RAPIX DALI-2 Relay DGOZ-RLY-16A-01 / DGOZ-RLY-16A-02 

 

 

Page 2 of 4 

Wiring 

To operate correctly, the DALI Relays must be connected to ac mains voltage and a DALI line, as shown below. 

One Channel Relay 

Two Channel Relay 

 

 

Notes: 

 

The R

elays are not ‘voltage

-

free’ type: The

 load (switched line) output has an internal high impedance connection to 

Line input. 

 

The mains earth connection is optional and is not internally connected. Only the Mains Line & Neutral connections are 
required. If a 3-core cable with Earth conductor is used, the included Earth bar can be used to loop the Earth wire. 

 

If required, the Neutral and Earth bars can be used to loop 3-core cables to the load or other parts of the circuit. 

Cable entry tabs/knockouts for 1.5mm2, 2.5mm2 and 5-Core modular cables 

The terminal cover includes cable entry tabs/knockouts for use with typical 1.5 mm

2

 and 2.5 mm

2

 Flat TPS/building cable. 

 

 

Tab locations 

Tab pushed backwards to accommodate 1.5mm

2

 cable 

 

 

Tab removed to accommodate 2.5mm

2

 cable 

Circular knockout removed to accommodate 5-core modular 

wiring cable 

Use cable ties to secure DALI mains supply and switched output cables 

The base of the cable termination area has slots to tie down cables.  Knockouts for 
additional cable ties are also provided. Cable ties are included with the Relay. 

Commissioning 

To operate correctly, the DALI Relay must be programmed with the appropriate DALI 
addresses. Depending on application, the following parameters may need to be configured: 

 

DALI Short Address; 

 

DALI Group Address(s); 

 

DALI Scene Address(s); 

 

Minimum Level and Maximum Level; 

 

Power On Level and System Failure Level; 

 

Fade Time and Fade Rate. 

These parameters can be configured using 

RAPIX 

software, or any other DALI software which allows these standard DALI 

parameters to be configured in a DALI Compliant Relay device. 