Cig-Arrête Master Flame Detector with Voice Alarm (Part No CSA-FDV)
Battery Operation Instructions
Remove detector head, by rotating anti-clockwise. Remove battery holder from the rear of detector. Insert 4 x good
quality AA alkaline batteries into battery holder - observing polarity and replace holder (or 1 x 9V PP3 battery) . Fix to
ceiling using appropriate fixing screws. Either accept factory default settings or configure as required and refit detec-
tor head and lock into position using anti-tamper screwdriver. Fit anti-vandal cage (part no. CSA-AVC2) if additional
protection is considered necessary.
Note: Detector can be locally powered if necessary, using optional plug-in daughter board. (see PIN CSA-DBD)
THE CSA-FDV DOES NOT FLASH ITS LED. THE ONLY TIME THE LED WILL FLASH IS WHEN THE DETECTOR HAS SENSED A FLAME,
AND WHEN THE DETECTOR HAS INITIATED AN ALARM CONDITION.
Installation
DO NOT INSTALL THE CSA-FDV IN AN EXTERNAL ENVIRONMENT WHERE RAIN CAN PENETRATE THE UNIT.
By default the stand alone module is factory set to DIP switch 2 and 8 in the ON position. (see table below for configu-
ration)
Voice Message No 1 –
“This is a no smoking area. Please extinguish your cigarette. Staff have been contacted.”
Full volume
Adjustable via potentiometer
1 message Play -
(DIP Switch 3 and 4 OFF)
Set for 4 x AA batteries - The preferred battery size due to longevity of the product (DIP Switch 8 ON)
Install the unit on a ceiling or on a wall in line with the operating parameters shown overleaf. Please ensure that the
sensing window is clean and free from dust and grease as this may affect the sensitivity of the unit. Test the unit by op-
erating a lighter within 6 metres. If the unit is sensing the flame the LED will flash and the unit will initiate an alarm.
Fault Indication
Low Battery
0.5 (S) blip, once every 150 seconds - high tone
Head Removal
0.5 (S) blip, once every 150 seconds - low tone
Specification
Temperature -10
to
+50
C
Humidity
0 – 95% non condensing
Operating Voltage
4 to 12V dc
Operating Current
60µA standby, 100mA during alarm
@6V dc
Battery Life based on quality DURACELL alkaline batteries
.
Note:
The life of the battery is dependant on the number of message plays. In areas
where smoking occurs frequently then utilise the D Cell battery box (Part No
CSA—EBB) or purchase a plug in power supply e.g. (Part No CSA—246)
Detector Sensitivity Adjustment
High Sensitivity
= SW1 ON + SW2 OFF + SW3 OFF
Normal Sensitivity = SW1 ON + SW2 ON + SW3 OFF
Low Sensitivity
= SW1 ON + SW2 ON + SW3 ON
SW4 Used only on CSA-FDV / R model (see separate installation guide)
1 2 3 4 5 6 7 8
Infra Red Remote
Enabled
ON
Disabled
OFF
Sound Output
Alert Tone
OFF
Speech
ON
Message Repeats
1
OFF OFF
(or tone)
3
OFF
ON
5
ON
OFF
Silent
(no tone or speech)
Relay On 20 Secs
ON
ON
Message Select
1
OFF OFF OFF
2
OFF OFF
ON
3
OFF
ON
OFF
4
OFF
ON
ON
5
ON
OFF OFF
6
ON
OFF
ON
7
ON
ON
OFF
Battery Monitor
9V Battery
OFF
6V Battery
ON
DIL SWITCH SETTINGS
Duracell
AA 6V
PP3 9V
D 6V
Capacity
2.85 A/hr
0.58 A/hr
15.00 A/hr
Standby Time
5 Years
1 Year
10 Years
Max No of Plays (10 secs)
10,000
2,000
50,000