background image

Installation Manual 

SYSTEM BOILER  – Cod. 99951NA – November  2002

 

 

 

FLUE POSITION 

 
IMPORTANT:  THE FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN BS 
5440:1. 
The boiler MUST  be installed so that the terminal is exposed to the external air. 
It is important that the position of the terminal allows free passage of air across it at all times. 
If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance and that the terminal will 
not obstruct the passageway. 
In certain weather conditions a terminal may emit a plume of steam.  Positions where this would cause a nuisance should be avoided. 
IMPORTANT REQUIREMENT:  The correct dimensional relationship between the terminal and any obstruction, openable window or 
ventilator as shown in Fig 1 pag.7 It is ESSENTIAL TO ENSURE,  in practice, that products of combustion discharging from the terminal 
cannot re-enter the building, or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration, or 
forced ventilation/air conditioning systems.  If this should occur, the appliance MUST BE TURNED OFF IMMEDIATELY and the local gas 
region consulted. 
Where the lowest part of the terminal is fitted less than 2m (6.6ft) above a balcony, above ground, or above a flat roof to which people have 
access, the terminal MUST be protected by a purpose designed guard.  
Where the terminal is fitted within 850mm (34in) of a plastic or painted gutter, or 450mm (18in) of painted eaves, an aluminium shield of at 
least 1000 mm (40in)  long should be fitted to the underside of the gutter painted surface. 
The air inlet/products outlet duct and the terminal of the boiler MUST NOT be closer than 25mm (1in) to combustible material.

 

 

 
 
TERMINAL POSITION 

 

J

E

A

G

M

F

F

A

D

H,I

TOP VIEW REAR FLUE

D

G

L

K

G

N

B.C

TERMINAL 
ASSEMBLY

PROPERTY BOUNDARY LINE

300 min

 

 
A

  Directly below an openable window, air vent or any other ventilation opening. 

300  mm 

B

  Below gutter, drain pipes or soil pipes. 

25  mm  

C

  Below eaves. 

25  mm  

D

  Below balcony or carport roof. 

25  mm  

E

  From vertical drain pipes or soil pipes. 

25  mm  

F

  From internal or external corners. 

25  mm  

G

  Above adjacent ground, roof or balcony level. 

300  mm  

H

  From a surface facing the terminal. 

600  mm  

I

 

Facing the terminals. 

1200  mm  

J

  From opening (door, window)in the carport into dwelling. 

1200  mm  

K

  Vertically from a terminal on the same wall 

1500  mm  

L

  Horizontally from a terminal on the same wall 

300  mm  

M

  Above an opening, air brick, opening window etc. 

300  mm 

N

  Horizontally to an opening, air brick, opening window etc. 

300  mm 

Fig. 1 

Summary of Contents for RS 30 E

Page 1: ...Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED ONLY HEATING WALL HUNG BOILERS SYSTEM BOILERS Model RS 20 E RS 2...

Page 2: ......

Page 3: ...QUIREMENTS page 5 BOILER INSTALLATION page 7 ELECTRICAL CONNECTIONS page 9 15 16 BOILER CONTROL PANEL page 10 STARTING UP THE BOILER FOR THE FIRST TIME page 10 REGULATING THE GAS PRESSURE page 12 MULT...

Page 4: ...an expansion vessel 2 WARNINGS REGARDING INSTALLATION Warranty expires 12 months from date of installation and in all cases no later than 18 months from date of construction First start up must be pe...

Page 5: ...KCal h 9450 12900 14560 Kw 11 15 16 90 BTU hr 37498 51187 57774 Max working pressure heating bar 3 3 3 Max working pressure water bar 6 6 6 Min working pressure heating bar 0 3 0 3 0 3 Max heating tem...

Page 6: ...60 rotation It allows the flue exhaust into a flue duct and the air intake directly from an external wall N B To insert a bend in the flue reduce total flue length by 1 5 m R RETURN G GAS 1 2 F COLD W...

Page 7: ...tem with 360 rotation It allows the flue exhaust into a flue duct and the air intake directly from an external wall N B To insert a bend in the flue reduce total flue length by 1 5 m R RETURN G GAS 1...

Page 8: ...1988 Pipework that supplies the boiler must be a 22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the a...

Page 9: ...ulted Where the lowest part of the terminal is fitted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose desig...

Page 10: ...ary pipe connections WATER CONNECTIONS To facilitate installation the boiler is equipped with a fittings kit IMPORTANT Before connecting the heating system pipes carefully clean the system to prevent...

Page 11: ...e temperature falls to 5 C Heating sensor and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must b...

Page 12: ...r screws on the housing and open the electrical control box by lifting the cover as shown in fig 1 E With the electrical control box now open make the following connections Connect the yellow green wi...

Page 13: ...e gas cock and check the gas seals making sure the counter shows no sign of leaks in any case double check by using a soapy solution and eliminate all eventual leaks The checking procedure for the gas...

Page 14: ...gnition procedure in any case wait 3 minutes before turning the boiler off and on again then try to ignite it once more calibrate the boiler after carrying out this operation return the panel to its c...

Page 15: ...P1 MAX HEAT trimmer to the minimum heat by turning it counter clockwise regulate the minimum pressure by turning the P2 MIN GAS trimmer see the table below for calibration pressures on completion set...

Page 16: ...for gas leaks each time gas connections are dismantled and reassembled d replace the gas setting plate that indicates the type of gas and nominal pressure for the boiler When converting the boiler to...

Page 17: ...IRCULATING PUMP RSL 15 6 5 GAS VALVE VK4105 6 LT 6 EXPANSION VESSEL 7 3 BAR SAFETY VALVE 8 BURNER 13 R 9 BURNER 17 R 10 HEATING SENSOR 11 WATER PRESSURE SWITCH 12 WATER PRESSURE GAUGE 13 LIMIT THERMOS...

Page 18: ...CLOCK ROOM THERMOSTAT SUMMER WINTER SWITCH TA E I ER EA OR IMPORTANT RESPECT LIVE NEUTRAL POLARITY 19 POWER SUPPLY TERMINAL BLOCK 16 Switch E I IG 18 17 N L M2 7 5 6 9 8 PAC blue black TF 1 2 black br...

Page 19: ...10 R6 M7 RV C 35 M7 33 EV C3 RV D6 M7 32 26 LB M5 TL 8 7 6 5 4 3 1 2 24 M5 ROOM SEALED WIRING DIAGRAM RT LOW VOLTAGE CIRCUIT MAX HEAT MIN GAS T HEAT T SAN THERMOSTATS MODULATION BLOCK SPIA 1 BAR SPIA...

Page 20: ...ption in the instruction manual for the boiler When dismantling the boilers casing be careful when removing the side panels after having removed the front panel the side panels are removed by undoing...

Page 21: ...Installation Manual SYSTEM BOILER Cod 99951NA November 2002 18 SHORT LIST...

Page 22: ...TA02B101 B1203 Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH USER MANUAL Model RS 20 E 40 60 TYPE C ROOM SEALED Model RS 24 E 70 90 TYPE C ROOM SEALED...

Page 23: ...the boiler in efficient and safe operating condition carefully follow the instructions listed below Have normal maintenance performed at least once a year by one of our authorised service centres a fe...

Page 24: ......

Page 25: ...LET HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET E OE ALL RIGHTS...

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Reviews: