RE / DD / UM / 2508 V1.2- 01
66
6.5
Trouble Shooting:
Condition
Root Cause
Remedy
There is no
indication on
the panel
No power to the
Panel
Check Primary (AC)
power and Standby
power.
During Mains fail
condition Battery
fault LED is
glowing
May be battery low
(<21.6V) or the
battery reaches the
de-rated (<19.5V)
Voltage.
Check the Battery
voltage and charge the
battery or replace the
battery.
The Battery
fault and
charger fail
shown in LCD.
The Battery
connected in
reverse.
Connect the battery
properly.