Radiant RMA Installation, Use And Maintenance Manual Download Page 18

Installation Manual  

Wall Hung Boiler with D.H.W. Storage Cylinder Low Nox – Cod. 99881NA – July 2001 

 

 

13 

BOILER ADJUSTMENTS 

 
 

 

 
 
 

 
 

 
 
 

 
 
 

 
 

 
 
 

 
 

 
 
 

 
 
 

 
 

 
 
 

 
 

SELECTOR

GPL-MET

NATURAL GAS

L.P.G.

SELECTOR

M5

M11

D6

+

C22

CM3

RS1

J16

R48

R2

3

R2

4

FA1

C2

0

C1

9

C7

C6

C2

1

R47

R17
R49

R1

5

R32

C13

41

R16

C14

R5

7

R6

1

R39

R62

M9

J20

C9

C5

+

R38

42

R31
R37

R1

8

IC2

+

R58

R42

ME

T

43

44

GP

L

R41

C26

+

R43

R4

0

C1

5

R5

6

R3

3

R22

45

46

J7

T4

R21

M13

R63

C25

61

D1

2

47

J21

R3

6

R34

48

D4

R5

9

R6

0

59

A

B

60

+

IC4

J10

+

RISC.

P2

J11

C24

TR1

R1

4

R9

R1

1

R7

+

R12

R8

C3

R1

3

C8

J9

+

C1

7

R10

C1

8

C4

+

C2

7

C1

6

R3

0

R2

8

R2

6

J12

M10

40

FASX4

FASX1

R46

IC1

36

R45

J9

38

R44

39

J15

35
37

R5

C1

2

C1

0

R2

0

FASX2

FASX3

R19

+

R3

R6

R1

R4

C11

J13

J18

CM4

M8

R2

34

33

J4

T3

R29

R25

T1

M14

64

+

+

+

J5

P3

M. RIS

P4

P5

T. RIS

RLA

62
63

32

31

D2

D3

RL4-RV

T2

R27

D1

P1 SAN.

RL2-RS

M7

30

29

D5

PTC1

57

CM1

PR

IM

A

R

IE

SECON

D

O

R

IE

52

53
51
49

50

J1

7

J6

D1

1

D1

0

D7

55

56

R5

5

RLA

54

58

R35

D8

IC3

R53

D9

R54

M1

22

RL3-RT

RL1-RP

J2

J4

24

J1

R5

0

23

25

26

28

27

M12

M6

R51

M4

14

15

16

18

19

17

J3

R52

21 20

FUSE 1

2AF

2

3

4

12

11

9

10

8

7

M2

13

C23

6

5

M3

1

SELECTOR

RLA - CM1

LINK

COMMUTATOR

CM3

LINK

S

TARTING STEP RLA P4

 

This trimmer is a slow ignition 

regulator and it is calibrated at 
minimum during factory test.  
Use a small screwdriver for any 

adjustments. Turn clockwise to 
increase gas pressure to the 
burner at start-up (by setting 

the trimmer to  maximum 
calibration pressure of 

modulator – see page 16). 
Turn counter-clockwise to 
decrease gas pressure to the 

burner at start-up (by setting 
the trimmer to the minimum 

pressure at start-up will 
correspond to minimum 
calibration pressure of 

modulator –see page 16). 
Through the RLA commutator 
you can verify the minimum 

gas pressure adjusted to the 
modulator. Remove the 

commutator from the MET-GPL 
selector located on the 
RAMIRE 2 circuit board and 

insert it on the RLA CM1 
selector located on the same 
circuit board. Once pressure on 

the gauge has been checked, 
remove the commutator and 

insert it on the MET-GPL 
selector. 

HEATING TIMER 

Delays start-up times of the various ignitions once 
the boiler has reached optimum temperature (the 

range of adjustment is from 0 to 6 minutes, the 
value set during testing at the factory, to 2.5 min.)

 

Use a screwdriver to adjust the delay time. Turn 

clockwise to increase time and counter-clockwise 
to decrease time down to zero.

 

MAXIMUM HEATING TRIMMER. 

The trimmer is calibrated at 80% of the 

max. rated output during factory testing. 
For the first ignition of the boiler, adjust 
according to heating power of the 

system. Use a screwdriver to adjust it. 
Turn clockwise to increase, counter-
clockwise to decrease.

 

THE SELECTOR 

MUST BE INSERTED 

INTO THE 

COMMUTATOR 

Summary of Contents for RMA

Page 1: ...BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION USE AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS WITH DOMESTIC HOT WATER STORAGE CYLINDER Model RMA TYPE B OPEN C...

Page 2: ......

Page 3: ...REQUIREMENTS page 6 BOILER INSTALLATION page 8 ELECTRICAL CONNECTIONS page 10 19 22 BOILER CONTROL PANEL page 11 STARTING UP THE BOILER FOR THE FIRST TIME page 11 BOILER ADJUSTMENTS page 13 MULTIGAS O...

Page 4: ...ADDING AN OPTIONAL TIMER SELF DIAGNOSTIC LEGEND see fig 2 6 OPERATING POWER INDICATOR 7 DOMESTIC HOT WATER OPERATION 8 HEATING OPERATION 9 FLASHING LIGHT DENOTING AIR PRESSURE SWITCH FAILURE 10 FLASH...

Page 5: ...re range can be adjusted from a minimum of 30 C to a maximum of 80 C REGULATING THE HOT WATER TEMPERATURE The hot water temperature is regulated by turning knob 4 see fig 1 pag I turn it counter clock...

Page 6: ...mogeneous highly functional unit that is easy to install and simple to operate The wall mounted boiler is equipped with all of the approved accessories required to make it a true independent heating p...

Page 7: ...ating unit has been constructed to heat the home and to produce hot water The constructor declines all responsibility for incorrect installation and or use of the device Do not leave the device on whe...

Page 8: ...KCal h 22950 23090 Kw 26 68 26 85 BTU h 91066 91621 Minimum rated output KCal h 12950 12900 Kw 15 06 15 BTU h 51386 51187 Heting temperature adjustment C 30 80 30 80 Max working pressure heating bar 3...

Page 9: ...ength by 0 8 m Kit B Double exhaust emission twin flue system with 360 rotation It allows the flue exhaust into a flue duct and the air intake directly from an external wall To insert a bend reduce to...

Page 10: ...ust fans into single chimney collective flues with natural draft or multiple combined flues follow the directions set out in the UNI 10640 standard CONNECTION OF FLUE PIPES All boilers must be connect...

Page 11: ...should ensure a nominal dynamic pressure of 20m Bar 8 in wg at the boiler Installation pipes should be fitted in accordance with BS6891 1988 Pipework from the meter to the boiler must be 22mm copper t...

Page 12: ...r sources of natural air infiltration or forced ventilation air conditioning systems If this should occur the appliance MUST BE TURNED OFF IMMEDIATELY and the local gas region consulted Where the lowe...

Page 13: ...nect pipes and valves as shown in the picture 5 Position the boiler paying attention to hang it to the hanging bracket do not lean the boiler on the JIG and make final connections WATER CONNECTIONS To...

Page 14: ...5 C Heating sensor and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost...

Page 15: ...d with the earth symbol see fig 3 connect the blue wire to the terminal marked with the letter N connect the brown wire to the terminal marked with the letter L CONNECTION OF ROOM THERMOSTAT NOTE use...

Page 16: ...s no sign of leaks in any case double check by using a soapy solution and eliminate all eventual leaks The checking procedure for the gas burner attachment is carried out with the boiler working make...

Page 17: ...ignition procedure press release button 2 see fig 1 pag 11 and then try the ignition procedure once again If the boiler does not start press the reset button 2 see fig 1 pag 11 IMPORTANT should the bo...

Page 18: ...crewdriver for any adjustments Turn clockwise to increase gas pressure to the burner at start up by setting the trimmer to maximum calibration pressure of modulator see page 16 Turn counter clockwise...

Page 19: ...to suit the type of gas used undo fixing nut 8 on the thin aluminium gas pipe 9 and change the jet g replace the gas setting plate that indicates the type of gas and nominal pressure for the boiler W...

Page 20: ...biliser Fig B Widen locking clips 2 Fig C Slide out the coil 1 located above the gas valve Fig D Tighten plastic screw 3 by turning it clockwise be careful not to break it Fig E Use a no 17 spanner to...

Page 21: ...hich when set on the top position towards the valve head allows the boiler operating on the domestic hot water circuit while when set on the low position the boiler operates on the central heating cir...

Page 22: ...ot water see fig 2 item B fig 3 It allows conversion to hot water even with a minimum hot water demand 2 litres min using an electromagnetic principle with electrical switching by means of a relay The...

Page 23: ...AUTOMATIC AIR VENT 18 HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 19 DRAINING TAP 20 WATER PRESSURE GAUGE 21 WATER PRESSURE SWITCH 22 HEATING SENSOR 23 HOT WATER SENSOR 24 3 WAY DIVERTER VALVE 25 FLOW...

Page 24: ...IR VENT 17 AUTOMATIC AIR VENT 18 HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 19 DRAINING TAP 20 WATER PRESSURE GAUGE 21 WATER PRESSURE SWITCH 22 HEATING SENSOR 23 HOT WATER SENSOR 24 3 WAY DIVERTER VA...

Page 25: ...5 LED6 RAVI II J2 D2 J3 FA1 C3 R48 C20 R49 R17 R23 R24 R47 R13 C8 J9 C6 C19 C21 C7 R15 R32 C13 R39 R37 R31 41 M9 R62 R61 R57 R16 42 C14 C9 R38 C5 RS1 J20 IC2 R18 IC1 R42 43 GPL 44 J7 46 45 R20 C12 R58...

Page 26: ...5A 2019 4 PS 5 TS LB 7 6 9 9 8 11 11 10 10 12 12 8 13 EA ER 14 15 P 6 ELECTRONIC TEMPERATURE INDICATOR 54 50 51 53 52 55 56 58 57 RVB RVA RV 2 1 3 7 23 19 24 17 18 22 IG VD R CY CX L 20 5 21 16 4 NET...

Page 27: ...F CONNECTORS 23 LED5 C6 C7 RS1 R58 R22 R21 4 2 1 3 15 14 22 LED2 LED1 LED3 LED4 RAVI II R31 42 R18 R17 yellow blue R48 FA1 C20 R49 R23 R24 R47 C19 C21 red brown R39 C9 M9 R62 R61 R57 J16 R38 C5 J20 R3...

Page 28: ...OSTAT FLOWSWITCH MICRO SWITCH M F TS HEATING SENSOR D H WATER SENSOR SR SS 3 WAY DIVERTOR VALVE WIRING CONNECTION ONLY FOR Mod VC6012 VD black black black black brown orange black black M F WATER PRES...

Page 29: ...water flow rate and temperature When dismantling the boiler casing be careful when removing the side panels after having removed the front panel the front panel is removed by undoing the lower and fr...

Page 30: ...g 1 on a replace it b re connect or replace it c replace it d change over polarity e make earth connection f fit conversion kit 4 Boiler on temperature rises rapidly and extinguishes flame light 2 fig...

Page 31: ...08LA 3 BAR PRESSURE RELIEF VALVE 1 2 16 96026LA D H W CYLINDER TEMPERATURE 90 PRESSURE 7BAR SAFETY VALVE 17 20030LA INSULATED 25 LT STORAGE CYLINDER 18 95006LA 10 LT EXPANSION TANK W BRACKET 19 96007L...

Page 32: ...6 Tel 39 0721 498822 Fax 39 0721 499815 Email tecnico radiant it italia radiant it export radiant it Internet http www radiant it All descriptions and illustrations contained in this leaflet have been...

Reviews: