Total space of this openings is minimum 150cm² fro the boilers of the power of 50kW and for
the power over 50kW the space must be larger for another 2cm² per 1kW
.
A=150cm²+
)
50
(
2
2
kW
Q
kW
cm
n
−
n
Q
= possible power of over 50kW.
The lack of sufficient ventilation in the boiler room can cause more problems in the work of
boiler. Main problem is the inability to achieve high output water temperature i.e. the lack of
maximum power which leads to condensation in the boiler
.
•
Take into account the required minimum space required for access and security elements
to carry out cleaning operations
.
•
Determine whether the degree of electrical protection is in accordance with the
characteristics of the room where the boiler will be located
.
•
No exposure to atmospheric influences. The boiler itself is not anticipated for outdoor use
and contains no anti-freeze system
.
•
It is forbidden to close the vents in the boiler room in which the openings are necessary
for proper combustion
.