Be careful when building the smoke evacuation system and observe the regulations in force in the country where the stove 

is installed. 

 

The Manufacturer will not be held liable for incorrectly sized and non-regulation smoke evacuation systems. 

 

Smoke ducts and fittings

The term smoke duct indicates all ducts that connect the combustion equipment to the chimney. 

The following requirements need to be applied: 

• 

observe product standard EN 1856-2;

• 

the horizontal sections must have a minimum slope of 3% upwards; 

• 

the length of the horizontal section must be as minimum as possible, and its projection on the horizontal plane must not exceed 

2 metres;

• 

changes in direction must not have an angle of more than 90° (45° bends are recommended); 

• 

the number of direction changes, including the one necessary for insertion into the chimney, must not exceed 3;

• 

the cross section must have a constant diameter, the same from where it exits the firebox up to the fitting into the chimney;

• 

it is forbidden to use flexible metal and fibre cement pipes; 

• 

smoke ducts must not cross rooms where the installation of combustion equipment is prohibited. 

In any case, the smoke ducts must be sealed against combustion products and condensation, as well as insulated if they lead outside 

of the installation room. 

Installing manual draught adjustment devices is not allowed.

Chimney 

The chimney is a particularly important element for correct stove operation. 

 

The chimney must be sized so as to guarantee the draught declared by the Manufacturer.

 

Do not connect the stove to a collective chimney.

The chimney must be built applying the following regulations: 

• 

it must observe product standard EN 1856-1; 

• 

it must be made of materials that are suitable to guarantee resistance against normal mechanical, chemical and thermal stress 

and be correctly thermally insulated to limit the formation of condensation; 

• 

it must be mainly vertical and not feature any bottlenecks along its entire length; 

• 

it must be correctly spaced with an air gap and insulated from flammable materials; 

• 

there must be a maximum of 2 changes in direction and angles must not exceed 45°; 

• 

the  chimney  inside  the  home,  however,  must  be  insulated  and  can  be  inserted  into  a  skylight  shaft,  as  long  as  it  respects 

standards regarding placing inside a tube; 

• 

the smoke conduit must be connected to the chimney using a “T” fitting with an inspection collection chamber for combustion 

residue and especially for collecting condensation. 

 

📌

It is necessary to check the safety distances that need to be observed when there are flammable materials and the type of 

insulating material that needs to be used is on the chimney data plate.

 

Use watertight pipes with silicone seals.

 

It is forbidden to use the discharge mounted directly on the wall or directed towards indoor spaces and any other type of 

discharge that is not set forth by the regulation in force in the country of installation (Note: in Italy only roof-discharge is 

allowed).

Chimney pot 

The chimney pot, i.e. the top end of the chimney, must fulfil the following characteristics: 

• 

the cross-section of the smoke outlet must be at least twice the internal cross-section of the chimney; 

• 

it must stop water or snow from getting in; 

• 

make sure the smoke is taken away even when there is wind (wind resistant chimney pot); 

• 

the outlet height must be outside of the reflux zone (refer to national and local regulations to calculate the reflux zone); 

• 

it must always be built at a distance from antennas or dishes, it must never be used as support.

Installation 

 

For appliance installation and use it is necessary to observe all of the local, national and European laws and regulations. 

 

Stove installation and the preparation of the building work must observe the regulation in force in the country of installation 

(ITALY = UNI 10683).

 

📌

The installation activities must be carried out by a technician that is qualified and/or authorised by the Manufacturer. The staff 

in charge of installation must issue a declaration of conformity of the system to the buyer, whereby they take full responsibility 

Summary of Contents for S70

Page 1: ...USE AND MAINTENANCE MANUAL S70 S90 SC90...

Page 2: ......

Page 3: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 4: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 5: ...uiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y manten...

Page 6: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 7: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 8: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K28162020Z1 8 Declared per...

Page 9: ...llet stove Po le granul s de bois Ravelli S 70 S90 SC90 L oggetto della dichiarazione di cui sopra conforme alla pertinente normativa di armonizzazione dell Unione The object of the declaration descri...

Page 10: ...io energetico a norma della Legge 10 91 e D P R 26 08 93 n 412 ammesse ad usufruire dei benefici fiscali connessi al contenimento dei consumi energetici negli edifici ai sensi dell art 1 comma g del D...

Page 11: ...25 Set ups for the smoke evacuation system 25 Chimney 26 Chimney pot 26 Installation 26 Requirements for the installation premises 27 Installation example for a stove pellet stove 28 Connections 30 C...

Page 12: ...ion 52 MAINTENANCE 54 Safety warnings for maintenance 54 Cleaning 54 Glass cleaning 55 Combustion chamber cleaning 55 Extraordinary maintenance 55 Combustion chamber 55 Deep combustion chamber cleanin...

Page 13: ...do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informatio...

Page 14: ...030 7301758 www ravelligroup it info ravelligroup it Reference standards The S70 S90 SC90 stoves that this manual refers to are compliant with the regulation 305 2011 CONSTRUCTION PRODUCT REGULATION...

Page 15: ...defects as long as the product has not broken sue to an incorrect use negligence incorrect connection tampering installation errors The warranty becomes null and void even if only one requirement in t...

Page 16: ...ice Symbols used in the manual symbol definition This symbol is used to identify particularly important information in the manual This information also concerns the safety of users involved in using t...

Page 17: ...integrated into the stove s design and construction as much as possible For every residual risk there is a description of the risk and the zone or part that is applies to unless the risk applies to th...

Page 18: ...isation the use is considered improper Any contractual and non contractual liability of the manufacturer is excluded for damages to persons animals or property due to installation and maintenance adju...

Page 19: ...and a variable length between 10 and 40 mm Their density is equal to approximately 650 kg m3 Due to their low water content 10 they have a high energy content The UNI EN ISO 17225 2 2014 standard that...

Page 20: ...1 Minimum draft Pa mbar 10 0 1 10 0 1 10 0 1 Electrical connection Hz V 230 50 230 50 230 50 Electrical power consumption max W 280 280 280 Electrical power consumption reduced nominal W 46 59 46 61...

Page 21: ...STATO FORMATO TUTTE LE QUOTE MANCANTI SONO DA RICAVARE DAL MODELLO 3D ALL THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA...

Page 22: ...L THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA FOGLIO 1 10 A3 30019ER01 07 12 2019 Assieme Assemblato G Domenghini G Do...

Page 23: ...om by radiation and natural convection In the SC versions it is possible to activate the ducting to heat another room The stove is controlled by an electronic control unit that manages the start up op...

Page 24: ...ot create a vacuum in the room where the stove is installed that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly...

Page 25: ...ical and not feature any bottlenecks along its entire length it must be correctly spaced with an air gap and insulated from flammable materials there must be a maximum of 2 changes in direction and an...

Page 26: ...or the power of the appliance and in any case greater than 15 m3 When extraction fans example extraction hoods are used in the same room or space as the stove this can cause problems to stove operatio...

Page 27: ...talled externally there is another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draug...

Page 28: ...segment since the ashes would quickly obstruct smoke passage causing draught problems in the stove See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fi...

Page 29: ...the appliance and must remain accessible after installation To make the electrical connection proceed as described below First connect the power cable to the plug on the back of the stove and then to...

Page 30: ...st be protected by using insulating materials or taking appropriate measures It is recommended to insulate the entire length of the ducting pipe to avoid heat dispersion It is compulsory to connect th...

Page 31: ...o S3 Sonda ambiente opt Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 LEGEND Safety dev...

Page 32: ...eft Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 M5 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 S4 LEGEND Safety devices T1 Fire d...

Page 33: ...the menu Select the desired language with the scroll buttons and confirm your selection with the confirmation button In order to operate correctly the handheld set should be interfaced with the elect...

Page 34: ...ndheld set Remove the protective cover of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the handheld s...

Page 35: ...SETTINGS DATE TIME USER COMFORT CLIMA MANUFACTURER ENGINEER ENABLE EXT TH CONTRAST FW VERSION ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into t...

Page 36: ...ld you can switch the appliance on off using the appropriate button on the electronic board The brazier is mechanically cleaned before each ignition except after the initial screw feed and in case of...

Page 37: ...DHELD TOUCH RADIO Pag 24 Vers 01 of 07 04 14 MENU USER MANUFACTURER ENGINEER USING THIS METHOD IT IS NECESSARY TO VERIFY THAT AFTER EACH AUTOMATIC SHUTDOWN THE GRATE IS ALWAYS VERY CLEAN TO GUARANTEE...

Page 38: ...equests T C Boiler From STAND BY mode press the ARROW key UP to set the room T C and DHW boiler T C that you desire Boiler water T C From STAND BY mode press the ARROW key DOWN to set the boiler water...

Page 39: ...BLE COMFORT COMFORT CLIMA DELTA COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CON...

Page 40: ...E THERMOSTAT ENABLE THERMOSTAT ENABLE EXT T ENABLE EXT T ENABLE EXT T ENABLE EXT T SEASON SEASON SEASON SEASON CONTRAST CONTRAST CONTRAST CONTRAST FW VERSION FW VERSION FW VERSION FW VERSION LANGUAGE...

Page 41: ...he value read by the room temperature probe installed inside the handheld set with respect to a reference value The value can vary from 10 C to 10 C The standard value is 0 C By pressing the following...

Page 42: ...AUTO function and activate by confirming V Press the confirm key to go to the MANUAL or AUTOMATIC selection screen Ventilation manual mode Press the Access to menu key to access the MENU screen Press...

Page 43: ...ress the confirm key to go to the item CANALIZZATA DUCTED Press the selection key to go to the item TEMPERATURE Press the key to save the parameter and to go back to the DUCTED MENU screen Press the A...

Page 44: ...e item CANALIZZATA DUCTED Press the selection key to go to the item VISUALIZZA STATO VIEW STATUS 4 2 1 1 Cubature priority active in automatic mode 2 Ducted ventilation setting 3 Ducted temperature se...

Page 45: ...temperature set is reached see the dedicated section START RESTART WAIT Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically SWITCH ON RESTA...

Page 46: ...vice The fume extractor is blocked Contact the Support Service AL 05 NO SWITCH ON The pellet tank is empty Check for the presence of pellets in the container Top up if necessary Pellet calibration and...

Page 47: ...cable connection to power the gear motor screw Check the mains voltage AL 15 SCREW TRIAC An internal part of the electronic board that controls the pellet infeed screw is faulty Check the flue is free...

Page 48: ...tphone tablet entrare nel menu Android Impostazioni Connessioni Wi Fi iOS Impostazioni Wi Fi Selezionare la rete WINET XXXXXXXX ed inserire la chiave WPA indicata nell etichetta del dispositivo wi fi...

Page 49: ...l name e g KTR AIR and then click Yes The screen offers a list of firmware once you have identified your model click on Select Yes Close the App and go to step 6 to register the account 4 CONNECTION T...

Page 50: ...n where you can register the WiFi device WiFi device registration When you click the link in the confirmation E mail the window to register the new device will open click Register your wifi device now...

Page 51: ...umber and give the module a name e g living room stove STEP 3 complete with your information click Next and then Complete registration STEP 2 enter the product serial number and give the module a name...

Page 52: ...the pellet the stove operating mode and combustion control can affect maintenance activity frequency Cleaning Perform the cleaning operations so as to guarantee correct stove operation The table belo...

Page 53: ...the scraper rod and firmly move the scraper back and forth Combustion chamber cleaning To clean the ash drawer proceed as follows step action 1 The stove requires a simple yet frequent cleaning in or...

Page 54: ...g Door gasket Chimney Smoke conduit Schedule the above extraordinary maintenance activities with the Authorised Assistance Centre Deep combustion chamber cleaning This operation must be carried out by...

Page 55: ...Centre Plan this type of cleaning with the Ravelli Service Centre When thoroughly cleaning the stove the authorised technician must check that the gaskets of port ash drawer hatches are intact If not...

Page 56: ...13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 DISEG VERIF APPR FABB Qual SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE LINEARE ANGOLARE FINITURA INTERRUZIONE BOR...

Page 57: ...d not obstructed make sure the chimney is sized for the stove power make sure that the air intake in the room is clear of any obstructions and that there are no other combustion appliances or extracti...

Page 58: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Page 59: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Page 60: ...y errors in this booklet and considers itself free to make any variations to the features of its products without notice Aico S p A Via Kupfer 31 25036 Palazzolo sull Oglio BS ITALY Tel 39 030 7402939...

Reviews: