Cylinder  Setting  Screen 
with  the  RACO  Tools 
Software: 

 
 
 

Display Functions: 

 

 

Absolute Position 

 

Status of Binary Inputs  

 

Reed Switch Diagnostic 

 

Angular Position 

 

Connection Status 

 

Sensor Head Alignment 

 
 

Input Functions: 

 
 

Stroke length of Actuator 

 

Relationship of Stroke length 

                   to Number of Rotations 
 

Set Counter Zero Position 

 

Clockwise or Counter 

                   Clockwise Direction 
 

Set Zero Position 

 

Read Parameters from EPS 02 

 

Write Parameters to EPS02 

 
 
 
 
 
 
 
 
 
 

 

Cylinder Setting 

The  first  screen  displays  the  essential 
functions of the EPS 02 and ties the actuator 
specific  parameters  to  the  sensor  unit.  In 
most  cases  the  following  parameters  are 
already  factory  set.  Starting  at  the  left  hand 
corner: 

Cylinder  max  Stroke:

  Nominal  stroke 

length  of  the  purchased  actuator  in 
millimeters. 

Number of Motor Turns for max Stroke:

 

This value represents the number of rotations 
at the EPS 02 sensor head to account for the 
full nominal stroke of the actuator. 

Clockwise 

or 

Counter 

Clockwise 

Direction: 

The  physical  location  of  the 

EPS02  position  sensor,  in  the  “A”  or  “D” 
accessory housing, “C” design or number of 
stages in the utilized gearbox if so equipped, 
decides the direction of rotation at the sensor 
head  in  relation  to  the  stroke  direction.  A 
counting  direction  will  be  selected  with  the 
radio buttons. 

External  Reference  Function: 

If  an 

external  reference  switch  is  used,  this 
selector  box  will  be  enabled.  The  positive 
edge of the external reference switch will set 
the absolute position to 0mm. 

Input Status Display Windows: 

The below 

six input status display windows indicate the 
binary input channel conditions: 

 

 
-  Push Button S1, S2 (EPS02 only) 
-  Input 1, 2; Time Delay Extend /  
                     Retract 
-  Input 3; External Reference Switch 
-  Over Temperature Switch

 

Set  Zero Position: 

In the center of the 

screen,  below  the  angular  rotation 
display,  the  set  zero  push  button  is 
located.  By  pushing  this  button  the 
absolute position will be set to 0mm and 
stored  in  the  battery  backed  up  RAM. 
The factory set zero position represents 
the physical retracted end position. This 
position should never be reached under 
normal operating conditions.  

Sensor Misaligned: 

If the distance or alignment between the 
sensor  head  and  the  rotating  magnet  is 
out of range the normally gray field will 
turn purple. 

Speed 0 RPM:

 Displays the RPM value 

on the sensor head. 

Read  Parameter  Block  /  Send 
Parameter  Block: 

By  pressing  the 

button read or send parameter block, the 
upload  or  download  RACO  Tool 
software  function  will  be  initiated  and 
all parameters will be exchanged via the 
USB  and  /  or  TTL  communication 
interface between the EPS 02 and  the  

Summary of Contents for EPS 02

Page 1: ...an be used Three on board LED s will guide the user through the initial setup procedure and will function thereafter as operation control signals Function The EPS 02 consists of two potential free rel...

Page 2: ...e hard wired into the reversing motor starter or VFD control circuit to provide reliable end of stroke protection Within the permissible stroke range of the actuator the contacts are closed Relay outp...

Page 3: ...om one function to the next Push button S2 is used to select the value in each of the selected function There are two settings which can be made independent from each other 1 Setting of the end of str...

Page 4: ...LED pattern will change to its normal operational condition See above LED Display section Manual Position Setting Diagram TTL Level Communication Interface The EPS02 is equipped with a TTL level comm...

Page 5: ...n to the stroke direction A counting direction will be selected with the radio buttons External Reference Function If an external reference switch is used this selector box will be enabled The positiv...

Page 6: ...the screen into the EPS02 the Send Parameter Block button needs to be pushed This refers to all configuration screens Reed switch sector The reed switch sector display block is for diagnostic and func...

Page 7: ...a negative and positive band around the selected switching point This number should be selected large enough to avoid shattering of the output signal and small enough to provide the desired position...

Page 8: ...ollowing selections can be made 0 10V 10 0V 0 20mA 20 0mA 4 20mA and 20 4mA Based on the selection Cylinder max Stroke from the main screen the Limits for Analog Output Signal slide bar is initialized...

Page 9: ...of the EPS06 As soon as the forward or reverse auxiliary contacts of the reversing motor contactor or VFD circuit are pulled in the on delay timer with the predefined Motor Rush in Time Delay Retract...

Page 10: ...he main cylinder setting screen changes from red to green Connection Problem Trouble Shooting The most common problem is the incorrect selection of the COM Port With the EPS02 EPS06 connected and powe...

Page 11: ...m Examples The EPS 02 limit switch contacts are hard wired into the reversing motor starter circuit The EPS 02 output signals are wired as permissive signals into the control circuit of a variable fre...

Reviews: