Use and maintenance manual
RBV 8008 - RBV 8010
Pag.38
Rev.1 18/05/2021
FLAME
DESCRIPTION
RDS SYSTEM ADJUSTMENT
REQUEST
(only if the RDS system is provi-
ded)
It shows that the testing procedure and initial parameter calibration have not been completed
or have been performed incorrectly. This indication, however, does not block the stove.
SERVICE REQUEST
The threshold value of set work hours has been reached. The symbol displayed remains
active throughout the work phase. Non-routine maintenance is required on the stove.
AIR FLOW METER FAILU
-
RE
(only if the RDS system is provi-
ded)
It shows a failure of the air flow meter and the stove switches to minimum capacity disabling
the RDS system.
Warning Pop-Up
REASON
SOLUTION
• The door and the ash box are not closed correctly
• Make sure they are properly closed.
• Poor combustion in grate.
• Switch off the stove, clean the brazier and check the cleanliness of the
support bench, clean the tube bundle by activating the turbolators. and
adjust the combustion through Pellet/Air settings.
• Presence of foreign body in air intake tube.
• Check for any foreign body and remove it
• The air flow meter may be dirty.
• Clean the flow meter with the stove in "Switched off" state
• Contact the Support Service
SIGNALLING
RUN
BRAZIER CLEANING
(only if the RDS system is
provided)
The appearance of the message “ADJUST THE RDS SYSTEM” indicates that the initial parameter testing procedure and
calibration has been unsuccessfully. This indication does not block the stove.
Adjust RDS
system
modulate
Alarms (table with reference codes)
TRIAL
TITLE
REASON
SOLUTION
AL 01 BLACK OUT
- No voltage during work phase
- Press the switch off key and switch on
boiler switch-on.
- If the problem persists, contact the Support
Service
AL 02 FUME PROBE
- The fume probe is malfunctioning
- Contact the Support Service
- The fume probe is disconnected from the
electronic board
- Contact the Support Service
AL 03 FUME OVERTEMP.
- Combustion in the brazier is not optimal due to
clogging or obstructions of internal stove ducts
- Switch off the stove, clean the brazier and the
tube bundle and adjust the combustion setting
the Pellet/Air values
- The tangential fan (if provided) is
malfunctioning or damaged
- Contact the Support Service
- If the problem persists, contact the Support
Service
AL 04 FUME EXHAUST DAMAGED
- Fume exhaust encoder is not working or is
connected incorrectly
- Contact the Support Service
- No power to fume exhaust system
- Contact the Support Service
- The fume exhaust system is blocked
- Contact the Support Service
AL 05 NO SWITCH-ON
- The pellet tank is empty
- Check for the presence of pellets in the
container. Top up, if necessary.
- Pellet calibration and suction during switch on
phase is incorrect.
- Contact the Support Service
- The igntition coil is faulty or positioned
- Contact the Support Service
GENERIC ALARM
The stove is in alarm state; refer to the throubleshooting chapter.
ANOMALY (general)
The stove has detected an anomaly; refer to the throubleshooting chapter.
Summary of Contents for RBV 8008
Page 2: ...RBV 8008 RBV 8010 MANUALE D USO E MANUTENZIONE...
Page 3: ......
Page 7: ...RBV 8010 RBV 8008 RBV 8010...
Page 9: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 50: ...RBV 8008 RBV 8010 MANUEL D UTILISATION ET D ENTRETIEN...
Page 51: ......
Page 55: ...RBV 8010 RBV 8008 RBV 8010...
Page 56: ......
Page 57: ......
Page 95: ......
Page 96: ......
Page 98: ...RBV 8008 RBV 8010 USE AND MAINTENANCE MANUAL...
Page 99: ......
Page 103: ...RBV 8010 RBV 8008 RBV 8010...
Page 104: ......
Page 105: ......
Page 143: ......
Page 144: ......
Page 146: ...RBV 8008 RBV 8010 BEDIENUNGS UND WARTUNGSHANDBUCH...
Page 147: ......
Page 151: ...RBV 8010 RBV 8008 RBV 8010...
Page 152: ......
Page 153: ......
Page 191: ......
Page 192: ......
Page 194: ...RBV 8008 RBV 8010 MANUAL DE USO Y MANTENIMIENTO...
Page 195: ......
Page 199: ...RBV 8010 RBV 8008 RBV 8010...
Page 200: ......
Page 201: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 242: ...HANDLEIDING VOOR GEBRUIK EN ONDERHOUD RBV 8008 RBV 8010...
Page 243: ......
Page 249: ......
Page 290: ......
Page 291: ......
Page 292: ......