Rayburn Heatranger 368K Installation And Servicing Instructions Download Page 10

(x) Connect oil supply pipe from tank to inlet of Oil Control
Valve - open all oil valves to allow oil into the control valve.
(xi) Depress trip lever 

D

on the front of the oil control valve

P

(See Fig. 13).

(xii) Connect MAIN burner solenoid to 13A plug and
extension lead - switch on power to solenoid.
This will allow oil to flow to the burner without activating
the main controller.

(xiii) Wait about 10-15 minutes until the depth of oil within
the burner settles. Lower a dip stick through the hot plate
aperture, until it sets onto the burner base at its centre.
Remove the dip stick and measure the depth of oil which
must register 15-17mm depth.

To Correct Oil Depth

For small adjustments (1-2mm) - adjust oil control valve
height - for adjustments greater than this it may be
necessary to adjust the height of the burner base plate.
Should this be necessary then switch off the solenoid -
disconnect the pipe work and remove the boiler - release
the locking bolts on the base plate and turn the slotted
setting screws to the required position, re-check levelling
of base plate - replace burner and pipe work - switch on
solenoid and re-check oil depth.
WHEN CORRECT ENSURE THE VALVE IS LEVEL IN
ALL DIRECTIONS AND SECURE - INCLUDING THE
REAR SUPPORT SCREW. THIS MUST BE FITTED AND
SUPPORTING THE REAR OF THE VALVE.
OTHERWISE OIL RATES CAN CHANGE OVER A
PERIOD OF TIME.

(xiv) Switch 

OFF

mains power supply to solenoid.

(xv) Disconnect the main inlet oil feed and the pilot feed at
the front of the burner. Collect the oil spill over into a
receptacle, then proceed to withdraw the boiler burner as
previously indicated.
(xvi) Replace the two interstage baffles, the end baffles
and the top VEE baffle. ENSURING THE CORRECT
LOCATION OF EACH BAFFLE.
(xvii) Re-insert the boiler burner into the combustion
chamber ensuring it is fully engaged, refit the tie bar and
secure with the tie bolts - DO NOT ALLOW THE BURNER
FRONT TO LIFT AS IT IS TIGHTENED UP.
(xvii) Re-connect the main and pilot oil feed pipes as
previously described.
(xix) Re-connect electrical cables to glo-coil terminals,
ensuring that the shakeproof washer is fitted under the
Glo-Plug Locking Nut - Insert Flame Sensor into burner
front plate and secure.
Adjust fire bricks so that there is a gap between them in
the centre.
(xx) Replace boiler front fire bricks, boiler cover plate and
hot plate assembly. Ensure boiler cover plate is down
correctly, that the front screw is secure and that the type
gasket is sealing.
(xxi) Check oil flow rate to main burner. - This should be
38 - 40 cc/min as measured by the DRIP FEED METHOD
FOR SETTING THE OIL RATES SEE SECTION ON
SETTING THE OIL CONTROL VALVE.

The cooker burner comes packed in its own carton.
1. Screw the carbon leg assembly into the base using an
oil resistant sealant. The carbon leg must be positioned in
line with the length of the burner base. The end which the
carbon leg faces when tightly screwed in place is the front
of the burner, where the burner support bar is located.
The support bar must be screwed into location using a
counter sunk screw before the final tightening of the
carbon leg.
2. Screw the levelling screws into the support bar.
3. Screw the adjustment leg into the rear of the burner.
Check that the height of the levelling screw in the
adjustment leg is 39mm from the top of the lock nut to the
base of the screw (Fig. 9).
4. Open outer burner door and lift remove R.H. cooker
inner burner door.
5. Place burner base into combustion chamber and check
base is level in all directions. (ENSURE THAT THE LEGS
OF THE BASE ARE ENGAGED IN THE ROUND
RECESSES PROVIDED).
There are three - two at the front and one at the rear.
It is essential this is done or any adjustment on height or
level of the burner WILL BE WRONG.
6. Connect oil supply pipe and turn cooker control knob to
No.6 this will allow oil into the burner base. Allow
approximately 15-20 minutes for the oil level to stabilise. -
then test oil depth this should settle to a depth of 6mm.
7. To correct oil depth, slacken the nuts securing the
threaded support legs and adjust the leg height to suit.
Re-check that the burner is level in all directions.
8. With the burner level and a constant oil depth of 6mm
tighten the locking nuts on the oil burner levelling screws.
IMPORTANT: THE COOKER BURNER BASE MUST BE
LEVEL IN ALL DIRECTIONS AND THE OIL DEPTH
STABLE AT 6MM.
Switch off oil, drain and disconnect.
Remove cooker burner base.

9

SETTING UP THE COOKER BURNER

Fig.9 Cooker Burner Assembly

DESN 510835 A

Summary of Contents for Heatranger 368K

Page 1: ...WARNING This information is a copy of an original archive therefore Aga cannot be held responsible for its continued accuracy ...

Page 2: ...LOW Boiler ON Cooker HIGH Boiler ON kW Btu h IMPORTANT IN ORDER TO MAINTAIN OPTIMUM PERFORMANCE FROM THIS APPLIANCE IT IS ESSENTIAL THAT THE INITIAL COMMISSIONING IS UNDERTAKEN BY SELECTED TRAINED INSTALLATION SERVICING ENGINEERS YOUR RAYBURN STOCKIST WILL PROVIDE ADVISE ON THE LOCATION OF THE NEAREST INSTALLING ENGINEER AND WE RECOMMEND YOU CONTRACT OUT THE PERIODICAL SERVICING OF THE APPLIANCE T...

Page 3: ...inal See Chimney Terminations This appliance must be installed on a solid floor base or plinth made of incombustible material which is capable of supporting the total weight The location chosen for the appliance must permit installation and the provision of a satisfactory flue and an adequate air supply The location must also provide adequate space for servicing and air circulation around the appl...

Page 4: ...ory made prefabricated metal flue then a proprietary cowl can be used for this purpose Chimney Cleaning Ensure there are accessible airtight flue cleaning doors in order to obtain cleaning access to the complete chimney Providing the appliance is operating correctly an annual chimney flue cleaning will suffice but if in doubt arrange for a half yearly clean preferably at the beginning end of the c...

Page 5: ...Domestic Hot Water and Pumped Heating The 28mm O D primary flow pipe must rise continuously from the boiler section to the cylinder to ensure good gravity circulation and extended to provide an open vent The 28mm O D primary flow and return pipes must not exceed 10m in length Pipe runs in excess of 5m must be lagged To obtain Domestic Hot Water gravity circulation with the circulating pump on the ...

Page 6: ...Typical DHW Gravity System Fig 4 Typical Pumped System 5 ...

Page 7: ...CE HAVE MORE THAN ONE POWER SOURCE ALL POWER TO THE APPLIANCE MUST GO THROUGH ONE SINGLE 5 AMP FUSED ISOLATOR SWITCH General The appliance is floor mounted and the space in which the appliance is to be fitted must have the following minimum dimensions Between wall and L H side of appliance 300mm Between wall and R H side of appliance Zero Above the raised insulated cover handle 60mm In addition ad...

Page 8: ...iagram See below UNDER NO CIRCUMSTANCES SHOULD THE APPLIANCE HAVE TWO SEPARATE POWER SOURCES ALL POWER MUST GO THROUGH ONE SINGLE 5A FUSED ISOLATOR SWITCH Fig 6 Fig 7 Wiring Diagram for the 368K on a Fully Pumped System 7 ...

Page 9: ...etach the electrical connections to the glo coil See Fig 11 3 Slacken off bolts on tie bar retaining the boiler burner and remove tie bar 4 Holding the strap handle on the front of the burner withdraw horizontally until clear of the appliance See fig 13 5 i Lift out top Vee baffle ii Remove the two end baffles and inter stage baffles from within the boiler burner iii Check that the wick on the glo...

Page 10: ... Nut Insert Flame Sensor into burner front plate and secure Adjust fire bricks so that there is a gap between them in the centre xx Replace boiler front fire bricks boiler cover plate and hot plate assembly Ensure boiler cover plate is down correctly that the front screw is secure and that the type gasket is sealing xxi Check oil flow rate to main burner This should be 38 40 cc min as measured by ...

Page 11: ...Fig 12 Fig 10 Fig 11 DESN 510388 10 DESN 511324 ...

Page 12: ...cooker burner thus eliminating excessive fumes into the room Boiler Burner SEE FIG 12 1 Connect oil pipe work and solenoids between the oil control valve and the boiler burner 2 Ensure that both pipes rise steadily without kinks from the lowest point 3 Disconnect main burner oil feed and fit adaptor for measuring oil rates by the DRIP FEED METHOD 4 Put tray under adaptor outlet 5 Turn ON separate ...

Page 13: ...pplicable Checks to ensure electrical safety should be carried out by a competent person The whole of the system should be thoroughly flushed out with cold water without the pump in position Ensure that all valves are open With the pump fitted the system should be filled and air locks cleared Vent all heat emitters and check for water soundness SEE FIG 13 Check that 1 The boiler system is full of ...

Page 14: ... Allow the heating system to warm up then set the pump adjuster to maintain a boiler flow and return temperature differential of 10 C 14 C 18 25 F Checks must be made by the installer to see that this differential is obtained after the boiler Flow temperature is stabilised The system should be balanced by regulating the water flow rate through individual heat emitters to ensure a satisfactory wate...

Page 15: ...d down by the following morning in readiness for servicing Before commencing any servicing isolate the electricity supply switch OFF and remove plug then turn OFF the oil supply at the isolating valve near to the appliance Standard Half Yearly Service Schedule a Remove and clean Flue Draught Stabiliser b Service clean of complete boiler heat exchanger over flueways oven and hotplate flueways toget...

Page 16: ...t any heat deformation is minimal the assembly is free of heat oxidised surfaces and is interlocked together Remove any internal external surface deposits with soft brush iv Remove the wicks from oil burner base If the wicks are badly charred or heat hardened prepare replacements v Carefully remove any carbon deposit on machined surfaces of oil burner base which provide seating for burner shells R...

Page 17: ...l Reconnect the oil feed pipe and electrically reconnect the flame sensor and ignition glo coil igniter in reverse order of dis assembly Replace boiler strap and secure tightly with retaining bolts The boiler burner is now ready for re lighting NOTE ENSURE BOTH PILOT AND MAIN FEED PIPES RISE CONTINUALLY FROM THE LOWEST POINT TO AVOID AIR LOCKING PROBLEMS To Clean the Boiler Heat Exchanger and Cook...

Page 18: ...thermostat knobs Remove four screws securing control panel cover to L H side plate and remove cover c Remove split pin from boiler thermostat pocket d Remove and withdraw boiler thermostat phial from boiler phial pocket e Disconnect two electrical leads from thermostat body and earth terminal See Fig 14 for connections f Unscrew thermostat spindle locknut to detach boiler thermostat from mounting ...

Page 19: ...icro switch noting order of connection d Remove two fixing screws securing pressure switch to strap NOTE CHECK BOTH PLASTIC TUBES ARE INTACT AIRTIGHT AND REPLACE IF NECESSARY Replace switch assembly in reverse manner of dis assembly and remake electrical terminations Although the air pressure switch is now ready for use adjustments must be made to the switch for pressure activation as follows i Co...

Page 20: ...of electrical power Setting the thermostat knob from LOW TO MAX will cause the thermostat to switch electrical power ON OFF automatically and vary the oil rate to provide a selected oven temperature thermostatically controlled See Users Instructions for details of thermostat knob settings and oven temperatures Despite the loss of electrical power high oven cooking temperatures can still be obtaine...

Page 21: ...he sequence re commences Confirmation of oil rates and combustion must be made as a final check These can be carried out using the Drip Feed Method 1 Confirm the cooker burner base is level in all directions 2 Confirm the static oil depth in the cooker burner base is 6mm after a 15 20 minute period 3 Check the low fire oil rate 4 75cc min on low 4 Check high fire rate 13 0 13 5cc min 5 Assemble bu...

Page 22: ...am See Page below UNDER NO CIRCUMSTANCES SHOULD THE APPLIANCE HAVE TWO SEPARATE POWER SOURCES ALL POWER MUST GO THROUGH ONE SINGLE 5A FUSED ISOLATOR SWITCH Fig 29 Wiring Diagram for the 368K on a Fully Pumped System 21 Fig 28 ...

Page 23: ...uns on Lock out PCB fault Replace PCB light FAN and GLO PLUG on CONTINUOUSLY Fan and glo plug on pilot PCB fault Replace PCB solenoid does not open PILOT BURNER DOES NOT LIGHT Glo plug energised power to Pilot solenoid fault Replace solenoid pilot but does not open Pressure switch fault Check setting of pressure switch Replace pressure switch Air lock in pilot oil feed pipe Check oil pipe rises st...

Page 24: ...Draughts Check flue for down draughts and eliminate them Poor fitting burner shells Check set of shells seating properly Replace set of shells Check burner base replace if necessary CONTINUOUS LOW FIRE Power failure Check mains supply if power cut use manual control Cooker thermostat fault Replace cooker thermostat Oil valve electric top fault Replace electric top Oil valve control pin stuck Free ...

Page 25: ...policy of continuous product improvement the Company reserves the right to change specifications and make modifications to the appliance described at any time Manufactured by Aga Station Road Ketley Telford Shropshire TF1 5AQ England www aga web co uk www agacookshop co uk www agalinks com ...

Reviews: