This parameter is currently valid only for Active Energy Total Import/Export (kWh), Reactive Energy Total (kvarh), Total Energy (kVAh)

 

Note: Device is reporting only if there was a change of 0.1 in EnergyNote: In the future will be possible to measure and report also Active Energy on PH1,
PH2 and PH3. 

 

Size: 2 Byte, Default Value: 600

Setting

Description

0

reporting disabled

600 - 65536

Reporting enabled. Report is send with the time interval set by entered value. Seconds

Parameter 43: Other Values - Reporting on time interval
This parameter is valid only for Voltage (V of ph1, ph2, ph3), Current (A of ph1, ph2, ph3), Total Power Factor, Total Reactive Power (var)

 

Note: Device is reporting only if there was a change 

 

Size: 2 Byte, Default Value: 600

Setting

Description

0

reporting disabled

600 - 65536

Reporting enabled. Report is send with the time interval set by entered value. Seconds

Parameter 100: Enable / Disable External IR relay (BICOM)
NOTE1: After parameter change, first exclude module (without setting parameters to default value) and then re include the module.NOTE 2: If you don‘t
have IR BICOM relay module mounted and you enable IR communication (parameter 100 is 1 or 2) there will be no valid IR relay state reported. It will be
reported IR COMMUNICATION ERROR and LED2 will BLINK. 

 

Size: 1 Byte, Default Value: 0

Setting

Description

0

External IR relay disabled

1

External IR relay enabled and connected to all 3 Phases

2

External IR relay enabled and connected to a Phase 1

Parameter 101: Enable / Disable External relay (IKA)
After parameter change, first exclude module (without setting parameters to default value) and then re include the module. 

 

Size: 1 Byte, Default Value: 0

Setting

Description

0

External relay disabled

1

External relay enabled and connected to Phase 2

Parameter 106: External IR relay (BICOM) power threshold settings – maximum power of all phases together
This parameter defines a threshold when External IR relay is being turned off. (If Parameter no. 100 is set to the value 1 or 2)

 

NOTE: Meter is capable of measuring max 3x65A! 

 

Size: 2 Byte, Default Value: 0

Setting

Description

0

no function

10 - 60000

Watt

Parameter 107: External relay (IKA) power threshold settings – maximum power on phase L2
This parameter defines a threshold when External relay is being turned off (if the parameter no. 100 is set to the value 1 or 2).

 

NOTE: Meter is capable of measuring max 65A 

 

Size: 2 Byte, Default Value: 0

Setting

Description

0

no function

10 - 20000

Watt

Parameter 112: Power threshold – Delay before power on
External IR relay/ External relay is turned off due to detected overload (as set by parameter 106&107) and remains off for a time, defined in this parameter.
After that time, the output turns on to check, if the overload is still present.

 

Summary of Contents for GOAEZMNHXD1

Page 1: ...ication it will communicate with other devices secure as long as this device provides the same or a higher level of security Otherwise it will automatically turn into a lower level of security to main...

Page 2: ...properly from this network Reset to factory default This device also allows to be reset without any involvement of a Z Wave controller This procedure should only be used when the primary controller i...

Page 3: ...re info please see Qubino catalogue Product ordering codes model numbers IKA232 20 230V 030 046 833 000 BICOM432 40 WM1 30 074 038 Inclusion Exclusion On factory default the device does not belong to...

Page 4: ...your life more comfortable We have prepared a few of them for you so you can get an idea for your next smart home project Of course there are countless of other options for how to use Qubino 3 Phase S...

Page 5: ...des Description 1 1 Lifeline Configuration Parameters Z Wave products are supposed to work out of the box after inclusion however certain configuration can adapt the function better to user needs or u...

Page 6: ...l BLINK Size 1 Byte Default Value 0 Setting Description 0 External IR relay disabled 1 External IR relay enabled and connected to all 3 Phases 2 External IR relay enabled and connected to a Phase 1 Pa...

Page 7: ...070683 IP Class IP 20 Voltage 3x 230 V 400V Load 65 A Device Type Smart Meter Firmware Version 01 00 Z Wave Version 04 3d Z Wave Product Id 0x0159 0x0007 0x0054 Supported Command Classes Basic Switch...

Page 8: ...ave devices into a network Exclusion is the process of removing Z Wave devices from the network Association is a control relationship between a controlling device and a controlled device Wakeup Notifi...

Reviews: