2.1.2. BOILER COMMISSIONING
WARNING
Make sure that the system is correctly
filled.
Proceed with boiler commissioning as follows:
› Power the boiler.
THE START-UP SYSTEM WILL AUTOMATICALLY
ACTIVATE THE SYSTEM AIR RELIEF CYCLE
FUNCTION DISPLAYED ON SCREEN WITH CODE
“F33” (ONLY AT FIRST START-UP WILL LAST FOR
5 MINUTES*).
When function “F33” is active, the
pump is enabled and the burner start-up request
is disabled. The boiler can work normally only after
completing the operation.
› Open the gas tap.
› Use the button ‘
’ to select the desired
operation mode. If the symbol is displayed fixed,
it means that the function was activated.
› The burner will start as soon as the thermostat
contact is closed;
› if the flame is missing the board will repeat the
start-up operations after post-ventilation (20
seconds).
› You might have to repeat the start-up operation
several times to release all air inside the gas
tube. Before repeating the operation, wait at
least 5 seconds from the last start-up attempt
and unlock the boiler from “E01” error code by
pressing the Reset ‘
’ key.
(*) Only at the first start-up the system relief cycle
performed by the boiler lasts 5 minutes. After each water
pressure reset the boiler will automatically perform a
reduces system relief cycle, of 2 minutes. Throughout this
function the display will show the code “F33”. The boiler can
work normally only after completing the operation.