Section V - Operating instructions
78
Quincy Compressor
Starting
Procedure
1. Open the air outlet valve. See section Introduction for its location.
2. Switch on the voltage.
3. Close all manual condensate drain valves.
4. Press the start button (1). The compressor starts running and automatic operation
LED lights up.
5. The regulator will automatically stop and start the compressor modules in function
of the air pressure.
6. On compressors with integrated dryer, the nominal pressure dew point will be
reached after a few minutes.
NOTICE!
The number of starts is limited to 30 starts per hour. See also section Programmable
settings.
During operation
Procedure
1. If the automatic operation LED (3) is alight, the regulator is automatically
controlling the compressor modules (starting/stopping).
2. Check the readings on the display (1). In case of a warning or shutdown condition,
see section Problem solving or Event history menu.