PowerPlus RDIDC 100 3R 1U X PowerPlus RDIDC 100 3R 1U 1 PowerPlus RDIDC 100 3R 1U 2 ...

Page 2: ......

Page 3: ...Modules 13 6 2 Module Failure 14 6 3 Primary Module Failure 14 7 Modules 15 7 1 Module Replacement 15 7 2 Cold Module Replacement 16 7 3 Hot Module Replacement 16 7 4 Hot Module Replacement Invalid Module Installation 16 8 Module Settings 17 8 1 Settings Menus 17 8 2 Initial Settings Menu 17 8 3 5 Initial Settings Menu Output Voltage Selection 18 9 Live Settings Menu 19 9 1 Live Settings 19 9 2 Ne...

Page 4: ...imum degree of safety follow the sequences as outlined Before using the product read all instructions and cautionary markings on the product and on any equipment connected to the product CAUTION Unless otherwise noted product usage that is not recommended or sold by the product manufacturer can result in risk of fire electric shock or injury to persons CAUTION Do not operate the product if it has ...

Page 5: ... RRH site by providing superior electrical protection at the RRH and BBU PowerPlus is Raycap s solution for power transmission to the RRH units of a DAS Telecommunication site PowerPlus is a system installed at the PSU output that boosts the voltage at the base of a cellular site to overcome the voltage drop on the DC power cables that provide power to the RRHs 3 0 Package Contents 1 each 1 1U Pow...

Page 6: ...served 320 1674 Rev A Page 6 of 28 Scan QR for Complete Installation Instructions 4 Mounting 4 1 Select a suitable position within the rack for the installation of the unit You will need 1U vertical space 4 2 The unit ships with a Rack Extension Kit to mount into a 23 rack 4 4 Mount the unit on the rack 1U ...

Page 7: ...an QR for Complete Installation Instructions 4 4 1 Mounting Distance from 19 rack Note Mounting ear positions offer the following mounting configurations 4 5 Release the 4 push pins and remove touch guard as shown below Mounting Position A1 Mounting Position A3 Mounting Position A2 0 59 0 94 0 93 0 36 0 94 0 94 2 74 2 14 Mounting Position A4 ...

Page 8: ...efficient Additionally the PowerPlus RDIDC 100 3 1U X is beneficial when operating on battery backup power during a power outage The PowerPlus RDIDC 100 3 1U X will maintain a constant output voltage as configured to the radio while the battery discharges This allows the radio to operate for a longer period of time while the batteries discharge 5 2 System Configuration The PowerPlus RDIDC 100 3 1U...

Page 9: ...N MANUAL PowerPlus RDIDC 100 3R 1U X www raycap com Raycap All rights reserved 320 1674 Rev A Page 9 of 28 Scan QR for Complete Installation Instructions 5 3 System Topology 48VDC OUT 1 Unused 48VDC OUT 2 48VDC IN RTN OUT RTN IN GROUND ...

Page 10: ... MANUAL www raycap com Raycap All rights reserved 320 1674 Rev A Page 10 of 28 Scan QR for Complete Installation Instructions 5 4 Installation Configuration PowerPlus RDIDC 100 3 1U X system configuration 48VDC OUT 2 Unused 48VDC OUT 1 RTN OUT 48VDC RTN GND DC PS ...

Page 11: ...ns are 20 studs Torque to 65 in lbs DC Power Plant 150A 150A RDIDC 9052 PDU 48 Use 6 AWG copper wire for ground Use 6 AWG copper wire for ground 2 AWG for PowerPlus to PDU 1 O for DC Power Plant to PowerPlus and PDU Recommended Lugs For 1 O Use Panduit LCD1 O 14A X for Input Output For 2 Gauge Use Panduit LCD2 14A Q for Output For 6 Gauge Use Panduit LCD6 14A for Ground 48V OUT 1 48V OUT 2 48V OUT...

Page 12: ...tuds Torque to 65 in lbs DC Power Plant RDIDC 9052 PDU 48 Trunk to Upper OVP 48V 48V IN Return OUT Return 48V Return Return IN GROUND 100A Module Installed 100A Module Installed 300A Use 6 AWG copper wire for ground Use 6 AWG copper wire for ground 48V OUT 1 48V OUT 2 48V OUT Unused Power Plus Use 6 AWG copper wire for ground Recommended Lugs For 1 O Use Panduit LCD1 O 14A X for Input For 2 Gauge ...

Page 13: ...controls the proper operation of the complete system When a failure occurs the Primary module will coordinate the response to this event When the Primary module fails another Secondary module will take over control of the system and become the new Primary All modules will display the input and output voltage of the system The Primary module is indicated by an P character which is located at the en...

Page 14: ... voltage to the new Secondary module The alarm is cleared after pressing the ENTER button on the Primary module for more than 3 seconds 6 3 Primary Module Failure When the Primary module fails another Secondary module will takeover the role of Primary and raise an alarm The front panel s LED will change from GREEN to RED the remote contact will change to Failed and the new Primary module will disp...

Page 15: ...C 100 3R 1U X www raycap com Raycap All rights reserved 320 1674 Rev A Page 15 of 28 Scan QR for Complete Installation Instructions 7 Modules 7 1 Module Replacement Unscrew the thumb screws on both sides of module Release the side levers Pull out the device ...

Page 16: ... to settings mode and it will wait for new settings This is also a starting point of the initial settings menu 7 3 Hot Module Replacement Hot Module Replacement is the replacement of a module when the system is powered ON and operational Every module stores the settings of all other modules in the system When a module fails Primary module or Secondary module failure it must be replaced The replace...

Page 17: ...during system boot The live settings menu is enabled when the UP and DOWN buttons of the Primary module are pressed simultaneously for more than 3 seconds The initial settings menu and the live settings menu are very simple menus 8 2 Initial Settings Menu The initial settings menu will appear when the system detects conflicting setting during system boot or at initial power up Each module will dis...

Page 18: ...mary module in increments of 1V The maximum target voltage for the RRU is typically set to 58V 8 4 Initial Settings Menu Output Voltage Selection All Modules are Set Next Module Setting The same configuration procedure should be repeated for each of the Secondary modules 8 5 Initial Settings Menu Output Voltage Selection All Modules are Set Finish When all modules have been configured the system s...

Page 19: ...on cycle In this menu the modules in each slot display the SETTINGS message The Primary module is selected by pressing the ENTER button on any module e g Slot 1 module This module will become the Primary module and the other modules will be configured as Secondary modules UP DOWN 9 2 New Previous Configuration Selection Next step is the New Previous Configuration selection The configuration select...

Page 20: ...t section of this document 10 Alarms 10 1 Front Panel LED and Remote Contact Whenever an abnormal condition is encountered the system will raise an alarm The front panel s LED will change from GREEN to RED and the remote contacts will change to the failed position The maximum rated current of the remote contacts is 2A Alarm LED Green Red Remote Contact Alarm Alarm Condition Common Alarm Condition ...

Page 21: ...aximum rated current 110A for more than 3 seconds the Primary module will switch to its bypass mode and display the HIGH CURRENT message The Secondary module will detect the overcurrent condition of the Primary module and take control so as to become the Primary module This new Primary module will raise a PRIMARY FAILURE alarm 10 3 Low Input Voltage When the system input voltage is below the minim...

Page 22: ...will go to bypass and remain in this condition until the input voltage returns to its normal operational level All modules will display the EXTRA LOW Vin message 10 6 Temperature Alarm If the temperature of a Secondary module exceeds its maximum rated internal temperature for more than 3 seconds the module will go to bypass and display the HIGH TEMP message The Primary module detects this conditio...

Page 23: ...ore than 250 seconds the modules will go to bypass and remain in this condition until the temperature returns to its normal operating level 10 9 Module DC DC Converter Communication Failure If a failure of the internal DC DC converter occurs the module will halt its output and display a DC DC COM FAIL message 10 8 Module DC DC Converter Failure When a short circuit at the output of a module occurs...

Page 24: ...boost voltage on these long run to compensate for voltage drop HP HP HP HP HP HP LP LP LP G B A 150A Input from the DC Plant 150A Input from the DC Plant Input from PowerPlus Module 1 Input from PowerPlus Module 2 HP HP HP 9 8 7 HP HP HP LP LP LP 6 5 4 3 2 1 Output to Remote Radio Heads Legend A Alpha Blue color B Beta Orange color G Gamma Green color HP High Power RRU 1350W LP Low Power RRU 150W ...

Page 25: ...ensate for voltage drop HP HP LP HP HP LP HP LP HP G B A RDIDC 3045 PF 48 HP LP HP HP LP HP HP LP HP G B A RDIDC 3045 PF 48 Legend A Alpha Blue color B Beta Orange color G Gamma Green color HP High Power RRU 1350W LP Low Power RRU 150W Grey Cables are 240 Red Cables are 240 Legend A Alpha Blue color B Beta Orange color G Gamma Green color HP High Power RRU 1350W LP Low Power RRU 150W Grey Cables a...

Page 26: ...uired to boost voltage to compensate for voltage drop HP LP HP HP LP HP HP LP HP G B A RDIDC 3045 PF 48 G B A HP LP HP HP LP HP HP LP HP RDIDC 3045 PF 48 HP HP LP HP HP LP HP HP LP 9 8 7 6 5 4 3 2 1 Output to Remote Radio Heads Input from PowerPlus Module 1 Input from PowerPlus Module 1 Legend A Alpha Blue color B Beta Orange color G Gamma Green color HP High Power RRU 1350W LP Low Power RRU 150W ...

Page 27: ...INSTALLATION INSTRUCTION OPERATION MANUAL PowerPlus RDIDC 100 3R 1U X www raycap com Raycap All rights reserved 320 1674 Rev A Page 27 of 28 Scan QR for Complete Installation Instructions Notes ...

Page 28: ...PowerPlus RDIDC 100 3R 1U X INSTALLATION INSTRUCTION OPERATION MANUAL www raycap com Raycap All rights reserved 320 1674 Rev A Page 28 of 28 Scan QR for Complete Installation Instructions ...