3.3. Boiler room
Boiler room must be secured against freezing
.
The support surface of the boiler in the boiler room must be of non-combustible material.
Recommended distance of all four sides of the boiler in relation to the boiler walls or other solid
body (water heater, etc.) are shown in
Figure 8.1
. These values allow a safe distance access
when firing, sufficient space for cleaning and easy access to fan and valve for filling and
emptying. Boiler at its left hand side should be away from the wall 300 mm. The space on the
right side of the boiler, which is recommended to be at least 800mm. The space on the back is
important for installation on hydraulic system, for cleaning, etc.
Boiler room must have
sufficient ventilation holes for fresh air as well as for the outlet of the exhaust air!
Figure 8.1 Positioning of boiler in the Boiler room