2.2
Specification
AC Power
220-240 VAC, 50 Hz.
Wire size: 1.5 Sq. mm with 600V insulation
Battery (Lead Acid only)
Charging: Constant Voltage – 27.6v @ 0.5A
Charging Capacity: 26 Amp Hour Battery Max.
System Quiescent Current: 70mA + (4.4 – 6.8mA per zone)
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage: Nominal 24 VDC
Alarm Current: 15 – 35mA threshold
Short Circuit Current: 42mA Maximum
Loop resistance: 50 ohms Maximum
End-Of-Line Resistor: 4.7K, 1/4watt
Standby Current: 6.8mA (2.4mA for Detectors)
Notification Appliance Circuits (Sounder Circuit)
Class – B wiring
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output: 0.2A X No. of zone
End-Of-Line Resistor: 4.7K, 1/4watt
Three Form – C Relays
Relay Contact Rating: 2Amps @ 30 VDC, 2Amps @ 30VAC (Fire – 3
No’s).
24 VDC Power – For remote devices
Operating Voltage: 24VDC, 500mA Max.