REGULATION INSTRUCTIONS
TA05A140.A0307
28
5. REGULATING THE APPLIANCE
5.1 Parameters table
NOTES:
1 - Activate only for “heating only” boilers;
2 - If the heating system has more than one zone, an additional interface board (optional extra) must be installed on the
circuit board and parameter 15 set at 01;
3 - To install the telephone control, use non-polarised conductors connected to contact TA of the terminal board in
parallel with the remote control if fitted. Set the parameter 16 at 01.
4- When the parameter value 01/02/03 is set, parameters from no.17 to 22 are automatically activated and boiler
settings are carried-out in through these parameters (in Hz) that replace parameters from no.9 to no.
Once the parameter value has been set according to the boiler output, the P.C.B will automatically adjust the
maximum and minimum values.
PARAMETER N°
TYPE OF OPERATION
PARAMETER
VALUE
FUNCTION
1
Selects the type of boiler
00
01
02
Instantaneous
Boiler with storage tank
B. w/storage tank Comfort (+7°C)
2
Selects the type of gas
00
01
Natural gas
Lpg
3
Sets the central heating
temperature
00
01
Standard (30-80°C)
Reduced (25-40°C )
4
1
Selects pump mode during
heating phase
00
01
Standard ( 3’ pump overrun)
Permanent (pump runs continuously)
5
Water hammer prevention
00
01
Off
On
6
Central heating timer
00-90 (default = 36)
Delays the heating restart to prevent
frequent On/Offs, Expressed in steps of 5
sec (factory set at 36 x 5 = 180”)
7
Central heating pump overrun
timer
00-90 (default = 36)
The overrun timer can be modified.
Expressed in steps of 5 sec (factory set
at 36 x 5 = 180”)
8
(not applicable)
D.H.W. pump overrun timer
00-90 (default = 18)
The overrun timer can be modified.
Expressed in steps of 5 sec (factory set
at 18 x 5 = 90”)
9
Minimum gas pressure setting
-
Not applicable for premix boilers
10
Minimum central heating output
setting
-
Not applicable for premix boilers
11
Maximum gas pressure and
maximum central heating output
setting
-
Not applicable for premix boilers
12
Ignition sequence setting
-
Not applicable for premix boilers
13
(not applicable)
D.H.W priority function (2 min
delay on dhw function)
00
01
Off
On
14
4
Selects the type of burner
00
01
02
03
Atmospheric (not premix)
Premix 25 kW
Premix 29-34 kW
Premix 50 kW
15
2
Zone management board
activation
00
01
Off
On
16
3
Telephone control activation
00
01
Off
On
17
(not applicable)
Minimum fan speed setting
66 Hz (Metano)
60 Hz (GPL)
To set the minimum frequency value (Hz)
for the fan operation
18
(not applicable)
Maximum fan speed setting
162 Hz (Metano)
149 Hz (GPL)
To set the maximum frequency value
(Hz) for the fan operation
19
Minimum fan speed setting
(Central Heating)
66 Hz (Metano)
60 Hz (GPL)
To set the minimum frequency value (Hz)
for the fan operation in heating mode .
20
Maximum fan speed setting
(Central Heating)
162 Hz (Metano)
149 Hz (GPL)
To set the maximum frequency value
(Hz) for the fan operation in heating mode
21
Ignition sequence setting
90 Hz (Metano)
110 Hz (GPL)
To set the fan frequency value (Hz) at the
ignition
22
Fan frequency value display
00
01
Off
On (for 10 min. time)