background image

Use and maintenance manual S70 - S90 - SC90

Pag.39 

Rev.0  18/05/2020

            To exit the STOVE STATUS screen and return to the Home screen, press the key repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the

stove useful for service during inspection.

- RDS current reading RDS (m/s)

- RPM current smoke extractor speed (rpm)

- T fumes temperture (°C)

- Indication of stove status

- SET set value RDS (m/s)

- Df cold probe temperture RDS (°C)

- Sk: electronic board temperature (°C

Stove state

Below are given the steps for accessing the relative menu starting from “Home” mode.

RPM

T

Tsk

g/min

°C

°C

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

Comfort climate

The activation of this function enables the stove to reduce pellet consumption by activating the modulation phases, after the desired

temperature has been reached. Subsequently, the stove checks that the temperature is maintained steady for a preset time. If this

condition is met, it automatically switches off, and on display appears the writing ECO.

The stove turns on again when the temperature drops below the set threshold.

Below are given the steps for accessing the relative menu.

User’s manual HANDHELD TOUCH RADIO

User’s manual HANDHELD TOUCH RADIO

Pag.22 

Pag.23 

Vers. 01 of:07.04.14

Vers. 01 of:07.04.14

Loading the auger

MENU

USER

SCREW FEEDING

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

USER

MANUFACTURER 

ENGINEER

MENU

USER

MANUFACTURER 

ENGINEER

USER

USER

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

ENABLE COMFORT

ENABLE COMFORT

ENABLE COMFORT

RESTART DELTA

RESTART DELTA

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

ENABLE COMFORT

ENABLE COMFORT

COMFORT CLIMA DELTA

COMFORT CLIMA DELTA

RESTART DELTA

SHUTDOWN DELAY

SETTINGS

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

ALWAYS EMPTY THE BRAZIER BEFORE TURNING THE STOVE ON AND ALWAYS CHECK  

THAT ALL NONE OF ITS HOLES IS CLOGGED NEVER EMPTY THE RBAZIER INSIDE THE HOPPER.  

FIRE HAZARD.  

Carry out this operation to facilitate stove’s first start operations; You should also check that you have introduced pellets  

into the hopper and wait until the stove is in “SHUTDOWN” or “FINAL CLEANING” mode. The number expressed in sec-

onds indicates the rotation time of the infeed screw during the first loading cycle. Once this time has elapsed, the infeed  

screw stops immediately and then pellets are emptied from the grate before turning on the equipment.  

Below are given the steps for accessing the relative menu.  

Press the key  “access 

menu” to access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

At the end of the auger loading, the display shows 0 “and automatically switches to the USER menu page.  

Press the key for several times until the Stand-by page is displayed.  

Setting operating temperature and power: 

Set the two values following the indications given in the chapter “Description of thr display” 

Turning the device on 

Keep the key ON/OFF pressed for a few seconds to turn on the stove.  

Press CONFIRM to enable  

the rotation of the auger  

The appearance of the message “ADJUST THE RDS SYSTEM” indicates that the initial parameter testing procedure  

and calibration has been unsuccessfully. This indication does not cause stove blockage (see the SIGNALLING POP UP  

section).  

On the display of the handheld set appears the following:  

Press and hold the ON/OFF button to turn off the stove door, and reset any alarms triggered.  

In case the infeed screw operations described avobe have not been executed, the stove may fail to turn on. In this case,  

carry out the operations described above and   empty the brazier and reset the alarm.  

If the stove still fails to turn on, check that the grate is properly installed and perfectly adherent to the base, and also check that  

there are no deposits that prevent the smooth passage of air to enable ignition. If the problem persists, contact the support ser

-

vice. 

Sequence of ignition phases  

SWITCH-ON- initial pellet loading phase; 

WAIT FLAME - flame 

development  wait  

phase; 

FLAME PRESENT - flame stabilization  

phase and reduction of combustible  

inside the brazier;  

What happens if the batteries are empty?  

If the battery is discharged, within the  

“drop” is shown a symbol that indicates  

that the battery is empty, while maintain-

ing active the features of your device.  

WORK - operation phase 

described in  

the dedicated chapter;  

As soon as the level of the battery  

prevents the radio communication  the 

handheld set displays on full screen  the 

picture of empty battery and all device 

functions are locked  until the batteries 

are replaced   

CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT, THEREFORE, NOT POWERED. MORE-

OVER, WE RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3°C IF YOU INTEND TO USE  

THE COMFORT CLIMA FUNCTION.  

Operating phases of the appliance 

Modulation 

During the work phase, the appliance should reach the room temperature set; when this condition is met, the stove switches to  

MODULATION mode in which fuel consumption and ventilation are minimum.  

If you wish to detect the ambient temperature by means of an external thermostat (optional), this must be connected to  

the appropriate connector on the rear side of the stove; and you will have to activate the reading in “SETTINGS - EN  - 

ABLE THERMOSTAT.” On display appears the writing TON / TOFF based on thermostat request.  

Comfort climate 

The activation of this function enables the stove to reduce pellet consumption by activating the modulation phases, after the desired  

temperature has been reached. Subsequently, the stove checks that the temperature is maintained steady for a preset  time. If this 

condition is met, it automatically switches off, and on display appears the writing ECO.  

The stove turns on again when the temperature drops below the set threshold. 
Below are given the steps for accessing the relative menu.  

Press the key  

“access menu” to 

access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

Once you have accessed the Climate Comfort menu, it is possible to operate on the 3 types of settings dedicated to the function:  

Press the key for several times until the Stand-by page is displayed.  

Press the key “selection” for  

“selection”  

to switch to the second page  

of USER MENU and select  

CLIMATE COMFORT.   

Once you have accessed the Climate Comfort menu, it is possible to operate on the 3 types of settings dedicated to the function:

User’s manual HANDHELD TOUCH RADIO

User’s manual HANDHELD TOUCH RADIO

Pag.22 

Pag.23 

Vers. 01 of:07.04.14

Vers. 01 of:07.04.14

Loading the auger

MENU

USER

SCREW FEEDING

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

USER

MANUFACTURER 

ENGINEER

MENU

USER

MANUFACTURER 

ENGINEER

USER

USER

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

COMFORT CLIMA

ENABLE COMFORT

ENABLE COMFORT

ENABLE COMFORT

RESTART DELTA

RESTART DELTA

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

SHUTDOWN DELAY

ENABLE COMFORT

ENABLE COMFORT

COMFORT CLIMA DELTA

COMFORT CLIMA DELTA

RESTART DELTA

SHUTDOWN DELAY

SETTINGS

SCREW FEEDING

CHRONOTHERMOSTAT

AIR-PELLET SET

STOVE STATE

ALWAYS EMPTY THE BRAZIER BEFORE TURNING THE STOVE ON AND ALWAYS CHECK  

THAT ALL NONE OF ITS HOLES IS CLOGGED NEVER EMPTY THE RBAZIER INSIDE THE HOPPER.  

FIRE HAZARD.  

Carry out this operation to facilitate stove’s first start operations; You should also check that you have introduced pellets  

into the hopper and wait until the stove is in “SHUTDOWN” or “FINAL CLEANING” mode. The number expressed in sec-

onds indicates the rotation time of the infeed screw during the first loading cycle. Once this time has elapsed, the infeed  

screw stops immediately and then pellets are emptied from the grate before turning on the equipment.  

Below are given the steps for accessing the relative menu.  

Press the key  “access 

menu” to access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

At the end of the auger loading, the display shows 0 “and automatically switches to the USER menu page.  

Press the key for several times until the Stand-by page is displayed.  

Setting operating temperature and power: 

Set the two values following the indications given in the chapter “Description of thr display” 

Turning the device on 

Keep the key ON/OFF pressed for a few seconds to turn on the stove.  

Press CONFIRM to enable  

the rotation of the auger  

The appearance of the message “ADJUST THE RDS SYSTEM” indicates that the initial parameter testing procedure  

and calibration has been unsuccessfully. This indication does not cause stove blockage (see the SIGNALLING POP UP  

section).  

On the display of the handheld set appears the following:  

Press and hold the ON/OFF button to turn off the stove door, and reset any alarms triggered.  

In case the infeed screw operations described avobe have not been executed, the stove may fail to turn on. In this case,  

carry out the operations described above and   empty the brazier and reset the alarm.  

If the stove still fails to turn on, check that the grate is properly installed and perfectly adherent to the base, and also check that  

there are no deposits that prevent the smooth passage of air to enable ignition. If the problem persists, contact the support ser

-

vice. 

Sequence of ignition phases  

SWITCH-ON- initial pellet loading phase; 

WAIT FLAME - flame 

development  wait  

phase; 

FLAME PRESENT - flame stabilization  

phase and reduction of combustible  

inside the brazier;  

What happens if the batteries are empty?  

If the battery is discharged, within the  

“drop” is shown a symbol that indicates  

that the battery is empty, while maintain-

ing active the features of your device.  

WORK - operation phase 

described in  

the dedicated chapter;  

As soon as the level of the battery  

prevents the radio communication  the 

handheld set displays on full screen  the 

picture of empty battery and all device 

functions are locked  until the batteries 

are replaced   

CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT, THEREFORE, NOT POWERED. MORE-

OVER, WE RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3°C IF YOU INTEND TO USE  

THE COMFORT CLIMA FUNCTION.  

Operating phases of the appliance 

Modulation 

During the work phase, the appliance should reach the room temperature set; when this condition is met, the stove switches to  

MODULATION mode in which fuel consumption and ventilation are minimum.  

If you wish to detect the ambient temperature by means of an external thermostat (optional), this must be connected to  

the appropriate connector on the rear side of the stove; and you will have to activate the reading in “SETTINGS - EN  - 

ABLE THERMOSTAT.” On display appears the writing TON / TOFF based on thermostat request.  

Comfort climate 

The activation of this function enables the stove to reduce pellet consumption by activating the modulation phases, after the desired  

temperature has been reached. Subsequently, the stove checks that the temperature is maintained steady for a preset  time. If this 

condition is met, it automatically switches off, and on display appears the writing ECO.  

The stove turns on again when the temperature drops below the set threshold. 
Below are given the steps for accessing the relative menu.  

Press the key  

“access menu” to 

access  

the  

MENU page  

Press the key  

“confirm”  

to access the  

USER page  

Once you have accessed the Climate Comfort menu, it is possible to operate on the 3 types of settings dedicated to the function:  

Press the key for several times until the Stand-by page is displayed.  

Press the key “selection” for  

“selection”  

to switch to the second page  

of USER MENU and select  

CLIMATE COMFORT.   

Summary of Contents for S70

Page 1: ...USE AND MAINTENANCE MANUAL S70 S90 SC90...

Page 2: ......

Page 3: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 4: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 5: ...uiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y manten...

Page 6: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 7: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 8: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K28162020Z1 8 Declared per...

Page 9: ...llet stove Po le granul s de bois Ravelli S 70 S90 SC90 L oggetto della dichiarazione di cui sopra conforme alla pertinente normativa di armonizzazione dell Unione The object of the declaration descri...

Page 10: ...io energetico a norma della Legge 10 91 e D P R 26 08 93 n 412 ammesse ad usufruire dei benefici fiscali connessi al contenimento dei consumi energetici negli edifici ai sensi dell art 1 comma g del D...

Page 11: ...25 Set ups for the smoke evacuation system 25 Chimney 26 Chimney pot 26 Installation 26 Requirements for the installation premises 27 Installation example for a stove pellet stove 28 Connections 30 C...

Page 12: ...ion 52 MAINTENANCE 54 Safety warnings for maintenance 54 Cleaning 54 Glass cleaning 55 Combustion chamber cleaning 55 Extraordinary maintenance 55 Combustion chamber 55 Deep combustion chamber cleanin...

Page 13: ...do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informatio...

Page 14: ...030 7301758 www ravelligroup it info ravelligroup it Reference standards The S70 S90 SC90 stoves that this manual refers to are compliant with the regulation 305 2011 CONSTRUCTION PRODUCT REGULATION...

Page 15: ...defects as long as the product has not broken sue to an incorrect use negligence incorrect connection tampering installation errors The warranty becomes null and void even if only one requirement in t...

Page 16: ...ice Symbols used in the manual symbol definition This symbol is used to identify particularly important information in the manual This information also concerns the safety of users involved in using t...

Page 17: ...integrated into the stove s design and construction as much as possible For every residual risk there is a description of the risk and the zone or part that is applies to unless the risk applies to th...

Page 18: ...isation the use is considered improper Any contractual and non contractual liability of the manufacturer is excluded for damages to persons animals or property due to installation and maintenance adju...

Page 19: ...and a variable length between 10 and 40 mm Their density is equal to approximately 650 kg m3 Due to their low water content 10 they have a high energy content The UNI EN ISO 17225 2 2014 standard that...

Page 20: ...1 Minimum draft Pa mbar 10 0 1 10 0 1 10 0 1 Electrical connection Hz V 230 50 230 50 230 50 Electrical power consumption max W 280 280 280 Electrical power consumption reduced nominal W 46 59 46 61...

Page 21: ...STATO FORMATO TUTTE LE QUOTE MANCANTI SONO DA RICAVARE DAL MODELLO 3D ALL THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA...

Page 22: ...L THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA FOGLIO 1 10 A3 30019ER01 07 12 2019 Assieme Assemblato G Domenghini G Do...

Page 23: ...om by radiation and natural convection In the SC versions it is possible to activate the ducting to heat another room The stove is controlled by an electronic control unit that manages the start up op...

Page 24: ...ot create a vacuum in the room where the stove is installed that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly...

Page 25: ...ical and not feature any bottlenecks along its entire length it must be correctly spaced with an air gap and insulated from flammable materials there must be a maximum of 2 changes in direction and an...

Page 26: ...or the power of the appliance and in any case greater than 15 m3 When extraction fans example extraction hoods are used in the same room or space as the stove this can cause problems to stove operatio...

Page 27: ...talled externally there is another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draug...

Page 28: ...segment since the ashes would quickly obstruct smoke passage causing draught problems in the stove See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fi...

Page 29: ...the appliance and must remain accessible after installation To make the electrical connection proceed as described below First connect the power cable to the plug on the back of the stove and then to...

Page 30: ...st be protected by using insulating materials or taking appropriate measures It is recommended to insulate the entire length of the ducting pipe to avoid heat dispersion It is compulsory to connect th...

Page 31: ...o S3 Sonda ambiente opt Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 LEGEND Safety dev...

Page 32: ...eft Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 M5 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 S4 LEGEND Safety devices T1 Fire d...

Page 33: ...the menu Select the desired language with the scroll buttons and confirm your selection with the confirmation button In order to operate correctly the handheld set should be interfaced with the elect...

Page 34: ...ndheld set Remove the protective cover of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the handheld s...

Page 35: ...SETTINGS DATE TIME USER COMFORT CLIMA MANUFACTURER ENGINEER ENABLE EXT TH CONTRAST FW VERSION ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into t...

Page 36: ...ld you can switch the appliance on off using the appropriate button on the electronic board The brazier is mechanically cleaned before each ignition except after the initial screw feed and in case of...

Page 37: ...DHELD TOUCH RADIO Pag 24 Vers 01 of 07 04 14 MENU USER MANUFACTURER ENGINEER USING THIS METHOD IT IS NECESSARY TO VERIFY THAT AFTER EACH AUTOMATIC SHUTDOWN THE GRATE IS ALWAYS VERY CLEAN TO GUARANTEE...

Page 38: ...equests T C Boiler From STAND BY mode press the ARROW key UP to set the room T C and DHW boiler T C that you desire Boiler water T C From STAND BY mode press the ARROW key DOWN to set the boiler water...

Page 39: ...BLE COMFORT COMFORT CLIMA DELTA COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CON...

Page 40: ...E THERMOSTAT ENABLE THERMOSTAT ENABLE EXT T ENABLE EXT T ENABLE EXT T ENABLE EXT T SEASON SEASON SEASON SEASON CONTRAST CONTRAST CONTRAST CONTRAST FW VERSION FW VERSION FW VERSION FW VERSION LANGUAGE...

Page 41: ...he value read by the room temperature probe installed inside the handheld set with respect to a reference value The value can vary from 10 C to 10 C The standard value is 0 C By pressing the following...

Page 42: ...AUTO function and activate by confirming V Press the confirm key to go to the MANUAL or AUTOMATIC selection screen Ventilation manual mode Press the Access to menu key to access the MENU screen Press...

Page 43: ...ress the confirm key to go to the item CANALIZZATA DUCTED Press the selection key to go to the item TEMPERATURE Press the key to save the parameter and to go back to the DUCTED MENU screen Press the A...

Page 44: ...e item CANALIZZATA DUCTED Press the selection key to go to the item VISUALIZZA STATO VIEW STATUS 4 2 1 1 Cubature priority active in automatic mode 2 Ducted ventilation setting 3 Ducted temperature se...

Page 45: ...temperature set is reached see the dedicated section START RESTART WAIT Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically SWITCH ON RESTA...

Page 46: ...vice The fume extractor is blocked Contact the Support Service AL 05 NO SWITCH ON The pellet tank is empty Check for the presence of pellets in the container Top up if necessary Pellet calibration and...

Page 47: ...cable connection to power the gear motor screw Check the mains voltage AL 15 SCREW TRIAC An internal part of the electronic board that controls the pellet infeed screw is faulty Check the flue is free...

Page 48: ...tphone tablet entrare nel menu Android Impostazioni Connessioni Wi Fi iOS Impostazioni Wi Fi Selezionare la rete WINET XXXXXXXX ed inserire la chiave WPA indicata nell etichetta del dispositivo wi fi...

Page 49: ...l name e g KTR AIR and then click Yes The screen offers a list of firmware once you have identified your model click on Select Yes Close the App and go to step 6 to register the account 4 CONNECTION T...

Page 50: ...n where you can register the WiFi device WiFi device registration When you click the link in the confirmation E mail the window to register the new device will open click Register your wifi device now...

Page 51: ...umber and give the module a name e g living room stove STEP 3 complete with your information click Next and then Complete registration STEP 2 enter the product serial number and give the module a name...

Page 52: ...the pellet the stove operating mode and combustion control can affect maintenance activity frequency Cleaning Perform the cleaning operations so as to guarantee correct stove operation The table belo...

Page 53: ...the scraper rod and firmly move the scraper back and forth Combustion chamber cleaning To clean the ash drawer proceed as follows step action 1 The stove requires a simple yet frequent cleaning in or...

Page 54: ...g Door gasket Chimney Smoke conduit Schedule the above extraordinary maintenance activities with the Authorised Assistance Centre Deep combustion chamber cleaning This operation must be carried out by...

Page 55: ...Centre Plan this type of cleaning with the Ravelli Service Centre When thoroughly cleaning the stove the authorised technician must check that the gaskets of port ash drawer hatches are intact If not...

Page 56: ...13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 DISEG VERIF APPR FABB Qual SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE LINEARE ANGOLARE FINITURA INTERRUZIONE BOR...

Page 57: ...d not obstructed make sure the chimney is sized for the stove power make sure that the air intake in the room is clear of any obstructions and that there are no other combustion appliances or extracti...

Page 58: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Page 59: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Page 60: ...y errors in this booklet and considers itself free to make any variations to the features of its products without notice Aico S p A Via Kupfer 31 25036 Palazzolo sull Oglio BS ITALY Tel 39 030 7402939...

Reviews: