Chimney
Flue
Masonry
Insulated
Chimney
Connector Pipe
18” (46cm) below ceiling
Min.
2” (5cm)
Min.
2” (5cm)
B.
A.
E.
F.
C.
D.
B.
US
INSTALLATION
For rear venting or other unlisted configura-
tions, consult the local building codes and fol-
low the NFPA 211 guidelines.
If the stovepipe is fitted with a baffle, it must
be manually operated, visibly placed for ease
of use, and must not close completely. Con-
sult your chimney expert if you have any ques-
tions.
For venting vertically into a Class A chimney,
a single wall pipe (at least 24 gauge) may be
used in the room where the stove is installed.
Refer to the manufacturer’s instructions for
the connection to the listed chimney. The
chimney/stove pipe must not be smaller than
6” (15cm) in diameter.
For venting directly into a masonry chimney
or through a thimble, the top of the single wall
pipe must be at least 18” (46cm) below a com-
bustible ceiling and must conform to NFPA
211 guidelines and methods. Please see the
diagram to the left.
Required Installation Components:
A. Chimney Cap
B. Insulated Chimney
C. Storm Collar
D. Roof Flashing
E. Ceiling Support Box or Joist Shield/Firestop
Spacer
F. Chimney Connector
NOTE!
Please ensure that there is easy access to the chimney cleanout door.
INSTALLATION