www.raycap.com
©Raycap • All rights reserved
320-1261 Rev.C
Page 11 of 24
INSTALL INSTRUCTIONS
3315-ALM-RS485
Procedure
Installation of 3315-ALM-RS485
10.1 Align new alarm board to frame.
Using a #2 Phillips-head screwdriver,
secure 4 screws
.
ATTENTION - Ensure ESD wriststrap is used
Electrostatic sensitive devices. ESD mitigative
procedures, such as wearing wriststraps are to
be used during installation and maintenance.
7.0
Installing Alarm Wiring
A.
Alarm Output to BTS: Outputs for Intrusion, H2O, and Power
B.
Legacy: parallel voltage monitor wire connections
C.
Rotary Switch for Base Mode Operation. Place rotary switch to
position “2, 3, 4, 5, or 6” which corresponds to base mode
address “0, 1, 2, 3, or 4”. If in daisy chain configuration, place
selector switch to the next base mode address.
Place rotary switch to “
•”
or “1” for Tower Top Mode Operation.
D.
Legacy alarm wire connections 2: For Daisy Chain
E.
Legacy alarm wire connections 1: For Intrusion, H2O, and Power
F.
Base Communication: Base RS485 communication input from
tower, 2-twisted pair (4 wires total)
G.
VBoost Input: Optional ethernet daisy chain input
H.
VBoost Output: Optional ethernet output to daisy chain / VBoost
A
B
C
D
E
H
G
F