2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P16
CLIMATE COMPENSATION CURVE
(ONLY WITH EXTERNAL PROBE CONNECTED)
YOU CAN CONNECT AN EXTERNAL TEMPERATURE PROBE (SEE
CHAPTER ‘ELECTRICAL CONNECTIONS’) THAT AUTOMATICALLY
CHANGES THE DELIVERY TEMPERATURE BASED ON THE
EXTERNAL MEASURED TEMPERATURE. THE NATURE OF THE
CORRECTION DEPENDS ON THE THERMO-ADJUSTMENT VALUE
KD SET (SEE CHART).
THE SELECTION OF THE CURVE IS DETERMINED BY THE
MAXIMUM DELIVERY TEMPERATURE TM AND THE MINIMUM
EXTERNAL TEMPERATURE TE TAKING INTO ACCOUNT THE HOUSE
INSULATION DEGREE.
THE VALUES OF THE DELIVERY TEMPERATURES TM, REFER TO
STANDARD SYSTEMS 30-80 °C OR FLOOR SYSTEMS 25-45 °C. THE
SYSTEM TYPE CAN BE SET FROM PARAMETER P03.
0 - 30
(SET BY DEFAULT AT 15) THE
NUMBERING OF THE VALUE
CORRESPONDS TO ‘KD’ CURVES
ON THE CHART (SEE CHART
BELOW).
P17
BOILER LOADING SETPOINT DIFFERENTIAL
(ONLY FOR THE VERSION WITH REMOTE BOILER SUPPLY SYSTEM).
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO SET THE
PREVIOUS START VALUE FOR THE BOILER ACCORDING TO THE
SETPOINT OF THE DOMESTIC CIRCUIT SET BY THE USER.
3 - 15
VALUE EXPRESSED IN °C (PRE-SET
TO
5
°C)