9
R1K 34 - RAD - ING - Man.Inst. - 1901.1_firm.L224C_AHS
1 Av
ver
ten
ze ge
ne
rali pe
r l'ins
talla
zion
e_
Lo
cale
cald
aia_
con
d_
luo
go pa
rz. pr
ot_
AU
ST
RA
LIA
_E
N
1. INSTALLATION
INST
ALLER
to observe this caution will void the warranty of the
heat exchanger.
THIS BOILER HAS BEEN DESIGNED FOR OUTDOOR
INSTALLATION IN A PARTIALLY PROTECTED
LOCATION (SEE FIG.2 AT CHAPTER ‘POSITIONING
AND MINIMAL TECHNICAL SPACES’).
THIS BOILER IS ABLE TO OPERATE IN A PARTIALLY
PROTECTED PLACE, WITH SURROUNDING
TEMPERATURES WITHIN A MIN. OF -10 °C AND A
MAX. OF 60 °C.
WARNING
If the temperature in the boiler installation
location goes below -10° centigrades, please fill
the plant with anti-freeze liquid and insert and
electrical resistances kit (see chapter ‘ANTI-FREEZE
PROTECTION’).
WARNING
The manufacturer will not be held
responsible for damages caused by incorrect
installation not in conformity with the over mentioned
instructions and not protected adequately from the
freeze.
1.1.3. REFERENCE LEGISLATION
The installation must be realized according to
the requirements of current legislation and in
compliance with local technical regulations,
according to the indications of the good technique.
This appliance must be installed by an authorised
person in accordance with this instruction manual,
AS/NZS 5601 – Gas installations (installation and
pipe sizing), local gas fitting regulations, local
electrical regulations, local water regulations,
local health regulations, Building Code of Australia
and any other government authority.