background image

Use and maintenance manual S70 - S90 - SC90

Pag.38 

Rev.0  18/05/2020

Chronothermostat

With the Chrono-thermostat function you can program the automatic switch ON/OFF of the stove for each day of the week for each 

day of the week in 4 independent time intervals (SET CHRONO 1-2-3-4). Below are given the steps for accessing the relative menu 

starting from “Home” mode.

            To exit the page and return to “Home” page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Air - pellet set    

The setting of the PELLET-FLUSSO mixture allows to adjust the combustion by varying the quantity of pellets loaded in the brazier and/

or the quantity of air. In fact, by its nature, pellets vary in grain size and composition: even bags of pellets of the same brand can have 

different characteristics. 

If combustion is not optimal, vary the flow parameter to adjust the combustion air. If air regulation alone is not sufficient, it may also be 

necessary to modify the pellet parameter.

 

Combustion regulation is an operation that requires a lot of experience. We recommend that you contact an Authorised 

Service Centre to calibrate the stove appropriately.

To exit the screen and return to the home screen, press the key repeatedly.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.32 

Pag.33 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

VERSION FW.

Press the key

“confirm”

to access the function

To access the next setting, follow the steps given above or simply remove and replace the batteries.

The device resets and prompts you again to select the language you want to set.

Settings > Language

Settings > Adjust

Use the UP/DOWN keys to change the value read by the 

room temperature probe installed inside the handheld 

set, with respect to a reference value.

  The value can vary from -10°C to 10°C.

The standard value is 0°C.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu

The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and

the room temperature fan installed inside them.

Below are the messages shown on display when the stove is equipped with ventilation system.

            To exit the page and return to Stand-by page, press the button repeatedly.

VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)

Control: v

entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting 

the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

            To exit the page and return to Stand-by page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Press the key

“enter” at the end of the

setting, from the following

CHRONO page

The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by 

adjusting the stove, set the fan to A mode as shown in the relative chapter.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“confirm”

to quickly switch to

VENTILATION.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

Pages displayed upon the activation of advanced layouts

By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will 

display all connected utilities such as the temperature of the boiler of the puffer.  

Below is shown the new display mode and the function of every icon for every layout, to change the various settings.

Layout 1 (DHW heating control)

The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer

that should be connected to the circuit to produce hot domestic water.

In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote

chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly 

to the back of the stove. Below is shown the new “Stand-by” mode.

By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output 

by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.

The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the

boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within

the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room

temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).

The 3-way valve is directed again into the boiler when:

- there is a request from the Boiler;

- there is a requested from the flow switch (optional, if connected).

The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.

T°C Boiler

From STAND BY mode, press

the ARROW key UP

to set the

room T°C

and DHW boiler T°C that you

desire.

Boiler water T°C

From STAND BY mode, press

the ARROW key DOWN

to set

the boiler water T°C

that you desire.

Press the key

“V” from STAND BY page

to display the actuale states and

the room temperature

Chrono function

By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

CRONO-THERMOSTAT.

If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the

optional kit from the retailer or the authorized Ravelli dealer.

DATE-TIME

DATE-TIME

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

CONTRAST

CONTRAST

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

MENU

USER

TECHNICIAN

VENTILATION POW.

USER

POWER SETTING

CHRONOTHERMOSTAT

SCREW LOADING

SET AIR-PELLET

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

POWER SETTING

SET AIR-PELLET

SET AIR-PELLET

CHRONOTHERMOSTAT

CHRONOTHERMOSTAT

SCREW LOADING

SCREW LOADING

CHRONO

CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

VENTILATION POW.

SET CHRONO 1

SET CHRONO 1

SET CHRONO 2

SET CHRONO 2

SET CHRONO 3

SET CHRONO 3

SET CHRONO 4

SET CHRONO 4

POWER                    MOD

PUMP
3-WAY VALVE         HEAT
PRESSURE  1.1 BAR
HH T .     

21°C

MANUFACTURER’S

MANUFACTURER’S

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.32 

Pag.33 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

VERSION FW.

Press the key

“confirm”

to access the function

To access the next setting, follow the steps given above or simply remove and replace the batteries.

The device resets and prompts you again to select the language you want to set.

Settings > Language

Settings > Adjust

Use the UP/DOWN keys to change the value read by the 

room temperature probe installed inside the handheld 

set, with respect to a reference value.

  The value can vary from -10°C to 10°C.

The standard value is 0°C.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu

The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and

the room temperature fan installed inside them.

Below are the messages shown on display when the stove is equipped with ventilation system.

            To exit the page and return to Stand-by page, press the button repeatedly.

VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)

Control: v

entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting 

the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

            To exit the page and return to Stand-by page, press the button repeatedly.

The exit key shows the CHRONO menu to set other variables related to the menu functions.

Press the key

“enter” at the end of the

setting, from the following

CHRONO page

The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by 

adjusting the stove, set the fan to A mode as shown in the relative chapter.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“confirm”

to quickly switch to

VENTILATION.

Press the increase/decrease keys

“increase/decrease”

to change the ventilation.

Pages displayed upon the activation of advanced layouts

By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will 

display all connected utilities such as the temperature of the boiler of the puffer.  

Below is shown the new display mode and the function of every icon for every layout, to change the various settings.

Layout 1 (DHW heating control)

The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer

that should be connected to the circuit to produce hot domestic water.

In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote

chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly 

to the back of the stove. Below is shown the new “Stand-by” mode.

By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output 

by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.

The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the

boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within

the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room

temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).

The 3-way valve is directed again into the boiler when:

- there is a request from the Boiler;

- there is a requested from the flow switch (optional, if connected).

The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.

T°C Boiler

From STAND BY mode, press

the ARROW key UP

to set the

room T°C

and DHW boiler T°C that you

desire.

Boiler water T°C

From STAND BY mode, press

the ARROW key DOWN

to set

the boiler water T°C

that you desire.

Press the key

“V” from STAND BY page

to display the actuale states and

the room temperature

Chrono function

By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

CRONO-THERMOSTAT.

If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the

optional kit from the retailer or the authorized Ravelli dealer.

DATE-TIME

DATE-TIME

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

CONTRAST

CONTRAST

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

MENU

USER

TECHNICIAN

VENTILATION POW.

USER

POWER SETTING

CHRONOTHERMOSTAT

SCREW LOADING

SET AIR-PELLET

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

POWER SETTING

SET AIR-PELLET

SET AIR-PELLET

CHRONOTHERMOSTAT

CHRONOTHERMOSTAT

SCREW LOADING

SCREW LOADING

CHRONO

CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

ENABLE CHRONO

VENTILATION POW.

SET CHRONO 1

SET CHRONO 1

SET CHRONO 2

SET CHRONO 2

SET CHRONO 3

SET CHRONO 3

SET CHRONO 4

SET CHRONO 4

POWER                    MOD

PUMP
3-WAY VALVE         HEAT
PRESSURE  1.1 BAR
HH T .     

21°C

MANUFACTURER’S

MANUFACTURER’S

1

Ignition time

2

Shutdown time

3

Day of the week when the 

program is active

4

Program number “chrono” 

5

Power setting

6

Setting the room temperatures

1

2

3

4

5

6

Select SET AIR-PELLET 

and press the CONFIRM 

button.

Use the UP and DOWN 

keys to change the % pellet 

value.

Press the CONFIRM button 

to confirm the value and

go to the item % change 

flow.

Use the UP and DOWN buttons to change the 

flow % value. Press the CONFIRM button to 

confirm the value and

change to the item % pellets.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

Press the selection 

keys to navigate the 

menu screens.

USER.

Manuale utente PALMARE IDRO TOUCH RADIO     

Manuale utente PALMARE IDRO TOUCH RADIO     

Pag.30 

Pag.31 

Vers. 01 del 07/04/15

Vers. 01 del 07/04/15

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Stove State

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

several times

to quickly switch to

Stove STATUS.

            To exit the STOVE STATE page and return to Stand-by page, press the button repeatedly.

In this mode you can check the proper operation of the most important parameters of the appliance. Here is a list of real data of the 

stove useful for service during inspection.

- Circulator state (ON running)

- Position of 3-way valve DHW (domestic hot water) or HEAT (heating);

- System pressure;

- Stove state;

- Current boiler power;

- Flow read by the flow meter;

- Fume extractor speed;

- Actual flow set;

Settings > Enable thermostat

Press the “enter” key

to access the

SETTINGS

Press the key

“selection” to switch to

ENABLE THERMOSTAT.

Press the key

“confirm”

to access the function

Press the key

“confirm”

to enable the function.

In Stand-By mode, instead of room temperature measured

and settable, appears the line T ON if the room in which 

the thermostat is installed has not reached the temperature 

requested  or  the  writing  T  OFF  if  the  temperature  in  the 

room is reached.

Press the key for several 

times

to return to 

“STAND BY” page

- Temperature read by the handheld unit;

- External thermostat (request ON);

- Flame temperature (combustion chamber);

- Combustion fume exhaust temperature;

- Inlet flow meter temperature;

- Heated flow meter temp.;

- Electronic board temperature;

- Boiler water temperature (SUPPLY);

- Boiler water temperature (optional) - RETURN from the system;

- Boiler DHW temperature;

- Puffer  temperature - average warm point;

- Puffer  temperature second reading (low temp.).

Below are given the steps for accessing the relative menu starting from Stand-By mode.

Settings

Press the key

“access menu” to

access the

MENU page

Press the key

“confirm”

to access the

USER page

Press the key

“selection” to switch to

second menu page

to the function

SETTINGS.

After following the procedure above step by step, you can set the following functions:

Settings > Contrast

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use the UP/DOWN keys to change contrast setting and obtain 

a better visualisation of the information shown on the handheld 

set.

The  value  can  vary  from  0  to  100.  50  with  respect  to  the 

standard value.

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Settings > Season

Press the key

“confirm” to

access the

SETUP

SETTINGS

Press the key

“selection”  to switch

to the function

CONTRAST.

Press the key

“confirm”

to access the function

Use  the  UP/DOWN  keys  to  change  the  WINTER/

SUMMER season. Function that can be set when 

working with DHW puffer (Boiler).

See chap. Evolved hydraulic diagrams

By pressing the following  key you will confirm of data 

and switch to the page within SETTINGS menu.

Press the “enter” key to

access the

SETTINGS

Press the key

“selection” to switch to

CONTRAST.

Press the key

“confirm”

to access the function

Settings > Firmware version

By pressing the button you will confirm the data and switch to the page within the SETTINGS menu.

MENU

STOVE STATE

STOVE STATE

STOVE STATE

STOVE STATE

USER

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTIVE PARTS

ACTUAL STATES

PUMP

PRESSURE   1.1 BAR

SHUTDOWN

POWER MOD

HH T …

EXT.T …

FLAME T 340°C

FUME T   120°C

F. EX. T   30°C

C. EX. T    55°C

EL B. T---25°C

T. CALDERA
T.PUFFER H
T.PUFFER L

3-WAY VALVE   HEAT

ACTUAL STATES

ACTUAL STATES

ACTUAL STATES

H20 TEMPERATURE

H20 TEMPERATURE

v

H20 TEMPERATURE

TECHNICIAN

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

STATE TEMPERATURE

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

DATE-TIME

WINTER

CONTRAST

FIRMWARE

SUMMER

DATE-TIME

ENABLE THERMOSTAT

ENABLE THERMOSTAT

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

ENABLE EXT. T

SEASON

SEASON

SEASON

SEASON

SEASON

SEASON

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

CONTRAST

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

FW VERSION

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

LANGUAGE

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

DATE-TIME

ENABLE EXT. T

SEASON

CONTRAST

FW VERSION

LANGUAGE

ADJUST

MENU

USER

TECHNICIAN

USER

USER

POWER SETTING

STOVE STATE

CHRONOTHERMOSTAT

COMFROT CLIMA

SCREW LOADING

SETTING

SET AIR-PELLET

MANUFACTURER’S

MANUFACTURER’S

% Flow

% Flow

Summary of Contents for S70

Page 1: ...USE AND MAINTENANCE MANUAL S70 S90 SC90...

Page 2: ......

Page 3: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 4: ...ruiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y mante...

Page 5: ...uiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y manten...

Page 6: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 7: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K12332020E8 8 Declared perf...

Page 8: ...The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K28162020Z1 8 Declared per...

Page 9: ...llet stove Po le granul s de bois Ravelli S 70 S90 SC90 L oggetto della dichiarazione di cui sopra conforme alla pertinente normativa di armonizzazione dell Unione The object of the declaration descri...

Page 10: ...io energetico a norma della Legge 10 91 e D P R 26 08 93 n 412 ammesse ad usufruire dei benefici fiscali connessi al contenimento dei consumi energetici negli edifici ai sensi dell art 1 comma g del D...

Page 11: ...25 Set ups for the smoke evacuation system 25 Chimney 26 Chimney pot 26 Installation 26 Requirements for the installation premises 27 Installation example for a stove pellet stove 28 Connections 30 C...

Page 12: ...ion 52 MAINTENANCE 54 Safety warnings for maintenance 54 Cleaning 54 Glass cleaning 55 Combustion chamber cleaning 55 Extraordinary maintenance 55 Combustion chamber 55 Deep combustion chamber cleanin...

Page 13: ...do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informatio...

Page 14: ...030 7301758 www ravelligroup it info ravelligroup it Reference standards The S70 S90 SC90 stoves that this manual refers to are compliant with the regulation 305 2011 CONSTRUCTION PRODUCT REGULATION...

Page 15: ...defects as long as the product has not broken sue to an incorrect use negligence incorrect connection tampering installation errors The warranty becomes null and void even if only one requirement in t...

Page 16: ...ice Symbols used in the manual symbol definition This symbol is used to identify particularly important information in the manual This information also concerns the safety of users involved in using t...

Page 17: ...integrated into the stove s design and construction as much as possible For every residual risk there is a description of the risk and the zone or part that is applies to unless the risk applies to th...

Page 18: ...isation the use is considered improper Any contractual and non contractual liability of the manufacturer is excluded for damages to persons animals or property due to installation and maintenance adju...

Page 19: ...and a variable length between 10 and 40 mm Their density is equal to approximately 650 kg m3 Due to their low water content 10 they have a high energy content The UNI EN ISO 17225 2 2014 standard that...

Page 20: ...1 Minimum draft Pa mbar 10 0 1 10 0 1 10 0 1 Electrical connection Hz V 230 50 230 50 230 50 Electrical power consumption max W 280 280 280 Electrical power consumption reduced nominal W 46 59 46 61...

Page 21: ...STATO FORMATO TUTTE LE QUOTE MANCANTI SONO DA RICAVARE DAL MODELLO 3D ALL THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA...

Page 22: ...L THE MISSING MEASUREMENTS CAN BE FOUND IN THE 3D MODEL SCALA DISEGNATO MASSA CONTROLLATO DATA GRUPPO DI APPARTENENZA TIPOLOGIA FOGLIO 1 10 A3 30019ER01 07 12 2019 Assieme Assemblato G Domenghini G Do...

Page 23: ...om by radiation and natural convection In the SC versions it is possible to activate the ducting to heat another room The stove is controlled by an electronic control unit that manages the start up op...

Page 24: ...ot create a vacuum in the room where the stove is installed that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly...

Page 25: ...ical and not feature any bottlenecks along its entire length it must be correctly spaced with an air gap and insulated from flammable materials there must be a maximum of 2 changes in direction and an...

Page 26: ...or the power of the appliance and in any case greater than 15 m3 When extraction fans example extraction hoods are used in the same room or space as the stove this can cause problems to stove operatio...

Page 27: ...talled externally there is another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draug...

Page 28: ...segment since the ashes would quickly obstruct smoke passage causing draught problems in the stove See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fi...

Page 29: ...the appliance and must remain accessible after installation To make the electrical connection proceed as described below First connect the power cable to the plug on the back of the stove and then to...

Page 30: ...st be protected by using insulating materials or taking appropriate measures It is recommended to insulate the entire length of the ducting pipe to avoid heat dispersion It is compulsory to connect th...

Page 31: ...o S3 Sonda ambiente opt Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 LEGEND Safety dev...

Page 32: ...eft Generico G1 Debimetro G2 Encoder lettura giri estrattore G3 Palmare RADIO Touch M1 M2 M3 M5 S1 R1 S2 G1 G2 G3 nero rosso bianco T2 T1 RETE ALIMENTAZIONE 220 V S3 S4 LEGEND Safety devices T1 Fire d...

Page 33: ...the menu Select the desired language with the scroll buttons and confirm your selection with the confirmation button In order to operate correctly the handheld set should be interfaced with the elect...

Page 34: ...ndheld set Remove the protective cover of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the handheld s...

Page 35: ...SETTINGS DATE TIME USER COMFORT CLIMA MANUFACTURER ENGINEER ENABLE EXT TH CONTRAST FW VERSION ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into t...

Page 36: ...ld you can switch the appliance on off using the appropriate button on the electronic board The brazier is mechanically cleaned before each ignition except after the initial screw feed and in case of...

Page 37: ...DHELD TOUCH RADIO Pag 24 Vers 01 of 07 04 14 MENU USER MANUFACTURER ENGINEER USING THIS METHOD IT IS NECESSARY TO VERIFY THAT AFTER EACH AUTOMATIC SHUTDOWN THE GRATE IS ALWAYS VERY CLEAN TO GUARANTEE...

Page 38: ...equests T C Boiler From STAND BY mode press the ARROW key UP to set the room T C and DHW boiler T C that you desire Boiler water T C From STAND BY mode press the ARROW key DOWN to set the boiler water...

Page 39: ...BLE COMFORT COMFORT CLIMA DELTA COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CON...

Page 40: ...E THERMOSTAT ENABLE THERMOSTAT ENABLE EXT T ENABLE EXT T ENABLE EXT T ENABLE EXT T SEASON SEASON SEASON SEASON CONTRAST CONTRAST CONTRAST CONTRAST FW VERSION FW VERSION FW VERSION FW VERSION LANGUAGE...

Page 41: ...he value read by the room temperature probe installed inside the handheld set with respect to a reference value The value can vary from 10 C to 10 C The standard value is 0 C By pressing the following...

Page 42: ...AUTO function and activate by confirming V Press the confirm key to go to the MANUAL or AUTOMATIC selection screen Ventilation manual mode Press the Access to menu key to access the MENU screen Press...

Page 43: ...ress the confirm key to go to the item CANALIZZATA DUCTED Press the selection key to go to the item TEMPERATURE Press the key to save the parameter and to go back to the DUCTED MENU screen Press the A...

Page 44: ...e item CANALIZZATA DUCTED Press the selection key to go to the item VISUALIZZA STATO VIEW STATUS 4 2 1 1 Cubature priority active in automatic mode 2 Ducted ventilation setting 3 Ducted temperature se...

Page 45: ...temperature set is reached see the dedicated section START RESTART WAIT Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically SWITCH ON RESTA...

Page 46: ...vice The fume extractor is blocked Contact the Support Service AL 05 NO SWITCH ON The pellet tank is empty Check for the presence of pellets in the container Top up if necessary Pellet calibration and...

Page 47: ...cable connection to power the gear motor screw Check the mains voltage AL 15 SCREW TRIAC An internal part of the electronic board that controls the pellet infeed screw is faulty Check the flue is free...

Page 48: ...tphone tablet entrare nel menu Android Impostazioni Connessioni Wi Fi iOS Impostazioni Wi Fi Selezionare la rete WINET XXXXXXXX ed inserire la chiave WPA indicata nell etichetta del dispositivo wi fi...

Page 49: ...l name e g KTR AIR and then click Yes The screen offers a list of firmware once you have identified your model click on Select Yes Close the App and go to step 6 to register the account 4 CONNECTION T...

Page 50: ...n where you can register the WiFi device WiFi device registration When you click the link in the confirmation E mail the window to register the new device will open click Register your wifi device now...

Page 51: ...umber and give the module a name e g living room stove STEP 3 complete with your information click Next and then Complete registration STEP 2 enter the product serial number and give the module a name...

Page 52: ...the pellet the stove operating mode and combustion control can affect maintenance activity frequency Cleaning Perform the cleaning operations so as to guarantee correct stove operation The table belo...

Page 53: ...the scraper rod and firmly move the scraper back and forth Combustion chamber cleaning To clean the ash drawer proceed as follows step action 1 The stove requires a simple yet frequent cleaning in or...

Page 54: ...g Door gasket Chimney Smoke conduit Schedule the above extraordinary maintenance activities with the Authorised Assistance Centre Deep combustion chamber cleaning This operation must be carried out by...

Page 55: ...Centre Plan this type of cleaning with the Ravelli Service Centre When thoroughly cleaning the stove the authorised technician must check that the gaskets of port ash drawer hatches are intact If not...

Page 56: ...13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 DISEG VERIF APPR FABB Qual SE NON SPECIFICATO QUOTE IN MILLIMETRI FINITURA SUPERFICIE TOLLERANZE LINEARE ANGOLARE FINITURA INTERRUZIONE BOR...

Page 57: ...d not obstructed make sure the chimney is sized for the stove power make sure that the air intake in the room is clear of any obstructions and that there are no other combustion appliances or extracti...

Page 58: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Page 59: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Page 60: ...y errors in this booklet and considers itself free to make any variations to the features of its products without notice Aico S p A Via Kupfer 31 25036 Palazzolo sull Oglio BS ITALY Tel 39 030 7402939...

Reviews: