51
Radijator Inženjering d.o.o, 36000 Kraljevo, Živojina Lazića - Solunca br.6, Srbija
tel. +381 36 399 140, fax. +381 36 399 150, http://www.radijator.rs
The degree of utilization on pellets exceeds 90%. On normal modes, the temperature of flue
gases on exit is around 160°C, and on maximum modes is below 180°C. These values can be read on
the display at any moment.
Industrial TKAN boilers
have
the exchanger made of seamless pipes for the installation of
vents
for thermal leakage protection
. On these boilers, the existing sockets enable easy installation of
vents that directly load water into the boiler for thermal protection.
All parts of the water part of the boiler are made of seamless pipes (quality
ST 35.4
) and at least
5mm thick boiler sheets depending on the power of the boiler. Sheets are
1.0425 EU
standard
(speaking of quality), more precisely
P265GH
standard
EUII.
According to its principle of operation, the furnace is the so-called ‘spring’, where the fuel from
the transport zone goes vertically upwards, that is springs to the combustion zone. It is made of
massive insulation materials and grey cast iron. Fuel transport is ensured by screw conveyors. The
fuel comes from the silo capable of holding from 457l to 1610l depending on the size of the boiler.
When needed, it is easy to disassemble everything into three separate units: a silo (
picture 1, position
4
), a loading mechanism (
picture 1, position 3
), and a boiler with a furnace (
picture 1, positions
1 and 2
). A separate assembly within the furnace stands out – a semi-automatic boiler cleaning.
Boiler TKAN 60 does not have a screw axle for ejecting ash inside the furnace. Boilers TKAN 80
and TKAN 100 have one screw axle each, and TKAN 150 and higher, that is TKAN 200, TKAN
250, and TKAN 300 have two screw axles for ejecting ash each.
A very important notice regarding the construction of TKAN industrial boilers is that it also
enables additional equipment. The additional equipment is ordered prior to the boiler delivery, some
elements can be additionally installed on spot, and some of them have to be factory installed.
Additional equipment elements are:
-
Larger daily silos are next to the boiler.
Standard silos (picture 2) are listed in the table with
dimensions, however, if a buyer has more space in the boiler room and prefers a larger, so-called
daily silo in special dimensions, it is possible to order one made by Radijator inzenjering. The delivery
of this silo is possible additionally after the boiler is already placed in the boiler room.
-
Multi-day containers for pellets.
It is also possible to deliver silos of tens of tons in capacity and which
are connected to a small daily silo with the screw conveyor system. Loading these silos is done from a so-called
jumbo one-ton bag by bucket elevators. This equipment is also possible to be delivered additionally.