2. FIRST START-UP
SUPPOR
T
CENTRE
2.1.5. DIGITECH CS PARAMETERS TABLE (MIAH406)
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P00
BOILER MODEL SELECTION
(CHANGE THE PARAMETER VALUE ON BOTH CONTROL PANELS,
MASTER AND SLAVE, PLEASE SEE CHAPTER "PARAMETER ACCESS
AND PROGRAMMING").
0 - 3
0 = R1K 18_24-R2K 24-R2KA 24 (IN
ALL VERSIONS)
1 = R1K 25_28-R2K 28-R2KA 28 (IN
ALL VERSIONS)
2 = R1K 34-R2K 34-R2KA 34 (IN ALL
VERSIONS)
3 = R1K 50 (FOR R1K 100 SET THE
VALUE ON BOTH UNITS)
P01
BOILER TYPE SELECTION
0 - 1
0 = WITH REMOTE BOILER SUPPLY
SYSTEM (PRE-SET BY DEFAULT
,
WITH DHW CIRCUIT MANAGED BY
MODBUS) TO CHANGE THE DHW
OPERATING MODE, CHANGE THE
VALUE OF THE PARAMETER P32.
1 = HEATING ONLY
P02
GAS TYPE SELECTION
ATTENTION:
READ THE INSTRUCTION IN CHAPTER ‘GAS TRANSFORMATION’
BEFORE CHANGING THIS PARAMETER.
0 - 1
0 = METHANE
1 = GPL
P03
SETTING THE HEATING TEMPERATURE
IN CASE OF DIRECT SUPPLY, BY A BOILER, OF A LOW TEMPERATURE
SYSTEM, INSTALL A SECURITY THERMOSTAT ON THE DELIVERY
WHICH INTERRUPTS THE OPERATION OF THE BOILER IN CASE
OF HIGH DELIVERY TEMPERATURE. THE COMPANY IS NOT HELD
LIABLE FOR RESULTING DAMAGES TO PERSONS OR THINGS DUE
TO THE NON-OBSERVANCE OF SUCH INDICATION.
0 - 1
0 = STANDARD (30-80 °C)
(SET BY DEFAULT)
1 = REDUCED (25-45 °C) FOR
FLOOR SYSTEMS