Regulation (EU) n° 517/2014 of 16/04/14 on fluorinated greenhouse gases and repealing Regulation (EC) n°
842/2006
Leak checks
1.
Operators of equipment that contains fluorinated greenhouses gases in quantities of 5 tons of CO
2
, equivalent or more
and not contained in foams shall ensure that the equipment is checked for leaks.
2.
For equipment that contains fluorinated greenhouse gases in quantities of 5 tons of CO2 equivalent or more, but of less
than 50 tons of CO
2
equivalent: at least every 12 months.
Picture of the equivalence CO
2
1.
Load in kg and Tons amounting CO
2
.
Load and Tons amounting CO
2
Frequency of test
From 7 at 75 kg load = from 5 at 50 Tons
Each year
Concerning the Gas R32, 7.40kg amounting at 5 tons of CO
2
, commitment to check each year.
Training and certification
1.
The operator of the relevant application shall ensure that the relevant personnel have obtained the necessary certification,
which implies appropriate knowledge of the applicable regulations and standards as well as the necessary competence in
emission prevention and recovery of fluorinated greenhouse gases and handling safety the relevant type and size of
equipment.
Record keeping
1.
Operators of equipment which is required to be checked for leaks, shall establish and maintain records for each piece
of such equipment specifying the followinginformation:
a)
The quantity and type of fluorinated greenhouse gases installed;
b)
The quantities of fluorinated greenhouse gases added during installation, maintenance or servicing or due to leakage;
c)
Whether the quantities of installed fluorinated greenhouse gases have been recycled or reclaimed, including the name
and address of the recycling or reclamation facility and, where applicable, the certificate number;
d)
The quantity of fluorinated greenhouse gases recovered
e)
The identity of the undertaking which installed, serviced, maintained and where applicable repaired or decommissioned
the equipment, including, where applicable, the number of its certificate;
f)
The dates and results of the checks carriedout;
g)
If the equipment was decommissioned, the measures taken to recover and dispose of the fluorinated greenhouse gases.
2.
The operator shall keep the records for at least five years, undertakings carrying out the activities for operators shall keep
copies of the records for at least five years.
Do no release R32 coolant liquid into the atmosphere. This is a fluoride greenhouse effect gas
covered by the Kyoto agreement with a global warming potential (GWP) = 675 - (see the
European Community regulations on fluoride greenhouse effect gases Regulation (EU) No
517/2014).
Summary of Contents for INVERTER 11
Page 1: ...POMPE CHALEUR DE PISCINE D RACER INVERTER NOTICE D INSTALLATION ET D UTILISATION...
Page 2: ......
Page 6: ...3 2 Dimension 2 1 Dimension Mod les RACER INVERTER 7 9 KW...
Page 7: ...4 Mod les RACER INVERTER 11 14 16 KW Mod les RACER INVERTER 19 KW 25KW...
Page 42: ...39 10 Sch ma clat et liste des pi ces d tach es 10 1 Mod le RACER INVERTER 7KW 9KW...
Page 45: ...42 10 2 Mod le RACER INVERTER 11KW 14KW 16KW...
Page 49: ...46 10 3 Mod le RACER INVERTER 19KW 25KW...
Page 53: ...50 Swimming Pool Heat Pump RACER INVERTER...
Page 57: ...54 2 Dimension 2 1 Dimension RACER INVERTER 7 9 KW...
Page 58: ...55 RACER INVERTER 11 14 16 KW RACER INVERTER 19 KW 25 KW...
Page 87: ...84 2 3 The main interface...
Page 93: ...90 10 Exploded Diagram and spares parts list 10 1 RACER INVERTER 7KW 9KW...
Page 96: ...93 10 2 RACER INVERTER 11KW 14KW 16KW...
Page 100: ...97 10 3 RACER INVERTER 19KW 25KW...
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ...CASH PISCINES FRANCE 13 Avenue Neil Armstrong 33700 M rignac A0165RCI02...