QHPR Installation & Operating Instructions

Installation

Ambient Air Temperature

Locate the dryer indoors where the 

ambient air temperature will be between 

40°F and 100°F. Intermittent operation 

at ambient temperatures up to 113°F will 

not damage the dryer but may result in a 

higher dewpoint or dryer shutdown due 

to high refrigerant discharge pressure (see 

Field Service Guide).
Do not operate air-cooled dryers at 

ambient air temperatures below 40°F. 

Such operation may result in low suction 

pressure, causing freeze-up.
Call your local distributor if prolonged 

operation at ambient temperatures above 

100°F or below 40°F is unavoidable.

Location and Clearance

Mount the dryer on a level base. Install 

the dryer in a clean, well-ventilated area to 

reduce fouling of the condenser coils with 

dirt and dust.
Wall Mounting - Dryer may be wall 

mounted by using an optional wall 

mounting bracket. Clearance must be 

maintained on all other sides as indicated.

LOCKING

CLIP STUD

EXISTING

INSTALLATION

NEW

INSTALLATION

DRYER

HANGER

Optional Wall Mounting Bracket

Vapors and contaminants corrosive to 

copper and aluminum must not be in the 

area of the dryer or air compressor intake. 

Allow at least 6 inches clearance from the 

front and from the condenser coil service 

access. Install the dryer with the frame 

level. Anchor bolts are not required.

System Arrangement

Liquid water in the inlet air will adversely 

affect the performance of the dryer. Install 

the dryer downstream of an aftercooler or 

separator so that the temperature of the 

dryer inlet air does not exceed 1°F and 

the inlet air does not contain any liquid 

water.
Most compressed air systems require 

filters for removal of solid and liquid 

contaminants. When an oil-removal filter 

is used, it should be installed downstream 

of the refrigerated dryer. The dryer will 

remove some entrained dirt, extending the 

life of the replaceable filter element. Outlet 

air temperature may be 10°F to 30°F 

higher than inlet air temperature. This is 

normal. Consult your distributor if a lower 

outlet air temperature is required.

COMPRESSOR

OIL REMOVAL
FILTER

AFTERCOOLER

AUTOMATIC DRAIN

DRYER

SEPARATOR

RECEIVER

Typical Compressed Air System

Piping and Connections

Piping must be furnished by the user 

unless otherwise specified. Connections 

and fittings must be rated for the maximum 

operating pressure given on the dryer 

data plate and must be in accordance 

with applicable codes. Support all piping; 

do not allow the weight of any piping to 

stress the dryer or filters. Inlet and outlet 

shutoff valves and a bypass valve are 

recommended. Piping should be at least 

the size of the inlet and outlet connections 

to minimize pressure drop in the air 

system. See Engineering Data section for 

dryer inlet and outlet connections.

 

Quincy Compressor-QHPR Series Dryers 

3

Summary of Contents for QHPR Series

Page 1: ...uction Manual This manual contains important safety information and should be made available to all personnel who operate and or maintain this product Carefully read this manual before attempting to o...

Page 2: ......

Page 3: ...Precautions 2 Receiving Unpacking and Moving 2 Installation 3 Instrumentation 4 Start up Operation 5 Shutdown 5 Maintenance 6 Returns to Manufacturer 7 Field Service Guide 7 Troubleshooting 8 Technica...

Page 4: ......

Page 5: ...urer must first be authorized by the manufacturer Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid Products repaired or replaced under warranty sha...

Page 6: ...ons for the requirements for breathing quality air Receiving Unpacking and Moving Receiving This shipment has been thoroughly checked packed and inspected before leaving our plant It was received in g...

Page 7: ...evel Anchor bolts are not required System Arrangement Liquid water in the inlet air will adversely affect the performance of the dryer Install the dryer downstream of an aftercooler or separator so th...

Page 8: ...for the appropriate particulate filter Electrical Connections The dryer is designed to operate on the voltage phase and frequency listed on the serial number tag Reference the tag prior to making an e...

Page 9: ...ation or call your local distributor b Confirm that condensate is discharging from the drain This can only be done when there is air flow through the dryer Reference Serial Number Tag for appropriate...

Page 10: ...enser coils Remove accumulated dust and dirt with a soft brush or with air from an OSHA approved compressed air nozzle that limits the discharge pressure to 30 psig General For continued good performa...

Page 11: ...e water downstream of the dryer and excessive pressure drop Most causes can be identified and remedied by following this guide Closed refrigeration systems are potentially dangerous Work on the refrig...

Page 12: ...ambient temperature Improper adjustment of Expansion Valve Remedy Replace float mechanism Check aftercooler discharge temperature and reduce to dryer design condition 122 F max Consult local distribut...

Page 13: ...ssible causes Dryer undersized may cause water downstream of dryer Blocked separator Dryer freezing up Remedy Check airflow and dryer capacity Reduce airflow or resize and replace dryer Dismantle clea...

Page 14: ...t Typeb R 134A R 134A MINIMUM MAXIMUM OPERATING CONDITIONS Min Max Inlet Air Pressure compressed air at inlet to dryer 30 250 psig 30 250 psig Min Max Inlet Air Temperature compressed air at inlet to...

Page 15: ...TER S M COMP 1PH C OVERLOAD PROTECTOR Air Refrigerant Flow Schematic HEAT EXCHANGER REHEATER AUX CONDENSER AIR OUTLET SEPARATOR EVAPORATOR CHILLER DRAIN OUTLET AIR INLET LIQUID RECEIVER FILTER DRYER R...

Page 16: ...seller freight prepaid for inspection Seller warrants repaired or replaced parts of its own manufacture against defects in materials and workmanship under normal use and service for ninety 90 days or...

Page 17: ...nd storage charges may be applied at the discretion of Seller Accounts past due shall bare interest at the highest rate lawful to contract for but if there is no limit set by law such interest shall b...

Page 18: ...___________________________ __________________________________________________________________________ __________________________________________________________________________ ______________________...

Page 19: ......

Page 20: ...2009 Quincy Compressor All Rights Reserved Litho in U S A Dryer Department 724 746 1100 SPXDocument 5003991 E mail info quincycompressor com Website quincycompressor com...

Reviews: