6/28/2011 DOC.NO.: 150D - 1
P/N RE 150D Rev. No. 1
19
3.4
Output Circuits
Sounder Circuits:
The RE – 150D provides Notification Appliance
Circuits standard as Class B. The total load capacity of this circuit is
capacity of this O/P may be calculated as no. of zones X 0.2Amps.
Sounder Circuit – Class B
Note:
If the non polarized devices are used, connect the device as
mentioned in page 27.
Standard Relay
The control panel provides three Form-C relays rated for 2.0 amps @
30 VDC and 2.0 amps @ 30 VAC.
Relay connections may be power-limited or nonpower-limited,
provided that a minimum of 0.25" is maintained between conductors
of power-limited and nonpower-limited circuits.