5.3.6.
Alarm Verification:
This Alarm verification feature is applicable only to the IDC’s
in the zone in which only smoke detectors are used.
If the alarm verification is selected IDC, the smoke detector
activation will cause the FAP to reset the detector by
removing the power for 3.5 Seconds. Power is reapplied to the
detectors and restart period 12 Seconds begins to stabilize all
the detectors. If no other detector alarm, there will no alarm
indication in FAP during Retard - Reset - restart period. During
the conformation period of 60 seconds, the subsequent alarm
in the same detector will cause FAP to activate immediately
appropriate outputs and indicates alarm indication in the FAP.
During this conformation period or Reset & Retard period, if
there is any alarm in other zone, the panel activates
immediately appropriate outputs in FAP.
Figure - 24