Fault Finding
PROGRAMMER
SLIDERS SET TO
“CONT’ &
THERMOSTATS TO
MAXIMUM
IS THERE 230V AT
CONTROL BOX
TERMINALS 2 & 1 ?
SEE TROUBLE
SHOOTING BURNER
SECTION
HAS OVERHEAT
THERMOSTAT
ACTIVATED
IS THERE 230V
BETWEEN COOKER
OVERHEAT STAT AND
NEUTRAL
REPLACE COOKER
OVERHEAT STAT
RESET OVERHEAT
THERMOSTAT
THERMOSTAT OR
WIRING FAULT
YES
NO
NO
YES
NO
YES
CHANGE
CIRCULATING PUMP
IS CIRCULATING
PUMP OPERATING
SATISFACTORILY ?
CHECK & BALANCE
CH/DHW SYSTEM
CHANGE PUMP
OVERRUN
THERMOSTAT
NO
YES
IS THE PUMP
OVERRUN
OPERATING AT A
WATER TEMP OF
65°C
NO
YES