background image

Page 3

06206-90(I)

 

 

Wind Speed Alarm (annunciator blinks)

ALr no

 

Speed alarm not armed 

 

YES

 

Speed alarm armed 

ALr 000

 

Alarm set-point. SELECT key increments value. 

 

 

ENTER key saves.

  

  

Alarm Delay Time

dLY 030

 

Alarm delay time in seconds (0-999). SELECT key

 

 

increments value. ENTER key saves.

    

  

Sound

Snd no

 

No sound

 

YES

 

Audible beep with alarm activations or average update.

  

Wind Direction Voltage Output Scale

dir 360

 

0-360 degrees

 

540

 

0-540 degrees

  

Test Functions

tSt no

 

No test

 

YES

 Test

tSt ALr

 

SELECT key closes alarm relays. 

CAL 0.00

 

SELECT key alternates between 0.00 and 

 

 

5.00 VDC output to calibrate external devices.

tSt dsP

 

SELECT key tests display sections.

OPERATION

ALARMS

Wind speed and direction alarms each have their own set-point, 

LED status indicator, and relay contacts. The Alarm Delay parameter 

establishes time duration in or out of the set-point range needed for 

the alarm to change state. Front panel LEDs indicate alarm status 

during operation.

LED Off 

=  Alarm not armed and OFF. Relay open

LED Steady 

=  Alarm armed and OFF. Relay open

LED Blinking  =  Alarm armed and ON. Relay closed. 

 

 

  Audible beep if Sound parameter is enabled.

AVERAGING

When averaging is enabled, the front-panel AVG annunciator is 

illuminated, and average wind speed and direction values are displayed 

at intervals set by the Period (PEr) parameter. When averaging is 

disabled, instantaneous wind values are displayed.

BRIGHTNESS

Adjust display brightness by pressing and holding the left BRIGHT 

key for 1 second.

MAXIMUM or WIND DIRECTION DISPLAY

Either MAXIMUM WIND SPEED GUST or numerical WIND 

DIRECTION appears during operation depending on Right Display 

Window (dSP) parameter setting. Maximum gust may be reset during 

normal operation by pressing and holding the RESET key for 1 second.

REMOTE  DISPLAYS

The Marine Wind Tracker may be configured as a remote display by 

setting the Sensor Input for serial input (InP=SEr) and connecting 

the RS-485 terminals to a source providing a $WIMWV NMEA wind 

speed and direction string. This may be any valid NMEA source 

including another Wind Tracker operating as a master, a Young wind 

sensor or interface sending the NMEA string, or a shipboard system.

With a Marine Wind Tracker as the NMEA source, use these settings:

MASTER: Sensor InP = any non-serial device.

REMOTE: Sensor InP = SEr

Connect one Wind Tracker master to up to 16 remote displays via 

the RS-485 terminals as shown in wiring diagrams. Remote Wind 

Trackers display exactly the same information as the master including 

alarm states. MAX RESET and all display features are controlled by 

the master unit only. Brightness can be adjusted independently at 

each Wind Tracker display.

VOLTAGE OUTPUTS

Calibrated voltage outputs for wind speed and direction are updated 

16 times per second. Wind Speed 0-100 m/s = 0.00 to 5.00 VDC. 

Wind Direction may be scaled for either 0-360 or 0-540 degrees = 

0.00 to 5.00 VDC by setting the Direction (dir) parameter.

4-20 mA INPUTS

The Wind Tracker accepts 4-20 mA Line Driver inputs with either 

0-50 m/s or 0-100 m/s scaling (Ldi and Ld2 input settings). Connect 

as shown in wiring diagram. The back-panel switch labeled 4-20 mA 

must be in the UP position. 24VDC power is recommended for most 

4-20 mA installations.

POWER CONNECTIONS

The Wind Tracker operates from a 12 to 30 VDC power source. 

Power may be connected via the coaxial jack or terminals. These 

are internally wired in together so DO NOT CONNECT MORE THAN 

ONE POWER SOURCE AT THE SAME TIME. See wiring diagrams 

for examples.

ERROR MESSAGES

Ldi Err

 

4-20 mA (line driver) signal is missing or outside 

an acceptable range. Verify connections, signal, 

and 4-20 mA switch in UP position.

SEr Err

 

Unit set to receive RS-485 serial signal (inP=SEr), 

but no serial data detected. Verify NMEA  source 

is working.  Verify connections.

Summary of Contents for 06206

Page 1: ...OGICAL INSTRUMENTS INSTRUCTIONS R M YOUNG COMPANY 2801 AERO PARK DRIVE TRAVERSE CITY MICHIGAN 49686 USA TEL 231 946 3980 FAX 231 946 4772 WEB www youngusa com PN 06206 90 REV I111215 WIND TRACKER MODE...

Page 2: ...IONS INDOOR USE ONLY Unless placed in approved enclosure Operating temperature range 0 50 C 32 122 F 0 95 RH Use only recommended power sources 12 30 VDC 3 5 W Disconnect power when connecting or serv...

Page 3: ...m s Hd Wind Monitor HD Ldi Line Driver 4 20mA input 0 50 m s Wind Speed Units annunciator blinks SPd unt SELECT key changes units ENTER to save NMEA Serial Output Rate Out FSt 16 times per second SLO...

Page 4: ...d Tracker may be configured as a remote display by setting the Sensor Input for serial input InP SEr and connecting the RS 485 terminals to a source providing a WIMWV NMEA wind speed and direction str...

Page 5: ...at his own expense This ISM device complies with Canadian CES 001 Cet apparei ISM est conforme a Ia norme NMB 001 du Canada EN55011 CISPR 11 Group 1 Class B device Class B equipment is suitable for u...

Page 6: ...Page 5 06206 90 I WIRING DIAGRAMS WIND SENSOR 05103 04101 03002...

Page 7: ...Page 6 06206 90 I WIRING DIAGRAMS...

Page 8: ...R SETTINGS Output Mode RS 485 Output Only Output Format NMEA Baud Rate 4800 SENSOR SETTINGS Output Mode RS 485 Output Only Output Format NMEA Baud Rate 4800 06206 Wind Tracker with Inp SEr in setup 06...

Page 9: ...Page 8 06206 90 I Master Remote Display Wiring Example WIRING DIAGRAMS...

Reviews: